Altistart 48 Soft Starters for Asynchronous Motors
Altistart 48 soft start - soft stop units are designed for asynchronous motors, offering various combinations with circuit-breakers, contactors, and fast-acting fuses. These combinations are in accordance with standards IEC 60947-4-1 and IEC 60947-4-2, supporting Type 1 and Type 2 coordination.
Components for Use Together
The following tables detail compatible components for different motor power ratings (kW) and current ratings (A), across various voltage supplies (230V, 380V/400V/415V, 440V, 500V, 690V) and coordination types.
230 V Power Supply, Type 1 Coordination
Motor (kW) | Starter (A) | Circuit-breaker (Telemecanique) | Circuit-breaker Rating (A) | Contactor (Telemecanique) | Switch/Fuse (Merlin Gerin) | Fuse Unit Reference | Fuse Size | Fuse Rating (A) | ||
---|---|---|---|---|---|---|---|---|---|---|
3 | 11.5 | ATS 48D17 | GV2 L20 | 18 | LC1 D18 | LS1 D32 | DF2 CA16 | 10 x 38 | 16 | |
4 | 14.5 | ATS 48D17 | ATS 48D220 | GV2 L20 | 18 | LC1 D18 | LS1 D32 | DF2 CA16 | 10 x 38 | 16 |
5.5 | 20 | ATS 48D220 | ATS 48D320 | GV2 L22 | 25 | LC1 D25 | LS1 D32 | DF2 CA25 | 10 x 38 | 25 |
7.5 | 27 | ATS 48D320 | ATS 48D380 | GV2 L32 | 32 | LC1 D32 | GK1 EK | DF2 EA32 | 14 x 51 | 32 |
9 | 32 | ATS 48D380 | ATS 48D47 | GK3 EF40 | 40 | LC1 D38 | GK1 EK | DF2 EA40 | 14 x 51 | 40 |
11 | 39 | ATS 48D47 | ATS 48D620 | GK3 EF65 | 65 | LC1 D50 | GK1 FK | DF2 FA50 | 22 x 58 | 50 |
15 | 52 | ATS 48D620 | ATS 48D750 | GK3 EF65 | 65 | LC1 D65 | GK1 FK | DF2 FA80 | 22 x 58 | 80 |
18.5 | 64 | ATS 48D750 | ATS 48D880 | GK3 EF80 | 80 | LC1 D80 | GK1 FK | DF2 FA80 | 22 x 58 | 80 |
22 | 75 | ATS 48D880 | ATS 48C110 | NS1000 MA (2) | 100 | LC1 D115 | GK1 FK | DF2 FA100 | 22 x 58 | 100 |
30 | 103 | ATS 48C11 | ATS 48C140 | NS1600 MA (2) | 150 | LC1 D115 | GK1 FK | DF2 FA125 | 22 x 58 | 125 |
37 | 126 | ATS 48C14 | ATS 48C170 | NS1600 MA (2) | 150 | LC1 D150 | GS1 L | DF2 GA1161 | 0 | 160 |
45 | 150 | ATS 48C170 | ATS 48C210 | NS2500 MA (2) | 220 | LC1 F185 | GS1 N | DF2 HA1201 | 1 | 200 |
55 | 182 | ATS 48C21 | ATS 48C250 | NS2500 MA (2) | 220 | LC1 F225 | GS1 N | DF2 HA1201 | 1 | 200 |
75 | 240 | ATS 48C250 | ATS 48C320 | NS4000 MA (2) | 320 | LC1 F265 | GS1 QQ | DF2 JA1251 | 2 | 250 |
90 | 295 | ATS 48C32 | ATS 48C41 | NS4000 MA (2) | 320 | LC1 F330 | GS1 QQ | DF2 JA1311 | 2 | 315 |
110 | 356 | ATS 48C410 | ATS 48C480 | NS6300 MAE (2) | 500 | LC1 F400 | GS1 S | DF2 KA1401 | 3 | 400 |
132 | 425 | ATS 48C480 | ATS 48C590 | NS6300 MAE (2) | 500 | LC1 F500 | GS1 S | DF2 KA1501 | 3 | 500 |
160 | 520 | ATS 48C590 | ATS 48C660 | NS630b (2) Micrologic 5.0 | 630 | LC1 F630 | GS1 S | DF2 KA1631 | 3 | 630 |
Maximum Prospective Short-Circuit Current
Starter | Iq (kA) |
---|---|
ATS 48D17 to ATS 48C320 | 50 |
ATS 48C41 to ATS 48M120 | 70 |
Breaking Capacity of Circuit-Breakers
Voltage | Circuit-Breaker Type | Icu (kA) |
---|---|---|
230 V | GV2 L20, GK3 EF40 | 50 |
GV2 L22, GV2 L32, GK3 EF65, GK3 EF80 | 70 | |
230 V | NS100, NS160, NS250, NS400, NS630 | 85 |
NS800, NS1000 | 50 | |
NS1250 | 50 | |
C801, C1001 | 85 | |
C1251 | 85 |
Notes:
- (1) Replace with Q or Y according to the starter voltage range.
- (2) Replace with N, H or L, according to the breaking capacity (see table below).
- (3) DF2 CA, DFO EA, DFO FA: sold in lots of 20. DFO GA, DFO KA: sold in lots of 3. DFO LA: sold singly.
Additional Information
For detailed presentation, characteristics, references, dimensions, and schemes, please refer to the following pages:
- Presentation: pages 1/30 and 1/31
- Characteristics: pages 1/32 to 1/35
- References: pages 1/40 to 1/43
- Dimensions: pages 1/48 to 1/53
- Schemes: pages 1/54 to 1/59