ALTISTART® 48 Y-Range Soft Start Controllers Installation Guide

Section 1: Quick Start Procedure

⚠️ DANGER: HAZARDOUS VOLTAGE

Disconnect all power supplying this equipment prior to working on it. Failure to follow this instruction will result in death or serious injury.

1. Before installing or storing the ALTISTART® 48 (ATS48) soft starter, thoroughly inspect it according to the instructions in "Receiving and Preliminary Inspection" on page 9.

  • a. Verify that the soft starter catalog number printed on the label is the same as that on the packing slip and corresponding purchase order.
  • b. Remove the ATS48 soft starter from its packaging and check that it has not been damaged during transit. If any damage is found, notify the carrier and your Schneider Electric representative.

2. Install the ATS48 soft starter in accordance with the mounting, ventilation, and environmental requirements specified under "Mounting" on page 17.

3. With the power removed, make the following connections to the ATS48 soft starter:

  • a. Connect the 115 V or 230 Vac control supply to CL1 and CL2.
  • b. Connect the power supply to 1/L1, 3/L2, and 5/L3.
  • c. Connect the motor to 2/T1, 4/T2, and 6/T3.

NOTE: If a shorting/bypass contactor is used, connect it between L1, L2, and L3 on the line side supply terminals and A2, B2, and C2 of the ATS48 soft starter. Refer to Figure 1 and to the wiring diagrams in Appendix A beginning on page 73.

Figure 1: Power Block Diagram - Illustrates the connection of AC line supply to terminals 1/L1, 3/L2, 5/L3, the motor to terminals 2/T1, 4/T2, 6/T3, and the bypass/shorting contactor connections to A2, B2, C2.

Figure 2: Control Circuit Terminal Configuration - Shows the layout of control terminals including CL1, CL2 for control supply; PTC1, PTC2 for PTC probes; AO1, COM for analog output; LO1, LO2 for logic outputs; LO+, +24V for logic output power supply; LI3, LI4, RUN, STOP for logic inputs; R1A, R1C, R2A, R2C, R3A, R3C for relay outputs.

4. Set parameter IN (in the SEt menu, see page 41) to the motor nameplate current.

5. Apply power to the control terminals (CL1 and CL2). Do not apply power to the power terminals yet, and do not give a run command. The soft starter displays nLP to indicate that it is not powered up.

6. The ATS48 soft starter is factory configured for most standard duty applications. See Table 1 for the factory preset values. If the factory configuration is not suitable for your application, refer to "Programming" on page 37 for information on changing the parameter settings.

7. Apply power to terminals 1/L1, 3/L2, and 5/L3. The soft starter will display rdY indicating that it is powered up.

8. Connect +24 V to the RUN control terminal to start the system.

Table 1: Factory Configuration

ParameterFactory Setting
Nominal motor current (IN)Preset to correspond to 460 V rated motor current based on NFPA 70/NEC Table 430.150 ratings
Current Limit (ILt)400% of the motor current IN
Acceleration ramp (ACC)15 seconds
Initial torque on starting (tq0)20% of the nominal torque
Stop (StY)Freewheel stop (-F-)
Motor thermal protection (tHP)Class 10 thermal overload protection curve
DisplayrdY (soft starter ready) when power and control voltage are present and the motor is operating.
Logic inputsLI1: STOP, LI2: RUN, LI3: Forced freewheel stop (LIA), LI4: Forced local mode (LIL)
Logic outputsLO1: Motor thermal alarm (tA1), LO2: Motor powered (rnI)
Relay outputsR1: Fault relay (r1F), R2: Bypass relay at the end of starting, R3: Motor powered (rnI)
Analog output (AO)Motor current (OCr, 0–20 mA)
Communication parametersAdd: 0, tbr: 19200 bits per second, FOr: 8 bits, no parity, 1 stop bit (8n1)

Section 2: Receiving and Handling

Introduction

The ALTISTART 48 (ATS48) soft starter offers state-of-the-art acceleration and deceleration control of standard three-phase asynchronous induction (squirrel cage) motors. The ATS48 controller uses a patented technology to control the motor performance based on the motor torque rather than simple voltage or current based control. Advanced control algorithms are incorporated to ensure smooth rotation throughout the starting ramp without mechanical instability at the end of starting.

