Schneider Electric Altistart 22 Soft Starter
Product Data Sheet
Specifications
Product Name: Soft starter for asynchronous motor, Altistart 22, control 110V, 208 to 575V, 50 to 150hp
Product Reference: ATS22C17S6U
Product Availability: Stock - Normally stocked in distribution facility
Main
Attribute | Value |
---|---|
Range of Product | Altistart 22 |
Product or Component Type | Soft starter |
Product destination | Asynchronous motors |
Product Specific Application | Pumps and fans |
Component name | ATS22 |
Phase | 3 phase |
[Us] rated supply voltage | 208...600 V - 15...10% |
Maximum Horse Power Rating | 125 hp 460 V, 150 hp 575 V, 50 hp 208 V, 60 hp 230 V |
Factory setting current | 156 A |
Power dissipation in W | 91 W for standard applications |
Utilisation category | AC-53A |
Type of start | Start with torque control (current limited to 3.5 In) |
IcL starter rating | 170 A connection in the motor supply line for standard applications |
IP Degree of Protection | IP00 |
Complementary
Attribute | Value |
---|---|
Assembly style | With heat sink |
Function Available | Internal bypass |
Supply voltage limits | 177...660 V |
Supply frequency | 50...60 Hz - 10...10% |
Network Frequency | 45...66 Hz |
Device connection | In the motor supply line |
[Uc] control circuit voltage | 110 V - 15...10% 50/60 Hz |
Control circuit consumption | 20 W |
Discrete output number | 2 |
Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O, Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
Minimum switching current | 100 mA (12 V DC relay outputs) |
Technical Specifications
Attribute | Value |
---|---|
Maximum switching current | 5 A 250 V AC resistive (1 relay outputs), 5 A 30 V DC resistive (1 relay outputs), 2 A 250 V AC inductive (0.4...20 ms relay outputs), 2 A 30 V DC inductive (7 ms relay outputs) |
Discrete input number | 3 |
Discrete input type | LI1, LI2, LI3 logic, 5 mA 20 kOhm |
Discrete input voltage | 110 V <= 121 V |
Discrete input logic | Positive logic LI1, LI2, LI3 < 20 V <= 15 mA > 79 V, <= 2 mA |
Output current | 0.4...1 Icl adjustable |
PTC probe input | 750 Ohm |
Communication Port Protocol | Modbus |
Connector Type | 1 RJ45 |
Communication data link | Serial |
Physical interface | RS485 multidrop |
Transmission Rate | 4800, 9600 or 19200 bps |
Installed device | 31 |
Protection type | Phase failure line, Thermal protection motor, Thermal protection starter |
Marking | CE |
Type of cooling | Forced convection |
Operating position | Vertical +/- 10 degree |
Height | 14.02 in (356 mm) |
Width | 5.9 in (150 mm) |
Depth | 9.04 in (229.5 mm) |
Net Weight | 39.7 lb(US) (18 kg) |
Environment
Attribute | Value |
---|---|
Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2, Damped oscillating waves level 3 conforming to IEC 61000-4-12, Electrostatic discharge level 3 conforming to IEC 61000-4-2, Immunity to electrical transients level 4 conforming to IEC 61000-4-4, Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3, Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
Standards | IEC 60947-4-2 |
Product Certifications | CSA, GOST, CCC, C-tick, UL |
Vibration resistance | 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6, 1.5 mm (f= 2...13 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
Noise level | 56 dB |
Pollution degree | Level 2 IEC 60664-1 |
Relative humidity | 0...95% without condensation or dripping water IEC 60068-2-3 |
Ambient air temperature for operation | 14...104 °F (-10...40 °C) (without derating), 104...140 °F (40...60 °C) (with current derating 2.2% per °C) |
Ambient Air Temperature for Storage | -13...158 °F (-25...70 °C) |
Operating altitude | <= 3280.84 ft (1000 m) without derating, > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2% per additional 100 m |
Ordering and Shipping Details
Attribute | Value |
---|---|
Category | US1CP1G22576 |
Discount Schedule | CP1G |
GTIN | 3606480167454 |
Returnability | Yes |
Country of origin | ID |
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1: 1
Attribute | Value |
---|---|
Package 1 Height | 10.04 in (25.5 cm) |
Package 1 Width | 13.19 in (33.5 cm) |
Package 1 Length | 16.54 in (42.0 cm) |
Package 1 Weight | 29.28 lb(US) (13.28 kg) |
Unit Type of Package 2
P06
Number of Units in Package 2: 4
Attribute | Value |
---|---|
Package 2 Height | 28.94 in (73.5 cm) |
Package 2 Width | 31.50 in (80.0 cm) |
Package 2 Length | 23.62 in (60.0 cm) |
Package 2 Weight | 142.366 lb(US) (64.576 kg) |
Contractual Warranty
Warranty: 18 months
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.
