Product Data Sheet
Schneider Electric Altivar Process ATV600, ATV630, 250kW, 400hp, 380 to 480V, IP00
Image of the Schneider Electric Altivar Process ATV630 variable speed drive.
Main Specifications
Range of Product | Altivar Process ATV600 |
Product Specific Application | Process and utilities |
Product or Component Type | Variable speed drive |
Variant | Standard version |
Device short name | ATV630 |
Mounting Mode | Wall mount |
Communication Port Protocol | Modbus TCP, Modbus serial, Ethernet |
[Us] rated supply voltage | 380...480 V - 15...10% |
Relative symmetric mains voltage tolerance | 10% |
Relative symmetric network frequency tolerance | 5% |
nominal output current | 481.0 A |
IP degree of protection | IP21 |
Product destination | EMC filter Integrated 164.04 ft (50 m) IEC 61800-3 category C3 |
IP degree of protection (with kit) | IP00 IEC 61800-5-1, IP00 IEC 60529, IP21 with kit VW3A9113 IEC 61800-5-1, IP21 with kit VW3A9113 IEC 60529 |
type of cooling | Forced convection |
Supply frequency | 50...60 Hz - 5...5% |
Motor power kW | 250 kW normal duty, 220 kW heavy duty |
Maximum Horse Power Rating | 400 hp normal duty, 300 hp heavy duty |
Line current | 451 A 380 V normal duty, 366 A 480 V normal duty, 365 A 380 V heavy duty, 301 A 480 V heavy duty |
Continuous output current | 481 A 2.5 kHz normal duty, 387 A 2.5 kHz heavy duty |
Speed drive output frequency | 0.1...500 Hz |
Safety function | STO (safe torque off) SIL 3 |
Complementary Specifications
Feature | Details |
---|---|
Discrete input number | 8 |
Discrete input type | D17, DI8 programmable as pulse input 0...30 kHz, 24 V DC <= 30 V |
Discrete input logic | 16 preset speeds |
Discrete output number | 0 |
Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA; Relay outputs R1A, R1B, R1C 30 V DC 3000 mA; Relay outputs R2A, R2C 250 V AC 5000 mA; Relay outputs R2A, R2C 30 V DC 5000 mA; Relay outputs R3A, R3C 250 V AC 5000 mA; Relay outputs R3A, R3C 30 V DC 5000 mA |
Analogue input number | 3 |
Analogue input type | Al1, Al2, Al3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits; Al1, Al2, Al3 software-configurable current 0...20 mA 250 Ohm 12 bits; Al2 voltage analog input -10...10 V DC 31.5 kOhm 12 bits |
Analogue output number | 2 |
Analogue output type | Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits; Software-configurable current AQ1, AQ2 0...20 mA 10 bits; Software-configurable current DQ-, DQ+ 30 V DC; Software-configurable current DQ-, DQ+ 100 mA |
Relay output number | 3 |
Relay output type | Configurable relay logic R1 fault relay NO/NC 100000 cycles; Configurable relay logic R2 sequence relay NO 100000 cycles; Configurable relay logic R3 sequence relay NO 100000 cycles |
Maximum switching current | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC; Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC; Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC; Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC |
Minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC |
Phase | 3 phase |
Physical interface | Ethernet, 2-wire RS 485 |
Method of access | Slave Modbus TCP |
Transmission Rate | 10, 100 Mbits |
Transmission frame | RTU |
Output voltage | <= power supply voltage |
Permissible temporary current boost | 1.1 x In 60 s normal duty, 1.5 x In 60 s heavy duty |
Data format | 8 bits, configurable odd, even or no parity |
Type of polarization | No impedance |
Frequency resolution | Display unit 0.1 Hz, Analog input 0.012/50 Hz |
Electrical and Control Specifications
Feature | Details |
---|---|
Electrical connection | Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16; Line side screw terminal 4 x 185 mm² 3 x 350 kcmil; Motor screw terminal 4 x 185 mm² 3 x 350 kcmil |
Connector type | RJ45 on the remote graphic terminal Ethernet/Modbus TCP; RJ45 on the remote graphic terminal Modbus serial |
Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
Number of addresses | 1...247 Modbus serial |
Supply | External supply for digital inputs 24 V DC 19...30 V), <1.25 mA overload and short-circuit protection; Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5%, <10 mA overload and short-circuit protection; Internal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protection |