A microprocessor continuously monitors the motor and controller performance to provide maximum protection of the controller, motor, and driven machinery. A variety of starting and stopping modes are standard. A digital keypad display provides accurate controller setup and continuous motor performance display.

The ATS48 controller is available in twenty-one current ratings from 17 to 1200 A. All models use a common control interface for consistent and simple set up. ATS48 controllers are rated for use with 208 to 690 V motors, and are self-adjusting for a 50 or 60 Hz supply frequency.

This instruction bulletin covers the technical characteristics, specifications, installation, wiring, programming, and troubleshooting of all ATS48 controllers.

Many option kits are available for the ATS48 controllers. Refer to Appendix C beginning on page 79.

Terminology

Some of the terms and acronyms used in this manual are defined in Table 2.

Table 2: Definition of Terms

TermDefinition
FLAFull load amps: the current rating of an induction motor at rated speed and load. This value may be found on the motor nameplate.
ICLNominal current rating of the ATS48 controller. This value may be found on the controller nameplate.
INUser defined motor current rating. Same as FLA.
TNNominal motor torque as calculated by the ATS48 controller.
VNNominal voltage of supply power (mains supply). This should correspond to the motor rated voltage on the motor nameplate.

Receiving and Preliminary Inspection

Before installing the ATS48 controller, read this manual and follow all precautions.

Before removing the ATS48 controller from its packing material, verify that the packing carton is not damaged from shipping. Damage to the packing carton usually indicates improper handling. If any damage is found, notify the carrier and your Square D / Schneider Electric representative.

After removing the ATS48 controller from its packaging, inspect it for damage. If any shipping damage is found, notify the carrier and your sales representative. Verify that the ATS48 controller nameplate and label conform to the packing slip and corresponding purchase order.

⚠️ CAUTION: EQUIPMENT DAMAGE HAZARD

Do not operate or install any controller that appears damaged. Failure to follow this instruction can result in injury or equipment damage.

Storing and Shipping

If the ATS48 controller is not being immediately installed, store it in a clean, dry area where the ambient temperature is between -13 and +158 °F (-25 and +70 °C). If the ATS48 controller must be shipped to another location, use the original shipping material and carton to protect it.

Handling the Controller

Do not remove the ATS48 controller from the carton until it is at the final installation site. The carton provides protection and prevents damage to the controller's exterior. Handle the controller carefully after removing it from the carton to avoid damage to the internal components, frame, or exterior. Once removed from the carton, the controller can be handled:

  • With a hoist. When hoisting the controller, attach a spreader bar to the two lifting holes on top of the controller as shown in Figure 3.
  • In a horizontal position, with the back of the controller resting on a pallet.

The ATS48 range comprises 6 sizes, with various weights and dimensions. Small controllers can be removed from their packaging and installed without a handling device. A handling device must be used with large controllers; for this reason they are supplied with lifting holes.

NOTE: Do not rest the unit directly on the bus bar connectors.

⚠️ WARNING: HANDLING AND LIFTING HAZARD

Keep the area below any equipment being lifted clear of all personnel and property. Use the lifting method shown in Figure 3.

Failure to follow this instruction can result in death or serious injury.

Figure 3: Hoisting the ATS48 Controller - Depicts a controller being lifted using a spreader bar attached to lifting holes on the top of the unit, with a maximum tilt angle indicated.

Section 3: Technical Data

Technical Characteristics

Tables 3 and 4 describe the technical characteristics of the ATS48 controller. The information is based on operation at a maximum ambient temperature of 40 °C without a shorting/bypass contactor and at 50 °C with a shorting/bypass contactor.