Use Better
Materials and Substances
Attribute | Value |
---|---|
Packaging made with recycled cardboard | No |
Packaging without single use plastic | No |
EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
SCIP Number | F0ceff13-4dac-4695-a2e7-71002043e88b |
REACH Regulation | REACH Declaration |
California proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Use Again
Repack and remanufacture
Attribute | Value |
---|---|
Take-back | No |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
Dimensions Drawings
Frame Size C
Dimensions
Diagram Description: A technical drawing showing the dimensions of the Altistart 22 soft starter, Frame Size C. The drawing provides measurements in both millimeters (mm) and inches (in) for various dimensions, including height, width, depth, and mounting hole locations and sizes. Key dimensions indicated are: Overall height 356 mm (14 in), Overall width 150 mm (5.9 in), Overall depth 229.5 mm (9.04 in). Mounting hole details include 4 holes of Ø 7 mm (Ø 0.28 in) and 6 holes of Ø 9 mm (Ø 0.35 in). Terminal connection details show dimensions for bar and cable connections.
Power Terminal Bar Style:
- a: 20 mm (0.79 in)
- b: 5 mm (0.2 in)
- Bolt: M8 (0.31 in)
- Size: 95 mm²
- Gauge: 250 MCM
- Cable and protective cover: Protective cover LA9F702
- Tightening torque: 18 N.m (157.5 lb.in)
Power connections, minimum required wiring section:
- IEC cable (Cu 70°C/158°F): 70 mm²
- UL cable (Cu 75°C/167°F): 4/0 AWG
Mounting and Clearance
Precautions
Standards: The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1. For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. ATS22 soft starters are open devices and must be mounted in a suitable enclosure. Failure to follow these instructions will result in death or serious injury.
Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.
Diagram Description: A diagram illustrating the required air circulation space around the soft starter. Arrows indicate airflow from bottom to top. Minimum clearance dimensions are shown: ≥100 mm (≥3.9 in) at the top, and ≥50 mm (≥1.95 in) on the sides and bottom.
Overheating
To avoid the soft starter to overheat, respect the following recommendations:
- Mount the Altistart 22 Soft Starter within ± 10° of vertical.
- Do not locate the Altistart 22 Soft Starter near heat radiating elements.
- Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.
- If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the bottom soft starter can adversely affect the ambient temperature around the top soft starter.
Mounting
Diagram Description: A diagram showing the connection between the fan and the Altistart 22 Soft Starter. It labels component 1 as "Altistart 22 Soft Starter" and component 2 as "Fan".
Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.
Ventilation Grilles
Diagram Description: Illustration showing ventilation grilles with a note indicating ambient temperature condition: 0 ≤ 40°C (104°F).
Forced Ventilation Unit
Diagram Description: Illustration of a forced ventilation unit with a note indicating ambient temperature condition: 0 ≤ 40°C (104°F).
Connections and Schema
Power Terminal
Bar Style
Diagram Description: A diagram illustrating the bar style for power terminal connections, showing dimensions 'a' and 'b', and bolt size.
Schematics
110 Vac control, Logic Inputs (LI) 110 Vac, 3-wire control
Diagram Description: A wiring diagram for a 110 Vac control system using logic inputs (LI) and a 3-wire control configuration. It shows the connections for the Altistart 22 soft starter, including power terminals (L1, L2, L3, T1, T2, T3), logic inputs (LI1, LI2, LI3), control voltage (110V), and output relays (R1A, R1B, R1C, R2A, R2B, R2C). It also depicts the connection of a contactor (KM1) and a thermal overload relay (Q1).
110 Vac control, Logic Inputs (LI) 110 Vac, 2-wire control, freewheelstop
Diagram Description: A wiring diagram for a 110 Vac control system using logic inputs (LI) and a 2-wire control configuration with freewheel stop functionality. Similar to the 3-wire diagram, it illustrates the connections for the Altistart 22 soft starter, control voltage, logic inputs, and output relays, along with contactor (KM1) and thermal overload relay (Q1) connections.
Performance Curves
Motor Thermal Protection - Cold Curves
Diagram Description: A graph showing the motor thermal protection cold curves for the Altistart 22 soft starter. The x-axis represents motor nominal current (In) and the y-axis represents time in seconds (t(s)). Three curves (A, B, C) are plotted, corresponding to Class 10, Class 20, and Class 30 thermal protection classes, respectively. These curves indicate the trip time based on the motor current and the selected protection class when the motor is cold.
Trip time for a Standard Application (Class 10)
- 3.5 In: 32 s
Trip time for a Severe Application (Class 20)
- 3.5 In: 63 s
Trip time for a Severe Application (Class 30)
- 3.5 In: 95 s
Motor Thermal Protection - Warm Curves
Diagram Description: A graph showing the motor thermal protection warm curves for the Altistart 22 soft starter. Similar to the cold curves, this graph plots motor nominal current (In) against time in seconds (t(s)) for Class 10 (A), Class 20 (B), and Class 30 (C) thermal protection classes. These curves illustrate the trip time when the motor is already warm.
Trip time for a Standard Application (Class 10)
- 3.5 In: 16 s
Trip time for a Severe Application (Class 20)
- 3.5 In: 32 s
Trip time for a Severe Application (Class 30)
- 3.5 In: 48 s
Image of product / Alternate images
Alternative Images:
Image Description 1: Front view of the Altistart 22 soft starter, showing the control panel with a digital display and buttons, power terminals, and mounting points.
Image Description 2: Side view of the Altistart 22 soft starter, highlighting its compact design and heat dissipation features, such as the heatsink.
Image Description 3: Rear view of the Altistart 22 soft starter, showing the connection terminals and mounting interface.
Image Description 4: Another side view of the Altistart 22 soft starter, emphasizing the fan for cooling and the overall construction.