Elitech MS-100 Digital Manifold
User Manual and Technical Specifications
1. DESCRIPTION
The MS-100 digital manifold integrates pressure reading, evaporation and condensation temperature indication, refrigerant list, leak testing, and vacuum process functionalities into a single instrument. It offers the capability to transmit all this information via Bluetooth to the Elitech Tools application. Pressure readings (high and low), evaporation and condensation temperatures of the selected refrigerant are displayed on the screen, facilitating instrument use and speeding up processes.
1.1 General Indications
The instrument features:
- 1. LCD Display
- 2. Configuration Keys
- 3. Liquid Sight Glass
- 4. High and Low Pressure Valves
- 5. Hose Holder
- 6. Refrigerant Charging and Recovery Connection (1/4" SAE)
- 7. Suspension Hook
- 8. Battery Compartment (2 AAA batteries)
- 9. General Instrument Information (QR code for serial number)
1.2 Safety Instructions
- 10. Do not use this instrument for maintenance on systems where the refrigerant is ammonia.
- 11. This product contains internal batteries. Do not expose the product to high temperatures or near fire, as there is a risk of explosion.
- 12. Strictly comply with the safety instructions of the refrigeration system.
- 13. Use protective equipment such as gloves and goggles when handling this instrument. Before connecting it to the system, carefully read the refrigeration system maintenance manual.
- 14. In case of damage to the instrument, contact Elitech.
- 15. It is strictly forbidden to disassemble the product, as it may be damaged, potentially leading to battery combustion and consequent physical harm.
1.3 Environmental Protection
- 1. Comply with local environmental protection policies. Refrigerants cannot be released directly into the atmosphere; professional companies must be used for recycling.
- 2. At the end of its lifespan, the product must be recycled according to local regulations. If in doubt, contact Elitech.
- 3. Send discharged batteries to a battery collection point.
2. TECHNICAL SPECIFICATIONS
Pressure Measurement Range | -14psi to 800psi |
Pressure Reading Accuracy | ±1% FS |
Resolution | 1psi |
Units of Measurement | Pressure: psi, kPa, MPa, bar, inHg Temperature: °C, °F |
Refrigerant Types | The device stores up to 18 types of refrigerants in its memory, which can be updated via the Elitech Tools application. |
Refrigerants Stored in Memory:
R11, R12, R13, R22, R290, R32, R134a, R404A, R410A, R407C, R408A, R409A, R458A, R448A, R449A, R500, R502, R600
Selectable via Elitech Tools Application:
R11, R113, R114, R115, R116, R12, R123, R1233zd, R1234yf, R1234ze, R124, R125, R13, R134a, R14, R141b, R142b, R143a, R152a, R161, R170, R21, R218, R22, R227EA, R23, R236EA, R236fa, R245fa, R290, R32, R40, R401A, R401B, R401C, R402A, R402B, R403A, R403B, R404A, R405A, R406A, R407A, R407B, R407C, R407D, R407E, R407F, R408A, R409A, R409B, R41, R410A, R410B, R411A, R411B, R412A, R413A, R414A, R414B, R415A, R415B, R416A, R417A, R417B, R417C, R419A, R419B, R420A, R421A, R421B, R422A, R422B, R422C, R422D, R422E, R423A, R424A, R425A, R426A, R427A, R428A, R429A, R430A, R431A, R432A, R433A, R433B, R433C, R434A, R435A, R436A, R436B, R437A, R438A, R439A, R440A, R441A, R442A, R443A, R444A, R444B, R445A, R446A, R447A, R448A, R449A, R449B, R450A, R451A, R451B, R452A, R452B, R452C, R453A, R454A, R454B, R454C, R455A, R456A, R457A, R458A, R50, R500, R502, R503, R504, R507A, R508A, R508B, R509A, R510A, R512A, R514A, R600, R600a, R601, R601a, R717, R718, R720, R728, R732, R740, R744
Hose Connection | 1/4" SAE |
Power Source | 2 x 1.5V AAA Batteries |
Battery Life | Approx. 200 hours (display with backlight off) |
Display | LCD Display |
Product Dimensions | 110 x 75 x 135 mm |
Weight | Approx. 800g |
Operating Temperature | -10°C to 50°C (14°F to 122°F) |
Storage Temperature | -20°C to 60°C (-4°F to 140°F) |
Bluetooth Range | 20 m (unobstructed) |
Note: The list of selectable refrigerants via the application will be updated and available through the Elitech Tools app.