The ATS48 controller can be used in an ambient temperature of up to 60 °C as long as the maximum current rating for Class 10 thermal overload protection is derated by 2% for each degree above 40 °C without a shorting/bypass contactor or by 2% for each degree above 50 °C with a shorting/bypass contactor. The nominal motor current IN must not exceed the maximum current rating for Class 10 thermal overload protection.

Table 3: Standard Duty Application, 208 to 690 V Supply (+10% to -15%, 50 or 60 Hz)

hp @ 208 Vhp @ 230 VkW @ 440 Vhp @ 460 VkW @ 500 Vhp @ 575 VkW @ 690 VMax. Current Rating for Class 10 Thermal Overload ProtectionICL RatingCatalog Number
357.510915151717ATS48D17Y
57.51115112018.52222ATS48D22Y
7.510152018.525223232ATS48D32Y
101518.5252230303838ATS48D38Y
--2022303040374747ATS48D47Y
152530403750456262ATS48D62Y
203037504560557575ATS48D75Y
254045605575758888ATS48D88Y
305055757510090110110ATS48C11Y
40607510090125110140140ATS48C14Y
507590125110150132170170ATS48C17Y
60100110150132200160210210ATS48C21Y
75125132200160250200250250ATS48C25Y
100150160250220300250320320ATS48C32Y
125200220300250350315410410ATS48C41Y
150250250350315400400480480ATS48C48Y
--300355400400500500590590ATS48C59Y
200350400500500600560660660ATS48C66Y
250400500600560800630790790ATS48C79Y
350450630800630100071010001000ATS48M10Y
4005007101000800120090012001200ATS48M12Y

Table 4: Severe Duty Application, 208 to 690 V Supply (+10% to -15%, 50 or 60 Hz)

hp @ 208 Vhp @ 230 VkW @ 440 Vhp @ 460 VkW @ 500 Vhp @ 575 VkW @ 690 VMax. Current Rating for Class 10 Thermal Overload ProtectionICL RatingCatalog Number
235.57.57.510111217ATS48D17Y
357.510915151722ATS48D22Y
57.51115112018.52232ATS48D32Y
7.510152018.525223238ATS48D38Y
101518.5252230303847ATS48D47Y
152022303040374762ATS48D62Y
202530403750456275ATS48D75Y
253037504560557588ATS48D88Y
3040456055757588110ATS48C11Y
405055757510090110140ATS48C14Y
50607510090125110140170ATS48C17Y
607590125110150132170210ATS48C21Y
75100110150132200160210250ATS48C25Y
100125132200160250200250320ATS48C32Y
125150160250220300250320410ATS48C41Y
150200220300250350315410480ATS48C48Y
--250300350315400400480590ATS48C59Y
200300355400400500500590660ATS48C66Y
250350400500500600560660790ATS48C79Y
3004005006005608006307901000ATS48M10Y
350450630800630100071010001200ATS48M12Y

Specifications

Table 5: Environmental Characteristics

CharacteristicSpecification
Degree of protectionIP20 for ATS48D17Y to C11Y; IP00 for ATS48C14Y to M12Y
Shock resistanceConforms to IEC 60068-2-27: 15 g, 11 ms
Vibration resistanceConforms to IEC 60068-2-6, NCF 20706 and BV1: 15 mm peak from 2 to 13 Hz; 1 gn from 13 to 200 Hz
Soft starter audible noise levelMeasurements taken from 3 ft (1 m) away. Noise levels vary by model: ATS48D17Y to D47Y: 52 dBA; ATS48D62Y to C11Y: 58 dBA; ATS48C14Y to C17Y: 50 dBA; ATS48C21Y to C32Y: 54 dBA; ATS48C41Y to C66Y: 55 dBA; ATS48C79Y to M12Y: 60 dBA
Resistance to electrostatic dischargesConforms to IEC 61000-4-2, Level 3
Immunity to radio-electric interferenceConforms to IEC 61000-4-3, Level 3
Immunity to rapid electrical transientsConforms to IEC 61000-4-4, Level 4
Ambient air temperatureStorage: -13 to +158 °F (-25 to +70 °C). Operation: 14 to +104 °F (-10 °C to +40 °C) without derating. Up to +140 °F (+60 °C), derate current by 2% for each °C above 40 °C. 14 to 122 °F (-10 °C to +50 °C) with user-provided shorting/bypass contactor.
Maximum relative humidity95% without condensation or dripping water conforming to IEC 60068-2-3
Maximum ambient pollutionConforms to IEC 60664-1, Pollution Degree 3
Maximum operating altitude3300 ft (1000 m) without derating. Above this, derate nominal current by 2.2% for each additional 330 ft (100 m) to a maximum of 6600 ft (2000 m).
Operating positionMaximum vertical inclination ≤10° with respect to the normal mounting position.