Local signalling | 3 LEDs for local diagnostic; 3 LEDs (dual colour) for embedded communication status; 4 LEDs (dual colour) for communication module status; 1 LED (red) for presence of voltage |
Input compatibility | DI1...DI6 discrete input level 1 PLC IEC 61131-2; D15, D16 discrete input level 1 PLC IEC 65A-68; STOA, STOB discrete input level 1 PLC IEC 61131-2 |
Discrete input logic | Positive logic (source) DI1...DI8), < 5 V, > 11 V; Negative logic (sink) DI1...DI8), > 16 V, < 10 V |
Sampling duration | 2 ms +/- 0.5 ms DI1...DI4) - discrete input; 5 ms +/- 1 ms DI5, DI6) - discrete input; 5 ms +/- 0.1 ms Al1, Al2, A13) - analog input; 10 ms +/- 1 ms AO1) - analog output |
Accuracy | +/- 0.6% Al1, Al2, Al3 for a temperature variation 60 °C analog input; +/-1% AO1, AO2 for a temperature variation 60 °C analog output |
Linearity error | Al1, Al2, Al3 +/- 0.15% of maximum value analog input; AO1, AO2 +/- 0.2% analog output |
Refresh time | Relay output R1, R2, R3) 5 ms +/- 0.5 ms |
Isolation | Between power and control terminals |
Discrete and process manufacturing applications | Building - HVAC compressor centrifugal; Food and beverage processing other application; Mining mineral and metal fan; Mining mineral and metal pump; Oil and gas fan; Water and waste water other application; Building - HVAC screw compressor; Food and beverage processing pump; Food and beverage processing fan; Food and beverage processing atomization; Oil and gas electro submersible pump (ESP); Oil and gas water injection pump; Oil and gas jet fuel pump; Oil and gas compressor for refinery; Water and waste water centrifuge pump; Water and waste water positive displacement pump; Water and waste water electro submersible pump (ESP); Water and waste water screw pump; Water and waste water lobe compressor; Water and waste water screw compressor; Water and waste water compressor centrifugal; Water and waste water fan; Water and waste water conveyor; Water and waste water mixer |
Power range | 250...500 kW 380...440 V 3 phase; 250...500 kW 480...500 V 3 phase |
Enclosure mounting | Wall mounted |
4 quadrant operation possible | False |
Asynchronous motor control profile | Variable torque standard; Constant torque standard; Optimized torque mode |
Synchronous motor control profile | Permanent magnet motor; Synchronous reluctance motor |
Maximum output frequency | 500 kHz |
Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
Motor slip compensation | Automatic whatever the load; Not available in permanent magnet motor law; Can be suppressed |
Switching frequency | 2.5...8 kHz with derating factor; 2...8 kHz adjustable |
Nominal switching frequency | 2.5 kHz |
Braking to standstill | By DC injection |
Brake chopper integrated | False |
Maximum Input Current per Phase | 451.0 A |
Maximum output voltage | 480.0 V |
Apparent power | 279 kVA 480 V normal duty; 229 kVA 480 V heavy duty |
Maximum transient current | 529 A 60 s normal duty; 581 A 60 s heavy duty |
Network Frequency | 50-60 Hz |
Prospective line Isc | 50 kA |
Base load current at high overload | 387.0 A |
Base load current at low overload | 481.0 A |
Power dissipation in W | Forced convection 5773 W; Natural convection 606 W 380 V 2.5 kHz |
Safety Functions | Safely Limited Speed (SLS): False; Safe brake management (SBC/SBT): False; Safe Operating Stop (SOS): False; Safe Position (SP): False; Safe programmable logic: False; Safe Speed Monitor (SSM): False; Safe Stop 1 (SS1): False; Safe Stop 2 (SS2): False; Safe torque off (STO): True; Safely Limited Position (SLP): False; Safe Direction (SDI): False |
Environment and Certifications
Feature | Details |
---|---|
Protection type | Thermal protection motor; Safe torque off motor; Motor phase break motor; Thermal protection drive; Safe torque off drive; Overheating drive; Overcurrent between output phases and earth drive; Overload of output voltage drive; Short-circuit protection drive; Motor phase break drive; Overvoltages on the DC bus drive; Line supply overvoltage drive; Line supply undervoltage drive; Line supply phase loss drive; Overspeed drive; Break on the control circuit drive |
Quantity per Set | 1 |
Dimensions (W x H x D) | 23.5 in (598 mm) x 47.05 in (1195 mm) x 15.0 in (380 mm) |
Net Weight | 447.5 lb(US) (203 kg) |
Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
Noise level | 68 dB IEC 60068-2-6 |
Pollution degree | 2 IEC 61800-5-1 |
