Schneider Electric Altistart 480 Soft Starter ATS480D88Y

Product Data Sheet

Main Specifications

Product Name: Soft starter, Altistart 480, 88A, 208 to 690V AC, control supply 110 to 230V AC

Model: ATS480D88Y

Product Availability: Stock - Normally stocked in distribution facility

Range of Product Altivar Soft Starter ATS480
Product or Component Type Soft starter
Product destination Asynchronous motors
Product Specific Application Process and infrastructures
Device short name ATS480
Phase 3 phase
Utilisation category AC-3A, AC-53A
Ue power supply voltage 208...690 V - 15...+10%
Power supply frequency 50...60 Hz - 20...+20%
[le] rated operational current 88.0 A (at 40 °C)
Rated current in heavy duty 75.0 A at 40 °C heavy duty
Torque control True
IP Degree of Protection IP20
Motor power kW 22.0 kW 230 V (normal duty), 18.5 kW 230 V (heavy duty), 45.0 kW 400 V (normal duty), 37.0 kW 400 V (heavy duty), 45.0 kW 440 V (normal duty), 37.0 kW 440 V (heavy duty), 55.0 kW 500 V (normal duty), 45.0 kW 500 V (heavy duty), 55.0 kW 525 V (normal duty), 45.0 kW 525 V (heavy duty), 75.0 kW 660 V (normal duty), 55.0 kW 660 V (heavy duty), 75.0 kW 690 V (normal duty), 55.0 kW 690 V (heavy duty)
Maximum Horse Power Rating 25.0 hp 208 V (normal duty), 20.0 hp 208 V (heavy duty), 30.0 hp 230 V (normal duty), 25.0 hp 230 V (heavy duty), 60.0 hp 460 V (normal duty), 50.0 hp 460 V (heavy duty), 75.0 hp 575 V (normal duty), 60.0 hp 575 V (heavy duty)
Option card Communication module Profibus DP V1, Communication module Modbus TCP/EtherNet/IP, Communication module CANopen daisy chain, Communication module CANopen Sub-D, Communication module CANopen open style, Communication module PROFINET

Price is "List Price" and may be subject to a trade discount - check with your local distributor or retailer for actual price.

Complementary Specifications

Device connection In the motor supply line, To the motor delta terminals
[Us] control circuit voltage 110...230 V AC 50/60 Hz - 15...+10%
Apparent power 0.09 kVA
Integrated motor overload protection True
Motor thermal protection class Class 10E
Protection type Phase failure line, Integrated thermal protection motor, Thermal protection starter, Current overload motor, Underload motor, Excessive starting time, locked rotor motor, Motor phase loss motor, Line supply phase loss line, Line supply phase loss motor, Thermal protection motor
Current limiting %In (5 x le maximum) 150...700%
[In] Rated current pwr loss specifctn 88.0 A
Power loss static current independent 25.0 W
Power loss per device current dependent 270.0 W
Standards IEC 60947-4-2, UL 60947-4-2, IEC 60664-1
Product Certifications CE, cULus, CCC, UKCA, RCM, EAC, DNV, ABS, BV, CCS
Marking CE, CCC, UKCA, EAC, RCM, CULus
[Uc] control circuit voltage 24 V DC
Discrete input number 4
Discrete input type STOP) logic inputs, 3500 Ohm; RUN) logic inputs, 3500 Ohm; D13) programmable as logic input, 3500 Ohm; D14) programmable as logic input, 3500 Ohm
Input compatibility STOP discrete input level 1 PLC IEC 61131-2, RUN discrete input level 1 PLC IEC 61131-2, D13 discrete input level 1 PLC IEC 61131-2, D14 discrete input level 1 PLC IEC 61131-2
Discrete input logic Programmable digital input < 5 V
Relay output number 3
Relay output type Relay outputs R1A 1 NO, Relay outputs R1B 1 NO, Relay outputs R1C NO/NC programmable
Minimum switching current 100 mA 12 V DC relay outputs
Maximum switching current Relay outputs 2 A 250 V AC, Relay outputs 2 A 30 V DC
Discrete output number 2
Discrete output type DQ1) programmable digital output <= 30 V, DQ2) programmable digital output <= 30 V
Output compatibility Open collector level 1 PLC IEC 65A-68
Analogue input number 1
Analogue input type AI1/PTC PTC/Pt 100 temperature probe, PTC2 PTC/Pt 100 temperature probe, PTC3 PTC/Pt 100 temperature probe
Analogue output number 1
Analogue output type Current output AQ1 0...20 mA or 0...10 V 500 Ohm
Communication Port Protocol Modbus serial
Connector Type RJ45
Communication data link Serial
Physical interface 2-wire RS 485
Transmission Rate 1200...256000 bit/s
Transmission frame RTU
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance Modbus serial
Number of addresses 0...227 Modbus serial
Method of access Slave Modbus serial
Function Available External bypass control, Pre-heating, Smoke extraction, Multi-motor cascade, Second motor set, User management, Ports and services hardening, Security event logging, Cybersecure firmware update, Single direction
Display screen available True
Operating position Vertical +/- 10 degree
Height 290.0 mm (11.4 in.)
Width 190.0 mm (7.48 in.)
Depth 247.0 mm (9.72 in.)
Net Weight 8.3 kg (18.3 lb)

Environment and Sustainability

Environmental Conditions:

[Ui] Rated Insulation Voltage 690 V
Environmental class (during operation) Class 3C3 according to IEC 60721-3-3
Environmental class (during storage) Class 3S2 according to IEC 60721-3-3
Relative humidity 0...95% without condensation or dripping water IEC 60068-2-3
Ambient air temperature for operation 40...60 °C (with current derating of 2% per °C), 5...40 °C (without derating)
Ambient Air Temperature for Storage -25...70 °C
Operating altitude <= 1000 m without derating, > 1000...4000 m with current derating 1% per 100 m
Maximum deflection under vibratory load (during operation) 1.5 mm at 2...13 Hz
Maximum deflection under vibratory load (during storage) 1.75 mm at 2...9 Hz
Maximum deflection under vibratory load (during transport) 1.75 mm at 2...9 Hz
Maximum acceleration under vibrational stress (during operation) 10 m/s² at 13...200 Hz
Maximum acceleration under vibratory load (during storage) 15 m/s² at 200...500 Hz, 10 m/s² at 9...200 Hz
Maximum acceleration under vibratory load (during transport) 15 m/s² at 200...500 Hz, 10 m/s² at 9...200 Hz
Maximum acceleration under shock impact (during operation) 150 m/s² at 11 ms
Maximum acceleration under shock load (during storage) 100 m/s² at 11 ms
Maximum acceleration under shock load (during transport) 100 m/s² at 11 ms

Environmental Data:

Carbon footprint (kg CO2 eq, Total Life cycle) 7626
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
SCIP Number 5e2e4c7a-0593-47ad-92ac-80085d9dd549
REACH Regulation REACH Declaration
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Use Again:

Repack and remanufacture Circularity Profile, End of Life Information
Take-back No
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Dimensions Drawings

Detailed drawings illustrate the physical dimensions and mounting requirements.

Front, Side, and Rear View Dimensions:

Mounting Position and Clearance:

The soft starter can be mounted vertically with a tolerance of +/- 10 degrees. Required clearances are:

A visual indicator (red cross symbol ❌) is shown against an incorrect horizontal mounting orientation.

Connections and Schematics

Various diagrams detail the electrical connections and internal schematics.

Power Connections:

The power connections diagram shows the mains supply inputs labeled (1) with terminals 1/L1, 3/L2, 5/L3, and the motor outputs labeled (2) with terminals 2/T1, 4/T2, 6/T3. Bypass connections are also indicated as A2, B2, C2.

Wiring Diagrams:

Multiple wiring diagrams illustrate different installation configurations:

Control Block Wiring Diagram:

This diagram details the control terminals on the ATS480 unit. Key terminals include:

Notes clarify control power supply, external supply, and sensor connection types (e.g., 2-wire PTC/PT100).

Ordering and Shipping Information

Category: US1CP1G22588

Discount Schedule: CP1G

GTIN: 3606481089069

Returnability: Yes

Country of Origin: FR

Packing Units:

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 14.57 in (37.000 cm)
Package 1 Width 12.20 in (31.000 cm)
Package 1 Length 15.35 in (39.000 cm)
Package 1 Weight 21.572 lb(US) (9.785 kg)
Unit Type of Package 2 P06
Number of Units in Package 2 8
Package 2 Height 33.86 in (86.000 cm)
Package 2 Width 23.62 in (60.000 cm)
Package 2 Length 31.50 in (80.000 cm)
Package 2 Weight 190.700 lb(US) (86.500 kg)

Product Images

Images are provided showing the physical appearance of the Altistart 480 soft starter unit from various angles, including front and rear views.

PDF preview unavailable. Download the PDF instead.

Generatepdf.aspx?salesorgid=78&dist=849&lang=42&form=no&documenttype=plain&productid=ATS480D88Y cairo 1.15.12 (http://cairographics.org)

Related Documents

Preview ALTISTART® 48 Y-Range Soft Start Controllers Installation Guide
This installation guide provides comprehensive details for Schneider Electric's ALTISTART® 48 Y-Range Soft Start Controllers (ATS48), covering technical specifications, mounting, wiring, programming, application, protection, and fault management.
Preview Schneider Electric Altistart 22 Soft Starter Data Sheet
Detailed technical specifications, features, and performance data for the Schneider Electric Altistart 22 soft starter, designed for asynchronous motors.
Preview Schneider Electric Altistart 22 Soft Starter Quick Start Guide for Motor Control Centers
Quick start guide for programming Schneider Electric Altistart 22 Soft Starters in Motor Control Centers (MCC). Includes installation, connection, and configuration instructions, safety warnings, and parameter settings.
Preview Altistart 48 Telemecanique: Manual de Operação e Instalação
Guia completo para o Altistart 48 da Telemecanique (Schneider Electric), cobrindo instalação, operação, características técnicas, esquemas de aplicação, proteções e manutenção de conversores de partida e parada progressivas.
Preview Schneider Electric ATS480 Soft Starter SCCR Ratings & Compatibility Guide
Find detailed Short Circuit Current Ratings (SCCR) and compatible component data for Schneider Electric Altivar ATS480 soft starters, tested per UL60947-4-2 for electrical system safety and performance.
Preview Altistart 48 Panel-Mount Soft Starts: Wiring Diagrams & Component Selection Guide
Comprehensive guide to recommended wiring diagrams and component selection for Schneider Electric's Altistart 48 Panel-Mount Soft Starts, including contactor and disconnect recommendations for various motor applications.
Preview Altivar Soft Starter ATS480 User Manual - Schneider Electric
Comprehensive user manual for the Schneider Electric Altivar Soft Starter ATS480, detailing installation, operation, safety, technical specifications, and troubleshooting for industrial applications.
Preview Schneider Electric Digest 176: Global Specialist in Energy Management Solutions
Explore Schneider Electric's Digest 176, a comprehensive guide to energy management and electrical distribution solutions. Discover products and services for buildings, industrial plants, data centers, and smart grids, focusing on efficiency, reliability, and sustainability.