3. KEY FUNCTIONS
On/Off and Bluetooth
- 1. Press and hold: Turns the device ON/OFF.
- 2. Single press: Activates/Deactivates Bluetooth.
Zero/Up + Down/Play Simultaneously
Press and hold for 3 seconds to access the refrigerant selection function. The refrigerant selection will automatically exit after 10 seconds.
Mode + Down/Play Simultaneously
Single press: Alternates between leak test and vacuum process modes.
Mode
- 1. Press and hold: Accesses/Exits the configuration interface.
- 2. Single press: Navigates through configuration options.
Down/Play - Stop
- 1. Press and hold: Returns to the previous process (leak test, vacuum) or manually ends these processes.
- 2. Single press: Changes the selected refrigerant / Navigates through functionalities.
Zero/Up
- 1. Press and hold: Sets the pressure reading to zero.
- 2. Single press: Changes the selected refrigerant / Navigates through functionalities.
4. CONNECTIONS TO THE REFRIGERATION SYSTEM
1. Press the key once to turn on the device.
2. Enter the pressure and temperature measurement interface. Press and hold the keys [Zero/Up] and [Down/Play] simultaneously to select the refrigerant (list stored in the instrument).
3. The refrigerant indication will flash. Press the [Down/Play] or [Zero/Up] key once to choose the refrigerant to be used.
4. Connect the hose to the high or low-pressure side, according to the task.
5. Start the process and monitor pressure and temperature data in real-time on the instrument's display or via the Elitech Tools app.
5. OPERATION
5.1 Preparation and Measurement
- Press the [On/Off] key to turn on the instrument and enter the main screen.
- Zero the pressure sensor reading:
NOTICE! Perform the pressure sensor reading adjustment before each new measurement. This action ensures the instrument always has the lowest possible reading deviation. Perform this process with the hoses disconnected from the refrigeration system.
- Connect the refrigerant hose.
NOTICE! The low-pressure (blue) and high-pressure (red) hoses should be connected to the instrument and the refrigeration system, respectively.
- Define the refrigerant to be used by pressing and holding the [Zero/Up] and [Down/Play] keys simultaneously. To replace the previously selected refrigerant, press the [Down/Play] or [Zero/Up] keys once.
5.2 Pressure and Temperature (PT) Measurement Mode
After selecting the refrigerant, the display will show the measured low and high pressures (PL and PH), as well as the evaporation and condensation temperatures (Ev and Co) based on Pressure x Temperature calculations.
Note: The instrument does not have an external temperature sensor (clamps); indications are based on Pressure x Temperature calculations.
Image 1 - Main Screen
5.3 Leak Test Mode (HOLD)
Note: This functionality needs to be purchased through the Elitech Tools application, as detailed in section 6.4.
- Connect the hose to the high-pressure side of the manifold and then to the system under test, with the low-pressure valve closed.
NOTICE! The high-pressure side of the manifold is the connection point for the leak test.
- Adjust for the leak test: Press the [Mode] + [Down/Play] keys simultaneously.
- Define leak test parameters:
- Target Pressure Value: Configure the pressure value to be used as the baseline for the process. An audible alarm will indicate when the pressure reaches this value.
- Percentage of Loss: Configure the tolerable pressure loss percentage (based on the target value). An alarm will indicate if the pressure loss exceeds this percentage.
- Temperature Compensation: Enable/disable the temperature compensation functionality.
- Test Duration: Set the duration of the test.
- System Charging: Charge the system with nitrogen according to the configured target pressure value. An alarm will indicate when the pressure reaches this value.
Note: Press any key to temporarily disable the audible alarm.
- Start Leak Test: Press the [Down/Play] key once to begin the countdown as configured by the app. The instrument will monitor the percentage of loss and emit an audible alarm if the set value is reached.
Image 2 & 3 - Leak Test Interface
6.2 Leak Test Failure: If the leak test completes with a loss percentage exceeding the set value, or if this percentage is reached during the process, an audible and visual indication will be emitted by the instrument.