Vibration resistance | 1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
Relative humidity | 5...95% without condensation IEC 60068-2-3 |
Ambient air temperature for operation | 14...104 °F (-10...40 °C) (without derating); 104...140 °F (40...60 °C) (with derating factor) |
Operating altitude | <= 3280.84 ft (1000 m) without derating; 3280.84...9842.52 ft (1000...3000 m) with current derating 1% per 100 m |
Operating position | Vertical +/- 10 degree |
Product Certifications | CSA, UL, TÜV, CE |
Marking | CF |
Standards | UL 508C; IEC 61800-3; EN/IEC 61800-3 environment 1 category C2; EN/IEC 61800-3 environment 2 category C3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1 |
Maximum THDI | <48% full load IEC 61000-3-12 |
Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 μs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3 |
Environmental footprint | Carbon footprint (kg CO2 eq, Total Life cycle): 184862 |
Materials and Substances | Packaging made with recycled cardboard: Yes; Packaging without single use plastic: No; EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope); SCIP Number: 405cb612-8eb2-47cb-8883-95e373eada5f; REACH Regulation: REACH Declaration; California proposition 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Energy efficiency | Product contributes to saved and avoided emissions: Yes |
Repack and remanufacture | No |
Take-back | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
WEEE | No |
Dimensions and Mounting
Dimensions
Diagrams showing rear, right, and front views of the drive with dimensions.
View | Width | Height | Depth |
---|---|---|---|
Rear | 540 mm (21.26 in) | 920 mm (36.22 in) | 150 mm (5.91 in) |
Right Side | 379.88 mm (14.96 in) | N/A | 377.38 mm (14.86 in) |
Front | 598 mm (23.54 in) | 1195.38 mm (47.06 in) | N/A |
Mounting and Clearance
Diagram illustrating required clearances for mounting.
Clearance | Requirement |
---|---|
X1 | ≥ 200 mm (7.87 in.) |
X2 | ≥ 150 mm (5.91 in.) |
X3 | ≥ 10 mm (0.39 in.) |
Diagrams showing different mounting types.
Mounting Type A: Individual IP21
Description: Individual mounting with IP21 protection. Units can be installed side-by-side with a minimum spacing 'a' (a ≥ 0).
Mounting Type B: Side by Side IP20
Description: Side-by-side mounting with IP20 protection.
Mounting Type C: Individual IP20
Description: Individual mounting with IP20 protection. Units can be installed side-by-side with a minimum spacing 'a' (a ≥ 0).
Connections and Schema
Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagram showing upstream breaking using a line contactor (KM1), circuit breakers (Q2, Q3), pushbuttons (S1, S2), and transformer (T1). Relay R1 is used for fault indication.
Three-Phase Power Supply with Downstream Breaking via Contactor
Connection diagram showing downstream breaking using a contactor (KM1) placed after the drive.
Control Block Wiring Diagram
Diagram illustrating the control block wiring. Shows connections for digital inputs (DI1-DI6), Safe Torque Off (STO) inputs (STOA, STOB), 24V supply, analog inputs (AI1, AI2, AI3), analog outputs (AQ1, AQ2), and relay outputs (R1A/R1B/R1C, R2A/R2C, R3A/R3C).
Sensor Connection: It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
Sink / Source Switch Configuration
This switch adapts the operation of the logic inputs to the technology of the programmable controller outputs.
- Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
- Set the switch to Ext if using PLC outputs with NPN transistors.
Diagrams illustrating different switch configurations: SRC (Source) with output power supply, SRC (Source) with external power supply, SK (Sink) with output power supply, and EXT (External) with external power supply for Digital Inputs (DIs).
Performance Curves
Derating Curves
Graph showing derating curves for Nominal Drive Current (In) versus Switching Frequency (SF) at different ambient temperatures (40°C, 50°C, 60°C).
Ordering and Shipping Details
Feature | Details |
---|---|
Category | US1CP4E22207 |
Discount Schedule | CP4E |
GTIN | 3606481154729 |
Returnability | Yes |
Country of origin | ID |
Packing Units
Package Detail | Value |
---|---|
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 14.96 in (38.000 cm) |
Package 1 Width | 23.54 in (59.800 cm) |
Package 1 Length | 47.05 in (119.500 cm) |
Package 1 Weight | 500.450 lb(US) (227.000 kg) |