Elitech WJL-6000S Corona Detector

User Manual

Contact Information

Elitech Technology, Inc.
2528 Qume Dr, Ste 2
San Jose, CA 95131 USA
Tel: +1 408-898-2866
Sales: sales@elitechus.com
Support: support@elitechus.com
Website: www.elitechus.com

Elitech (UK) Limited
Unit 13 Greenwich Centre Business Park
53 Norman Road, London, SE10 9QF
Tel: +44 (0) 208-858-1888
Sales: sales@elitech.uk.com
Support: service@elitech.uk.com
Website: www.elitech.uk.com

Elitech Brasil Ltda
R. Dona Rosalina, 90 - Igara, Canoas - RS,
92410-695, Brazil
Tel: +55 (51)-3939-8634
Sales: brasil@e-elitech.com
Support: suporte@e-elitech.com
Website: www.elitechbrasil.com.br

Overview

The WJL-6000S is a corona leak detector featuring high sensitivity and a visualized alarm display. Its adjustable sensitivity ensures automatic and optimal detection status, leading to more accurate leak location. The device boasts a subtle structure, a built-in high-precision stabilivolt IC, and an ultra-low power consumption circuit design for enhanced stability and battery life. The WJL-6000S detector is suitable for identifying leaks in cooling systems, stored refrigerants, and recovered containers. It responds to all halogenated refrigerants (containing chlorine and fluorine), including but not limited to CFCs (e.g., R12, R11, R500, R503), HCFCs (e.g., R22, R123, R124, R502), HFCs (e.g., R134a, R404a, R125), and blends like AZ-50, HP62, MP39. It also detects ethylene oxide leaks in hospital sterilizing equipment, halogen-carrying gases, SF-6 in high voltage circuit breakers, most halogen gases containing chlorine, fluorine, and bromine, cleaning agents like carbon tetrachloride, and Halon gas used in fire extinguishing systems.

Specifications

ParameterValue
Operating Temperature0°C ~ 52°C (32°F ~ 125.6°F)
Battery LifeApprox. 20 hours for normal use
Work ModeContinuous without limitation
Reset Time2 to 10 seconds
Maximum Sensitivity5g(0.2oz)/a for halogenated refrigerants
Response TimeInstant
Probe Length20cm (7.8in)
Warm-up TimeApprox. 6 seconds
Battery4 AAA batteries

Structure

The WJL-6000S detector consists of the following components:

Visual Description of the Device: The detector is a handheld unit with a black plastic casing. A flexible metal probe extends from the top. The front panel features a rotary knob for power and sensitivity, several indicator LEDs, and a buzzer. The battery compartment is located at the base.

Functions

Start-up Reset / Automatic Circuit

The WJL-6000S can ignore halogen concentrations in the environment through its functions:

Start-up Reset

Upon activation, the detector automatically calibrates for 6 seconds to disregard the current refrigerant concentration at the probe, entering an optimal detection state. If activated near a leak source, it can pinpoint leaks with higher concentrations. Alternatively, activating in fresh air and setting to maximum sensitivity allows detection of any leak above zero.

Automatic Circuit

During detection, the detector's automatic circuit adjusts to changes in ambient halogen concentration, helping to cancel false alarms.

Sensitivity Adjustment

The detector offers flexible sensitivity adjustment during operation. Rotating the knob clockwise increases sensitivity, while counterclockwise decreases it. Note that higher sensitivity does not always equate to better detection and may cause false alarms in environments with high gas concentrations.

Leak Alarm

When a leaking gas is detected, the buzzer frequency increases. The greater the leak, the faster the buzzer sounds. The first indicator LED flashes rapidly, and the other four LEDs illuminate based on the concentration of leaked gases.

Battery Indication

The first indicator LED displays both leak status and battery level:

Operation

  1. Rotate the knob to turn on the detector; the buzzer will beep intermittently.
  2. Check the indicator to ensure the battery voltage is not low (LED blinks green).
  3. Adjust to the appropriate sensitivity level or regulate it later during detection.
  4. Begin detection 6 seconds after turning the detector on.
  5. Locate the possible leak source where the buzzer will beep quickly.
  6. Adjust the sensitivity level and continue detecting until the leak source is pinpointed.