Table 6: Electrical Characteristics

CharacteristicSpecification
Operating categoryConforms to IEC 60947-4-2, AC-53a
Three-phase supply voltage208 Vac -15% to 690 Vac +10%, 50/60 Hz
FrequencyAutomatic sensing (preset), ±5%: 60 Hz: 56.6 to 63.8 Hz; 50 Hz: 47.6 to 52.6 Hz. Manual selection, ±20%: 50 Hz: 40 to 60 Hz; 60 Hz: 48 to 72 Hz.
Rated current (ICL)21 device ratings, 17 to 1200 A
Silicon control rectifiers (SCRs)1800 V peak inverse voltage (PIV) rating
Motor power3 to 1200 hp
Motor voltage208 / 230 / 380 / 460 / 575 / 690 Vac
Soft starter control circuit supply voltage110 Vac -15% to 230 Vac, 50/60 Hz
Maximum control circuit consumption (with fans operating)ATS48D17Y to C17Y: 30 W; ATS48C21Y to C32Y: 50 W; ATS48C41Y to M12Y: 80 W
ProtectionIntegrated thermal I²t protection for motor (Class 2, 10, 10A, 15, 20, 25, 30 or no protection) and/or thermal protection with positive temperature coefficient (PTC) probes. Motor underload settings, Current overload settings, Phase reversal, Phase loss, Automatic restart.

Table 7: Electromagnetic Compatibility (EMC)

CharacteristicStandardsTest LevelsExamples (sources of interference)
Radiated and conducted emissionsIEC 60947-4-2, Class A----
Immunity testsIEC 61000-4-2, Level 3Electrostatic discharge: 6 kV through contact, 8 kV through airContact with an electrically charged person
IEC 61000-4-3, Level 3Radiated electromagnetic fields: 10 V/mEquipment transmitting radio frequencies
IEC 61000-4-5, Level 4Rapid electrical transients: 4 kV on power supply cables, 2 kV on control supply cablesOpening/closing of a contactor
IEC 61000-4-5, Level 3Shock wave: 1 kV phase-to-phase, 2 kV phase-to-ground--
IEC 61000-4-12, Level 3Damped oscillating waves: 1 kV @ 1 MHzOscillating circuit on the line supply
Radiated and conducted emissionsIEC 60947-4-2, Class B on soft starters up to 170 A (ATS48D17Y to C17Y)--Shorting/bypass contactors must be used.

Table 8: Short Circuit Protection Device (Type 1 Coordination)

Catalog NumberRecommended OCPD Rating (A) @ 208 VRecommended OCPD Rating (A) @ 230 VRecommended OCPD Rating (A) @ 460 VRecommended OCPD Rating (A) @ 575 VShort Circuit Current Rating @ 575 V (A)Fuse Class (Time Delay)
ATS48D17Y152020255,000J
ATS48D22Y253030305,000J
ATS48D32Y354040405,000J
ATS48D38Y455050455,000J
ATS48D47Y--6060605,000J
ATS48D62Y708080805,000J
ATS48D75Y901001009010,000J
ATS48D88Y11012511011010,000J
ATS48C11Y12515015015010,000J
ATS48C14Y17520017517510,000J
ATS48C17Y20022522522510,000J
ATS48C21Y25030030030018,000J
ATS48C25Y30035035035018,000J
ATS48C32Y40045045040018,000J
ATS48C41Y50060050050030,000L (600 A) or J (500 A)
ATS48C48Y--65060070030,000L
ATS48C59Y75080070080042,000L
ATS48C66Y10001000800100085,000L
ATS48C79Y135014001100140085,000L
ATS48M10Y150016001400160085,000L
ATS48M12Y160016001600160085,000L