6.3 Manual Stop of Leak Test: Press and hold the [Down/Play] key to manually end the leak test.
7. Exit Leak Test Screen: Press and hold the [Mode] key to exit the leak test screen.
Note: For the Temperature Compensation function to be inactive, it must be disabled in the instrument's settings (TC) or via the Elitech Tools application.
5.4 Vacuum Measurement Mode (VAC)
Note: This functionality needs to be purchased through the Elitech Tools application, as detailed in section 6.4.
- Connect the hose to the high-pressure side of the manifold and then to the system under test, with the low-pressure valve closed.
- Enter Vacuum Mode: Press the [Mode] + [Down/Play] keys simultaneously.
- Connect the hose to the high-pressure side of the manifold and then to the system under test, with the low-pressure valve closed.
- Turn on the vacuum pump to start the process.
Note: When the system pressure is below atmospheric pressure, the manifold display will show the vacuum percentage relative to the maximum possible measurement (-14.5psi). For example, -7.2psi represents 50%. Before starting the measurement, the screen will indicate the process time, pressure, and percentage.
- Once on the vacuum process screen, press and hold the [Down/Play] key for a few seconds to start the process, measurement, and time count as programmed.
Note: The pressure sensor used for the vacuum process is intended only as a reading reference.
Image 7 - Vacuum Process Interface
5.5 Offline Data Recording Mode
The offline data recording mode allows storing readings, date, and time on the device itself. Data can be activated, downloaded, and exported via Bluetooth connection to the Elitech Tools app.
Note: This functionality needs to be purchased through the Elitech Tools application, as detailed in section 6.4.
- Connect the device to the application and enter the main "Dashboard" screen.
- Click on "Setting", then on "Record Function".
- Recording Interval: Select the data saving interval.
- Start Recording: Enable/disable data recording. When enabled, the icon will appear as shown in Image 8.
NOTICE! The device can store up to 3000 data records.
- End Recording: Access "Record Function" again and click "Log off".
- Read Historical Data: Click to download the data stored by the instrument.
- Clear Stored Data: Click to erase the data stored on the instrument.
5.6 Configuration Mode
- Access Settings: Press and hold the [Mode] key to access the configuration menu (Image 9).
- Navigate Settings: Press the [Down/Play] or [Zero/Up] key to select an option.
- Modify Settings: Press the [Down/Play] or [Zero/Up] keys to adjust the desired value.
- Exit Settings: Press and hold the [Mode] key.
5.6.1 Unit of Measurement Selection
- Pressure: Access settings, select 'PRESS', then use [Down/Play] or [Zero/Up] to select the pressure unit.
- Vacuum: Access settings, select 'VAC', then use [Down/Play] or [Zero/Up] to select the vacuum unit.
- Temperature: Access settings, select 'TEMP', then use [Down/Play] or [Zero/Up] to select the temperature unit.
5.6.2 Temperature Compensation Configuration
Access settings, select 'TC'. Use [On/Off] to enable/disable temperature compensation. The MS-100 manifold has an internal temperature sensor for use during leak tests, specifically for temperature compensation. This function is enabled by default. Temperature compensation monitors ambient temperature variations to determine if pressure variations are due to leaks or temperature changes during the test.
5.6.3 Auto Power Off Configuration
Access settings, select 'AUTOOFF'. The default auto-off time is 15 minutes. Use [Down/Play] or [Zero/Up] to select the auto-off time (OFF - disabled, 5, 15, 30, 60 minutes). This function saves battery power.
5.6.4 Language Selection
Access settings, select 'LANG'.
5.6.5 About
- Access settings, select 'ABOUT'.
- This function allows viewing the software version, serial number (SN), and MAC address.
- Press [Down/Play] or [Zero/Up] to view the serial and MAC numbers, as well as QR codes for the serial number (SN) and downloading the Elitech Tools app.
6. ELITECH TOOLS APPLICATION
This Manifold features Bluetooth connectivity, allowing remote viewing of measurement data, recording and exporting stored reports, firmware updates, pressure alarms, and other intelligent functions through the Elitech Tools application.
6.1 Downloading the Elitech Tools App
- Download the app from the virtual stores: App Store for iOS or Google Play Store for Android.
