Toshiba Package Air Conditioner GBSC22414MUBZ Specifications

Model Name: GBSC22414MUBZ

Indoor Unit: AID-GP801BH

Outdoor Unit: ROA-RP2244HSZ

Branching Pipe: RBC-TRP100

Type: Ceiling-Embedded Inverter Heat Pump (Air-cooled)

Green Purchase Law Compliant

Performance Data

Cooling Performance

ItemUnitValue
Rated Cooling Standard CapacitykW20.0 (5.3~22.4)
Sensible Heat Ratio0.72
Rated Cooling Standard Energy EfficiencykW2.80 / 2.80 (50/60Hz)
Intermediate Cooling Standard CapacitykW9.0
Intermediate Cooling Medium Temperature CapacitykW9.5
Minimum Cooling Medium Temperature CapacitykW5.6

Heating Performance

ItemUnitValue
Rated Heating Standard CapacitykW22.4 (4.6~28.0)
Rated Heating Standard Energy Efficiency3.45 / 3.45
Intermediate Heating Standard CapacitykW10.1
Minimum Heating Standard CapacitykW5.7
Maximum Heating Low Temperature Capacity (Note 1)kW20.8

Energy Consumption Efficiency

ItemUnitValue
Annual Performance Factor (APF2015) (Note 5)(Cooling)5.0 / 5.0
(Heating)4.5 / 4.5
Average Cooling/Heating Energy Efficiency (APF2006)3.13 / 3.13

Electrical Characteristics

ItemUnitValue
Power SourceThree-phase 200V 50/60Hz
Fan Motor Rated OutputkW4.74
Compressor Motor Rated OutputkW4.74
Air Heat ExchangerFinned Tube
Refrigerant ControlElectronic Expansion Valve
FanPropeller Fan
High Pressure SwitchMPaOperating: 4.15, Reset: 3.20
Low Pressure SwitchMPa
Electrical Characteristics (Cooling)kW7.14 / 7.14
Electrical Characteristics (Heating)kW6.49 / 6.49
Intermediate Cooling StandardkW2.05 / 2.05
Intermediate Cooling Medium TemperaturekW1.75 / 1.75
Minimum Cooling Medium TemperaturekW0.760 / 0.760
Intermediate Heating StandardkW1.98 / 1.98
Minimum Heating StandardkW0.990 / 0.990
Maximum Heating Low TemperaturekW8.60 / 8.60
Operating Current (Cooling)A21.9 / 21.9
Operating Current (Heating)A19.9 / 19.9
Maximum CurrentA29.0 / 29.0
Starting CurrentA-
Power Factor (Cooling)%94 / 94
Power Factor (Heating)%94 / 94
Rated Noise (Sound Power Level) (Note 8)(Cooling) dB76
(Heating) dB77
Operating Noise (Sound Pressure Level) (Note 9)(Cooling) dB58
(Heating) dB61
IP CodeIPX4
Design Pressure High Pressure SideMPa4.15
Design Pressure Low Pressure SideMPa2.21
Refrigerant & Shipping ChargekgR32, 5.20
Maximum Piping Length without Refrigerant Additionm30
Refrigerant Addition Amountg/mBranch Piping: 40
Maximum Piping Length (Outdoor Unit Above)m30
Maximum Piping Length (Outdoor Unit Below)m30
Maximum Branch Piping Lengthm20
Maximum Difference in Branch Piping Lengthm10

Dimensions and Weight

ItemUnitValue
Outdoor Unit ModelROA-RP2244HSZ
Dimensions (Height)mm1,550
Dimensions (Width)mm1,010
Dimensions (Depth)mm370
Total Masskg141
Air Heat ExchangerFinned Tube
Sound and Heat Insulation MaterialExpanded Polystyrene / Polyethylene Foam
FanSirocco Fan
Airflow Rate (Note 6)m³/min20.0 / 18.3 / 16.8 / 15.7 / 13.5
MotorkW0.150
External Static PressurePa20.0
External Static Pressure Setting Range (Note 7)Pa20-30-40-50-65-80-100
Airflow Limit (Lower)m³/min11.3
Airflow Limit (Upper)m³/min24.0
Air FilterAttached to Indoor Unit
Operation Adjustment DeviceRemote Control Switch (Note 4)
Drain Pipe Diameter (Nominal)25 (PVC Pipe)
Rated Noise (Sound Power Level) (Note 8)dB(A)60/58/56/53/51
Operating Noise (Sound Pressure Level) (Note 9)dB(A)45/43/41/38/36

Electrical Installation

ItemUnitValue
Heater UnitNot Applicable
Power WiringSingle wire 1.6mm, Stranded wire 38.0mm² (Max 75m)
Circuit Breaker40A, 30mA, 0.1 sec or less (Note 10)
Handheld Switch CapacityA60
FuseA40
Wiring BreakerA40
Wire Diameter (Power Supply)Single wire 1.6mm x 3
Wire Diameter (Signal)Stranded wire 0.5mm² x 2
Power Supply Wiring Length (Max)m120m or less
Indoor Unit A/B Inter-unit WiringStranded wire 3.5mm² x 2
Indoor Unit A/C Inter-unit WiringStranded wire 3.5mm² x 1
Remote Control Cord(For connection to Indoor Unit A only) (Up to 500m) VCTF 0.5-2.0mm² etc.