Dimensions and Weights

Figure 4: ATS48D17Y–C66Y Dimensions - Shows a diagram with dimensions labeled 'a', 'b', 'c', 'e', 'G', 'H', '' for various ATS48 models.

Table 9: ATS48D17Y–C66Y Dimensions

ATS48 Modela in (mm)b in (mm)c in (mm)e in (mm)G in (mm)H in (mm) in (mm)Weight lb (kg)
D17Y, D22Y, D32Y, D38Y, D47Y6.30 (160)10.83 (275)7.48 (190)0.26 (6.6)3.94 (100)10.24 (260)0.28 (7)10.8 (4.9)
D62Y, D75Y, D88Y, C11Y7.48 (190)11.42 (290)9.25 (235)0.39 (10)5.91 (150)10.63 (270)0.28 (7)18.3 (8.3)
C14Y, C17Y7.87 (200)13.39 (340)10.43 (265)0.39 (10)6.30 (160)12.60 (320)0.28 (7)27.3 (12.4)
C21Y, C25Y, C32Y12.60 (320)14.96 (380)10.43 (265)0.59 (15)9.84 (250)13.78 (350)0.35 (9)40.1(18.2)
C41Y, C48Y, C59Y, C66Y15.75 (400)26.38 (670)11.81 (300)0.79 (20)11.81 (300)24.02 (610)0.35 (9)113.3 (51.4)

Figure 5: ATS48C79Y–M12Y Dimensions - Shows a diagram with dimensions labeled 'a', 'b', 'c', 'e', 'G', 'H', '' for larger ATS48 models.

Table 10: ATS48C79Y–M12Y Dimensions

ATS48 Modela in (mm)b in (mm)c in (mm)e in (mm)G in (mm)H in (mm) in (mm)Weight lb (kg)
C79Y, M10Y, M12Y30.31 (770)35.04 (890)12.40 (315)0.79 (20)13.78 (350)33.46 (850)0.35 (9)253.6 (115)

Serial and Model Numbers

The serial and model numbers of the ATS48 controller are on the bar code sticker located on the front right hand side of the device.

Figure 6: Serial Number and Model Numbers - Illustrates the location of the serial number and model number on the controller's label.

Section 4: Mounting

Mounting Precautions

Follow these precautions when mounting the ATS48 controller:

  • Controllers are open devices and must be installed in suitable enclosures or controlled access areas. The environment around the controller must meet Pollution Degree 3 requirements as defined in NEMA ICS1-1 or IEC 60664-1.

⚠️ DANGER: HAZARDOUS VOLTAGE

ATS48 controllers are open devices and must be mounted in a suitable enclosure. Electrical shock will result in death or serious injury.

  • When the installation surface is not even, put a spacer behind the controller mounting pads to eliminate gaps. Fastening the controller exterior to an uneven surface may damage the controller.
  • When installing the controller in an enclosure, cover the device to prevent metallic debris from falling into the controller.
  • The ATS48 controller generates heat and must be properly ventilated. Refer to "Thermal Considerations for Sizing Enclosures" on page 19 to determine power dissipated.
  • When several controllers are installed in a control panel, arrange them in a row. Do not stack controllers. Heat generated from the bottom controller can adversely affect the ambient temperature around the top controller.

⚠️ CAUTION: CONTROLLER OVERHEATING

  • Mount the ATS48 controller within ±10° of vertical.
  • Do not locate the controller near heat radiating elements.
  • Electrical current through the controller will result in heat losses that must be dissipated into the ambient air immediately surrounding the controller. To prevent thermal fault or equipment damage, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the controller.