- Compatibility: Apple systems require iOS version 11.0 or higher; Android systems require version 5.0 or higher.
Scan the QR code to download the application to your phone or tablet.
6.2 Connecting to the App
- Turn on the manifold by pressing the [On/Off] key once, then press it again to activate Bluetooth.
- Open the Elitech Tools app and click "Search nearby device". Once the app finds the manifold, click on its icon to connect.
6.3 User Registration
- Open the Elitech Tools app and click the menu icon [☰] in the upper left corner of the "Home" screen.
- Access the menu and click "Login".
- Select "Register" to save user information.
- Once registration is complete, click "Add Device" in "My Device" to add the device to your account.
- Manually enter the serial number (SN) from the information label on the back of the product, or scan the QR code to obtain it.
Note: If the information label is lost or damaged, refer to section 5.6.5 for how to view the serial number directly on the instrument's display.
6.4 Additional Services
How to acquire additional services:
- Method 1: Log in to the Elitech Tools app, click the menu icon [☰], then "User Info". On the "My Device" screen, select an instrument; the additional services will appear as available.
- Method 2: Connect the device via Bluetooth to the Elitech Tools app. Once connected, click "Settings" and select the desired services: "Record Function" (offline data recording), "Hold Pressure Setting" (leak test), and "Vacuum Function" (vacuum process).
6.5 Select / Exclude a Refrigerant (via App)
The device stores 18 commonly used refrigerants internally. To change this list, connect the instrument to the Elitech Tools app, click on the currently selected refrigerant, and replace it with another available type. The "All" tab contains the complete list of refrigerants. Follow the steps below to make selections:
- Connect the device to the app. On the "Dashboard" screen, click the refrigerant icon in the upper right corner to access the "Refrigerant" screen. Select the refrigerant and click SAVE. To make this refrigerant a favorite, click the star icon [★] after selecting it, then click the update icon [↑].
- To exclude a refrigerant from the instrument's list, select the refrigerant to be excluded and click the delete icon [?️].
6.6 Firmware Update
The device can perform remote firmware updates via the Elitech Tools app. Follow the steps below:
- Connect the device to the app.
- On the main "Dashboard" screen, click "Settings" and select "Update Firmware".
- If the current firmware is the latest version, a message "It is the latest version!" will appear on the phone screen. If a new version is available, the device will automatically enter the update process, and the screen will display "Update...".
Image 10 - Firmware Update
7. INSTRUMENT CARE
7.1 Battery Replacement
- Turn off the instrument and remove the battery compartment cover located on the back of the product.
- Remove the used batteries and install new ones (2 AAA batteries), observing the polarity markings.
- Reinstall the battery compartment cover.
- Turn the instrument back on.
Note: Remove the batteries if storing the equipment for an extended period to prevent corrosion and/or leakage, which could damage the instrument.
7.2 Product Cleaning
- Clean the exterior of the instrument with a damp cloth.
Note: Do not use detergents or corrosive solvents to clean the product.
- Keep the hose connections clean and free of grease or other contaminants.
7.3 Troubleshooting
Problem | Possible Causes | Solution |
---|---|---|
Battery charge indicator flashing | Low battery level | Replace batteries |
Instrument turns off automatically | 1. Auto-off function is enabled 2. Batteries are depleted |
1. Disable or increase the auto-off timer. 2. Replace batteries. |
Evaporation temperature display shows - - - - | Evaporation temperature exceeds the display limit | Keep within the allowed range |
Condensation temperature display shows - - - - | Condensation temperature exceeds the display limit | Keep within the allowed range |
Pressure display shows - 0 L- | Pressure reading exceeds the display limit | Keep within the allowed range |
7.4 Product Components
- 1 x MS-100 Manifold
- 1 x Manual
- 1 x Carrying Case
- 1 x Packaging (cardboard box)
7.4 CORRECT DISPOSAL
To ensure your waste does not cause pollution and environmental contamination, it is important to dispose of your equipment properly.
- To prevent soil contamination with components present in these materials, the ideal is specific recycling for this type of product.
- It is important to note that this type of waste should not be disposed of in landfills or wrapped in newspapers or plastics.
- When disposing of electronic material correctly, in addition to conservation, it allows the reuse or donation of components/instruments that are in good working condition.