Detection

General Notes:

Detection Procedure:

  1. Ensure sufficient refrigerant is charged into the air conditioner or cooling system, maintaining a minimum pressure of 340kPa (50psi) at shutdown. Leaks may not be detected below 15°C (59°F) due to insufficient pressure.
  2. Avoid contaminating the probe tip when inspecting a dirty part. If heavily polluted or covered with condensation (like water or vapor), wipe the part with an industrial towel or blow it off with industrial air. Do not use detergents or solvents, as the sensor may be sensitive to them.
  3. Visually inspect the entire cooling system, including pipelines, hoses, and components, for signs of oil leakage, damage, or corrosion. Use the probe tip to detect potential leak sources, focusing on fittings (e.g., hose to pipeline couplings), refrigerant control components, nut-sealed components, areas around copper pipes and welded joints, and fasteners.
  4. Scan along the cooling system pipeline for a thorough inspection. If a leak is detected, continue scanning the rest of the pipeline. Move the probe tip around the suspected leak source at a speed of 25 to 50 mm/s (0.78 to 1.96 in/s) within a surface distance of 5mm (0.19 in) for optimal detection.
  5. Rapid beeps indicate a possible leak source. Remove the detector, adjust sensitivity, and re-detect carefully until the source is pinpointed.
  6. To verify a leak source, repeat the following steps as needed:
    • If necessary, blow industrial air into the suspected leak area and detect again. This is helpful for pinpointing large leaks.
    • Turn on the detector in fresh air. Hold the probe tip as close as possible to the alerted leak source. Move the detector around the leakage until it is confirmed.
  7. For Automobile AC Systems:
    • To detect leaks in the evaporator core of the air-conditioning module, set the AC fan to its highest speed for at least 15 seconds.
    • Turn off the fan and wait 10 minutes for refrigerant to accumulate.
    • Place the probe tip into the fan resistor block or condenser water outlet (if no water), or evaporator heating/ventilation/AC opening (e.g., heat or vent pipe). If an alarm is triggered, the leak source is pinpointed.
  8. Note:
    • Shut off the engine before detecting leaks in an automobile air-conditioning system.
    • It is recommended to check all maintenance and service parts after the cooling system has been maintained.

Maintenance

Proper maintenance is crucial for the detector's performance and lifespan. Follow these instructions to avoid misoperation:

Troubleshooting Guide

Problem: The detector does not turn on

Possible Cause:

Problem: The detector gives false alarm or does not respond to a known leak

Possible Cause:

Important Notes and Warnings

Important!

Please read and understand this manual thoroughly before operation and maintenance. Use 4 AAA alkaline batteries and never connect to an external power source. The detector will beep at a fixed frequency after being turned on; this frequency changes only after leaked refrigerant is detected. Do not touch the sensor during use to avoid minor electric shock. When the detector indicates low battery, change the batteries promptly to prevent false alarms. Remove batteries if the detector will not be used for an extended period and store it in a dry place.

Warning!

Additional Notes:

Meet Standards

EN14624, RoHS, CE

Models: WJL-6000S, Corona Detector, WJL-6000S Corona Detector, Detector

PDF preview unavailable. Download the PDF instead.

B13VMcpKmgL Adobe PDF library 15.00 Adobe Illustrator(R) 17.0

Related Documents

Preview Elitech IR-200 Infrared & Heated Diode Leak Detector User Manual
Comprehensive user manual for the Elitech IR-200, a dual-sensor leak detector featuring infrared and heated diode technology. Learn about its specifications, operation, maintenance, and features for detecting refrigerant leaks.
Preview Elitech ILD Series Infrared Refrigerant Leak Detector User Manual
Comprehensive user manual for the Elitech ILD series infrared refrigerant leak detectors (ILD-100, ILD-200, ILD-300), covering specifications, operation, maintenance, and features. Learn how to effectively detect refrigerant leaks with this advanced device.
Preview Elitech ILD-100/ILD-200/ILD-300 Infrared Leak Detector User Manual
User manual for the Elitech ILD series infrared refrigerant leak detectors (ILD-100, ILD-200, ILD-300). Provides detailed information on operation, specifications, features, and maintenance for accurate refrigerant leak detection.
Preview Elitech LD-100 Heated Diode Refrigerant Leak Detector User Manual
User manual for the Elitech LD-100 Heated Diode Refrigerant Leak Detector, detailing its features, operation, and maintenance.
Preview Elitech MS-100 Digital Manifold: User Manual and Specifications
Comprehensive guide to the Elitech MS-100 digital manifold, covering its features, technical specifications, operation, safety instructions, and troubleshooting. Learn how to use the device for pressure and temperature measurements, leak tests, vacuum processes, and data logging with the Elitech Tools app.
Preview Elitech RC-5 Quick Start Guide: Temperature Data Logger
Quick start guide for the Elitech RC-5 temperature data logger, covering battery installation, software setup, logger operation, technical specifications, and troubleshooting.
Preview Elitech RCW-600 WiFi User Manual
User manual for the Elitech RCW-600 WiFi, a two-channel temperature monitor based on IoT technology. Learn about its features, technical parameters, appearance, installation, operation, and WiFi configuration.
Preview RCW-2000/2100/2200 User Manual - Elitech Wireless Temperature and Humidity Monitoring System
User manual for the Elitech RCW-2000 (Wi-Fi Gateway), RCW-2100, and RCW-2200 wireless temperature and humidity sensors. This guide covers technical specifications, appearance, indicator status, Elitech app setup, and cloud portal access for remote monitoring.