Toshiba Package Air Conditioner Specifications
Model Name (Indoor Unit): AIC-GP1121H x2
Model Name (Outdoor Unit): ROA-RP2244HSZG
Model Name (Branching Pipe): RBC-TWP102
Product Type: Ceiling Suspended Inverter Heat Pump Air Conditioner
Green Purchase Law Compliance: Compliant
Outdoor Unit Specifications
Item | Specifications | Unit | Details |
---|---|---|---|
Model Name | ROA-RP2244HSZG | ||
Exterior Finish | Silky Shade (Munsell 1Y8.5/0.5) | ||
Dimensions (Height) | 1,550 | mm | |
Dimensions (Width) | 1,010 | mm | |
Dimensions (Depth) | 370 | mm | |
Total Mass | 141 | kg | |
Compressor Type | Fully Sealed | ||
Compressor Motor Rated Output | 4.74 | kW | |
Refrigerant Control | Electronic Expansion Valve | ||
Fan Type | Propeller Fan | ||
Power Supply | Three-phase 200V 50/60Hz | ||
High Pressure Switch | Operates: 4.15 MPa, Resets: 3.20 MPa | MPa | |
Low Pressure Switch | MPa | ||
Protective Devices | Discharge Temperature Sensor, Overcurrent Sensor, Compressor Thermistor | ||
Case Heater | 152.5 | W | |
Refrigerant (Shipping Charge) | R32: 5.20 | kg | |
Maximum Piping Length (Refrigerant Addition Not Required) | 30 | m | |
Refrigerant Addition Rate | Main Piping: 40 g/m, Branch Piping: 40 g/m | g/m | |
Maximum Piping Length (Branch Pipe) | 100 | m | |
Maximum Height Difference (Branch Pipe) | Outdoor unit above: 30 m, Outdoor unit below: 30 m | m | |
Maximum Length Difference (Branch Pipe) | 20 | m | |
Leakage Breaker | 40A, 30mA, 0.1 sec or less | ||
Main Switch Capacity | 60 | A | |
Fuse Capacity | 40 | A | |
Circuit Breaker Capacity | 40 | A | |
Power Cable Conductor Size | Solid: 1.6mm², Solid: 2.0mm², Stranded: 3.5mm², Stranded: 5.5mm², Stranded: 8.0mm², Stranded: 14.0mm², Stranded: 22.0mm², Stranded: 38.0mm² | (24/24, 43/43, 68/68, 118/118) | |
Power Cable Length (Max) | Solid: 1.6mm² x3 (75m or less), Stranded: 3.5mm² x2 (120m or less) | m | |
Connecting Cable (Outdoor-Indoor) | (Power): Solid 1.6mm² x2, (Signal): Stranded 0.5mm² x2 | ||
Remote Control Cord | (Connected to Indoor Unit A only) VCTF 0.5-2.0mm² x2 (up to 500m) |
Indoor Unit Specifications
Item | Specifications | Unit | Details |
---|---|---|---|
Model Name | AIC-GP1121H | ||
Exterior Finish | Pure White (Munsell N9.1) | ||
Dimensions (Height) | 235 | mm | |
Dimensions (Width) | 1,586 | mm | |
Dimensions (Depth) | 690 | mm | |
Total Mass | 38 | kg | |
Air Heat Exchanger | Finned Tube | ||
Sound Insulation/Insulation Material | Polystyrene foam, Polyethylene foam | ||
Fan Type | Sirocco Fan | ||
Standard Airflow Rate (Fan Speed Settings) | 31.0 / 23.7 / 22.5 / 18.0 / 17.0 | m³/min | (High/Strong+/Strong/Weak+/Weak) |
Fan Motor Output | 0.139 | kW | |
Air Filter | Included with indoor unit | ||
Operation Control Device | Remote control switch | (Sold separately) | |
Drain Diameter (Nominal) | 20 (PVC pipe) | ||
Rated Noise (Sound Power Level) | 59 / 54 / 53 / 48 / 47 | dB(A) | (High/Strong+/Strong/Weak+/Weak) |
Operating Noise (Sound Pressure Level) | 44 / 39 / 38 / 33 / 32 | dB(A) | (High/Strong+/Strong/Weak+/Weak) |
Performance Data
Category | Standard Cooling Capacity | Sensible Heat Ratio | Unit | Details |
---|---|---|---|---|
Cooling Performance (Rated Standard) | 20.0 | 0.78 | kW | (5.3~22.4) |
Cooling Performance (Rated Standard Energy Efficiency) | 3.28 / 3.28 | |||
