Toshiba Package Air Conditioner Specifications
Model: GDSB28014MUB
Indoor Unit: AID-GP1401H
Outdoor Unit: ROA-RP2804HS
Branching Pipe: RBC-TWP102
Type: Ceiling-Embedded Ducted Type Inverter Heat Pump Air Conditioner (Dual Twin)
Cooling Performance
Rated Cooling Standard Capacity | kW | 25.0 (5.3 ~ 28.0) | ||
Sensible Heat Ratio | 0.82 | |||
Rated Cooling Standard Energy Efficiency | 2.38 / 2.38 | |||
Intermediate Cooling Standard Capacity | kW | 11.3 | ||
Intermediate Cooling Medium Temperature Capacity | kW | 11.6 | ||
Minimum Cooling Medium Temperature Capacity | kW | 6.3 |
Heating Performance
Rated Heating Standard Capacity | kW | 28.0 (4.6 ~ 35.0) | ||
Rated Heating Standard Energy Efficiency | 3.31 / 3.31 | |||
Intermediate Heating Standard Capacity | kW | 12.6 | ||
Minimum Heating Standard Capacity | kW | 7.0 | ||
Maximum Heating Low Temperature Capacity (Note 1) | kW | 22.2 |
Annual Performance Factor (APF)
APF 2015 (JIS B 8616:2015) | (Cooling) | 4.6 / 4.6 | ||
(Heating) | 4.3 / 4.3 | |||
Cooling/Heating Average Energy Efficiency | 2.85 / 2.85 |
Electrical Characteristics
Power Supply | 3-Phase 200V 50/60Hz | |||
Compressor Motor Rated Output | kW | 7.16 | ||
Air Heat Exchanger | Finned Tube | |||
Refrigerant Control | Electronic Expansion Valve | |||
Fan Motor | Propeller Fan | |||
High Pressure Switch | MPa | Operation: 4.15, Reset: 3.20 | ||
Low Pressure Switch | MPa | |||
Protection Devices | Discharge Temperature Sensor, Overcurrent Sensor, Compressor Thermistor, Case Heater | |||
Rated Noise (Sound Power Level) (Note 9) | (Cooling) dB | 78 | ||
(Heating) dB | 80 | |||
Operating Noise (Sound Pressure Level) (Note 10) | (Cooling) dB | 61 | ||
(Heating) dB | 63 | |||
IP Code | IPX4 | |||
Legal Refrigeration Ton | 4.39 | |||
Efficiency | (Cooling) % | 95 / 95 | ||
(Heating) % | 95 / 95 | |||
Starting Current | A | - / - |
Outdoor Unit Specifications
Model Name | ROA-RP2804HS | |||
Appearance | Silky Shade (Munsell 1Y8.5/0.5) | |||
Dimensions (Width x Depth x Height) | mm | 1,550 x 1,010 x 370 | ||
Total Mass | kg | 141 | ||
Compressor Type | Fully Hermetic | |||
Air Heat Exchanger | Finned Tube | |||
Fan Motor | Propeller Fan | |||
Rated Air Flow (Note 6) | m³/min | 0.200 + 0.200 | ||
Refrigerant Piping (Gas/Liquid) | mm | 25.4 / 12.7 | ||
Maximum Piping Length | m | 100 | ||
Maximum Height Difference | m | 30 (Outdoor unit above) / 30 (Outdoor unit below) | ||
Maximum Branching Pipe Length | m | 20 | ||
Maximum Branching Pipe Length Difference | m | 10 | ||
Fan Motor Output | kW | 0.350 | ||
External Static Pressure Setting Range (Note 7) | Pa | 50-75-100-125-150-175-200 | ||
Air Flow Limit (Lower) | m³/min | 18.3 | ||
Air Flow Limit (Upper) | m³/min | 42.0 | ||
Air Filter | Not included as standard. Prepare locally or use optional filter chamber, antibacterial high-performance filter, etc. (Note 8) | |||
Drain Pipe Diameter (Nominal) | 25 (PVC Pipe) | |||
Rated Noise (Sound Power Level) (Note 9) | dB(A) | 65 / 62 / 60 / 56 / 54 | ||
Operating Noise (Sound Pressure Level) (Note 10) | dB(A) | 42 / 40 / 38 / 36 / 35 |
Installation Specifications
Indoor Unit Model Name | AID-GP1401H | |||
Appearance | Silver (Hot-dip galvanized steel plate) | |||
Dimensions (Width x Depth x Height) | mm | 1,400 x 750 x 298 | ||
Total Mass | kg | 42 | ||