Optional Parts

ItemValue
Remote ControllerRBC-AMSU52

Notes

  1. Cooling and heating performance, and electrical characteristics are values under temperature conditions specified by JIS B 8616:2015 and standard piping (equivalent piping length 7.5m (5m for P40~P63 models), 0m head difference). Values in <> indicate the capacity range.
  2. Power voltage should not exceed ±10% of the rated voltage.
  3. When using three indoor units with the same indoor unit, the values shown are per indoor unit.
  4. Remote control switches are sold separately. Refer to the 'Remote Controller Outline Drawing' for remote control cord wiring length.
  5. The Annual Performance Factor (APF) based on JIS B 8616:2006 is applied for the Annual Energy Consumption Efficiency according to the 'Judgment Standards for Manufacturers, etc. for Improving the Performance of Air Conditioners' (commonly known as the Energy Saving Law Standards) notified by the Ministry of Economy, Trade and Industry, Notification No. 213.
  6. Rated airflow is for 'Rapid' setting.
  7. External static pressure must be set on-site if changed.
  8. Rated noise (sound power level) is based on JIS B 8616:2015.
  9. Operating noise (sound pressure level) is based on JIS B 8616:2006.
  10. If the earth leakage circuit breaker is for ground fault protection only, a handheld switch + fuse, or a circuit breaker must be installed. Use a harmonic-compatible earth leakage circuit breaker.
  11. Depending on optional parts, the external dimensions, appearance, mass, operating noise, and performance characteristics of the air conditioner may change.

Document Number: T2525065Z 01

Manufacturer: Toshiba Carrier Corporation

PDF preview unavailable. Download the PDF instead.

GBSC22414MUBZ 仕様表 T2525065Z Microsoft Excel for Microsoft 365 Microsoft Excel for Microsoft 365

Related Documents

Preview Toshiba Package Air Conditioner GCSC22414MUBZ Specifications
Technical specifications for the Toshiba GCSC22414MUBZ package air conditioner, a multi-zone inverter heat pump system designed for ceiling suspension. Includes detailed performance data for cooling and heating, electrical characteristics, dimensions, and refrigerant information.
Preview Toshiba Package Air Conditioner Specifications - GCSC22414MUBZG
This document provides detailed specifications for the Toshiba GCSC22414MUBZG package air conditioner, a ceiling-suspended inverter heat pump system. It includes performance data, electrical characteristics, dimensions, sound levels, and refrigerant information.
Preview Toshiba Package Air Conditioner Specifications GCSB28014MUB
Technical specifications for the Toshiba GCSB28014MUB package air conditioner, a ceiling-suspended inverter heat pump system.
Preview Toshiba Package Air Conditioner Specifications - GCSC22414XU
Technical specifications for the Toshiba GCSC22414XU package air conditioner with wireless remote control, featuring heat pump technology and ceiling-suspended indoor units.
Preview Toshiba Package Air Conditioner Specifications - GDSB28014MUB
Technical specifications for the Toshiba GDSB28014MUB package air conditioner, a ceiling-embedded ducted type inverter heat pump system.
Preview Toshiba Package Air Conditioner Specifications - GDSB22414MUB
Technical specifications for the Toshiba GDSB22414MUB package air conditioner, a ceiling-embedded ducted inverter heat pump type. Includes details on cooling and heating performance, energy efficiency, electrical characteristics, dimensions, and refrigerant.
Preview Toshiba Package Air Conditioner GCSA22414MUB Specifications
Technical specifications for the Toshiba GCSA22414MUB package air conditioner, an air-cooled inverter heat pump ceiling-suspended type. Includes details on cooling and heating performance, energy efficiency, electrical characteristics, dimensions, and noise levels.
Preview Toshiba Package Air Conditioner GCSA22414MUBZG Specifications
Technical specifications for the Toshiba Package Air Conditioner, model GCSA22414MUBZG, an air-cooled inverter heat pump ceiling-suspended type. Includes performance data, electrical characteristics, dimensions, and noise levels.