Cooling Performance (Intermediate) | 9.0 | kW | ||
Cooling Performance (Intermediate - Mid-Temp) | 9.5 | kW | (Note 1) | |
Cooling Performance (Minimum) | 5.6 | kW | ||
Heating Performance (Rated Standard) | 22.4 | 3.92 / 3.92 | kW | (4.6~28.0) |
Heating Performance (Intermediate) | 10.1 | kW | ||
Heating Performance (Minimum) | 5.7 | kW | ||
Heating Performance (Maximum - Low Temp) | 20.5 | kW | (Note 1) | |
Annual Performance Factor (APF 2015) | 5.8 / 5.8 | (JIS B 8616:2015) | ||
Annual Performance Factor (APF 2006) | 5.2 / 5.2 | (JIS B 8616:2006) | ||
Cooling Power Consumption (Rated Standard) | 6.10 / 6.10 | kW | ||
Cooling Power Consumption (Intermediate) | 1.67 / 1.67 | kW | ||
Cooling Power Consumption (Intermediate - Mid-Temp) | 1.46 / 1.46 | kW | ||
Cooling Power Consumption (Minimum - Mid-Temp) | 0.680 / 0.680 | kW | ||
Heating Power Consumption (Rated Standard) | 5.72 / 5.72 | kW | ||
Heating Power Consumption (Intermediate) | 1.71 / 1.71 | kW | ||
Heating Power Consumption (Minimum) | 0.930 / 0.930 | kW | ||
Heating Power Consumption (Maximum - Low Temp) | 9.15 / 9.15 | kW | ||
Operating Current (Cooling) | 18.7 / 18.7 | A | ||
Operating Current (Heating) | 17.6 / 17.6 | A | ||
Operating Current (Maximum) | 28.4 / 28.4 | A | ||
Power Factor (Cooling) | 94 / 94 | % | (Note 1) | |
Power Factor (Heating) | 94 / 94 | % | (Note 1) | |
Starting Current | - | A | ||
Design Pressure (High Side) | 4.15 | MPa | ||
Design Pressure (Low Side) | 2.21 | MPa |
Piping Specifications
Item | Specifications | Unit | Details |
---|---|---|---|
Gas Pipe Diameter (Outdoor Unit - Indoor Unit) | 25.4 | mm | |
Liquid Pipe Diameter (Outdoor Unit - Indoor Unit) | 9.5 | mm | |
Gas Pipe Diameter (Branch Pipe - Indoor Unit) | 15.9 | mm | |
Liquid Pipe Diameter (Branch Pipe - Indoor Unit) | 9.5 | mm |
Notes
- (Note 1) Cooling and heating performance, and electrical characteristics are based on JIS B 8616:2015 temperature conditions and standard piping (equivalent piping length 7.5m for P40-P63 models, 5m; head difference 0m). Values in < > indicate the performance range.
- (Note 2) Power supply voltage should not fluctuate by more than ±10%.
- (Note 3) When two indoor units are used with the same indoor unit, the displayed values are per indoor unit.
- (Note 4) Remote control switch is a separately sold item. Refer to the remote control external view diagram for remote control cord wiring length.
- (Note 5) The Annual Performance Factor (APF) according to the Ministry of Economy, Trade and Industry Notification No. 213 "Criteria for Manufacturers etc. for Improving Air Conditioner Performance" (commonly known as the Energy Saving Law standard) applies to "APF (JIS B 8616:2006)".
- (Note 6) Rated noise (sound power level) is based on JIS B 8616:2015.
- (Note 7) Operating noise (sound pressure level) is based on JIS B 8616:2006.
- (Note 8) Rated airflow is for "High" fan speed.
- (Note 9) If the leakage breaker is for ground fault protection only, install a main switch + fuse or a circuit breaker. Use a harmonic-aware leakage breaker.
- (Note 10) Depending on separately sold items, the external dimensions, appearance, mass, operating noise, and performance characteristics of the air conditioner may change.