Air Heat Exchanger | Finned Tube | |||
Soundproofing Insulation Material | Foamed Polystyrene / Polyethylene Foam | |||
Fan Type | Sirocco Fan | |||
Air Flow (Fan Speed: Rapid/High+/High/Low+/Low) | m³/min | 35.0 / 31.7 / 28.3 / 25.0 / 23.0 | ||
Refrigerant Piping (Gas/Liquid) | mm | Gas: 15.9 / Liquid: 9.5 | ||
Maximum Piping Length (Outdoor unit to Branching pipe) | m | 100 | ||
Maximum Height Difference (Outdoor unit above/below) | m | 30 / 30 | ||
Maximum Branching Pipe Length | m | 20 | ||
Maximum Branching Pipe Length Difference | m | 10 | ||
External Static Pressure | Pa | 0.350 | ||
Fan Speed (Rapid/High+/High/Low+/Low) | Rapid / High+ / High / Low+ / Low | |||
Electrical Heater | Not applicable |
Electrical Wiring
Leakage Breaker (Note 11) | 50A, 30mA, 0.1sec or less | |||
Main Switch Capacity | A | 60 | ||
Fuse Capacity | A | 50 | ||
Circuit Breaker Capacity | A | 50 | ||
Power Wiring | Wire Gauge | Single wire 1.6mm, Single wire 2.0mm, Stranded wire 3.5mm², Stranded wire 5.5mm², Stranded wire 8.0mm², Stranded wire 14.0mm², Stranded wire 22.0mm², Stranded wire 38.0mm² | ||
Maximum Power Wiring Length (m) | 75m or less (Single wire 1.6mm x 3 wires), 120m or less (Stranded wire 3.5mm² x 2 wires) | |||
Interconnecting Wiring (Indoor A to Indoor B) | Separate cable (Signal wire: Stranded wire 0.5mm² x 2 wires) | |||
Remote Control Wiring | (Connect only to Indoor Unit A) (Up to 500m) VCTF0.5-2.0mm² etc. |
Optional Parts
Remote Control Switch | RBC-AMSU52 | |||
Remote Controller |
Notes
- (Note 1) Cooling and heating performance and electrical characteristics are based on temperature conditions according to JIS B 8616:2015, standard piping (piping equivalent length 7.5m (5m for P40~P63 models), 0m head), and are values at that time. Values in < > indicate the capacity range.
- (Note 2) Power supply voltage should not fluctuate by more than ±10%.
- (Note 3) When using two indoor units, the values shown are per indoor unit.
- (Note 4) Remote control switch is an optional part. Refer to the "Remote Control Outline Drawing" for remote control wiring length.
- (Note 5) The Annual Performance Factor (APF) for the "Energy Saving Act Standard Value" based on the Ministry of Economy, Trade and Industry Notification No. 213 "Manufacturing Business Operators' Judgment Standards for Improving Air Conditioner Performance" (commonly known as the Energy Saving Act Standard) applies APF (JIS B 8616:2006).
- (Note 6) Rated air flow is for "Rapid" speed.
- (Note 7) External static pressure needs to be changed on-site.
- (Note 8) Air filters are not included as standard. Prepare locally or use optional filter chambers, antibacterial high-performance filters, etc.
- (Note 9) Rated noise (sound power level) is a value based on JIS B 8616:2015.
- (Note 10) Operating noise (sound pressure level) is a value based on JIS B 8616:2006.
- (Note 11) If the leakage breaker is for ground fault protection only, install a main switch + fuse or a circuit breaker. Use a harmonic-compatible leakage breaker.
- (Note 12) Depending on the optional parts, the external dimensions, appearance, mass, operating noise, and performance characteristics of the air conditioner may change.
Manufacturer Information
Toshiba Carrier Corporation
Model Number: T2525071 01