Failure to follow this instruction can result in injury or equipment damage.

Soft Starter Ventilation

On soft starters fitted with a cooling fan, the fan switches on automatically as soon as the heatsink temperature reaches 50 °C. It is switched off when the temperature drops to 40 °C.

Table 11: Fan Flow Rates

Part NumberCFMm³/hour
ATS48D32Y and D38Y2414
ATS48D47Y4828
ATS48D62Y to C11Y14686
ATS48C14Y and C17Y235138
ATS48C21Y to C32Y476280
ATS48C41Y to C66Y1020600
ATS48C79Y to M12Y20401200

Mounting in a General Purpose Metal Enclosure

Follow the instructions in this section in order to meet NEMA Type 1 (IP23) degree of protection. To ensure adequate air flow inside the controller, follow these guidelines:

  • Leave sufficient space around the controller (see Figure 7).
  • Ensure sufficient ventilation. If necessary, install a cooling fan with filters.

Figure 7: Ventilation and Clearances - Shows a diagram indicating required clearances around the soft starter for ventilation, typically 4 inches (100 mm) on sides and top/bottom.

Mounting in a Dust and Damp-Proof Metal Enclosure

Follow the instructions in this section in order to meet NEMA Type 12 (IP54) degree of protection.

Maintain clearances as shown in Figure 7. Do not use insulated or non-metallic enclosures as they have poor thermal conduction. Provide a stirring fan to circulate air inside the enclosure and prevent hot spots in the controller, as shown in Figure 8. This allows operation of the soft starter in an enclosure with a maximum internal temperature of 140 °F (60 °C). Ensure that the ambient temperature around the soft starters does not exceed this limit.

To reduce temperature rise within the enclosure, use a shorting/bypass contactor (duty cycle not to exceed 2 starts per hour) or a heat exchanger. Derate the soft starter current IN by 2% per °C for temperatures above 40 °C if a shorting/bypass contactor is not used.

Figure 8: Ventilation for Dust and Damp-Proof Enclosure - Illustrates an enclosure with a stirring fan to circulate air, showing internal (i) and external (e) ambient temperatures.

Thermal Considerations for Sizing Enclosures

When mounting the ATS48 soft starter in an enclosure, use the enclosure manufacturers' recommendations for proper sizing based on thermal considerations. For this, it is necessary to sum the power dissipated by each device in the enclosure. Table 12 lists the steady state power dissipation for the ATS48 soft starter, operating at rated current, with and without a shorting/bypass contactor.

Table 12: Watts Loss Information

Catalog NumberPower Dissipation in Watts (with Shorting/Bypass Contactor)Power Dissipation in Watts (without Shorting/Bypass Contactor)
ATS48D17Y to C17YATS48C21Y to M12YATS48D17Y to C17YATS48C21Y to M12Y
ATS48D17Y15 W50 W59 W580 W to 3497 W
ATS48D22Y15 W74 W
ATS48D32Y25 W104 W
ATS48D38Y25 W116 W
ATS48D47Y25 W142 W
ATS48D62Y25 W201 W
ATS48D75Y25 W245 W
ATS48D88Y25 W290 W
ATS48C11Y25 W322 W
ATS48C14Y25 W391 W
ATS48C17Y25 W479 W
ATS48C21Y50 W580 W
ATS48C25Y695 W
ATS48C32Y902 W
ATS48C41Y1339 W
ATS48C48Y1386 W
ATS48C59Y1731 W
ATS48C66Y1958 W
ATS48C79Y2537 W
ATS48M10Y2865 W
ATS48M12Y3497 W

The total dissipated Watts loss is provided strictly for sizing the environmental HVAC cooling requirements based upon nominal current operating conditions. The control power circuit consumption is 25 W.

Remote Keypad Display (If Used)

The VW3G48101 remote keypad display can be mounted on the door of a wall-mounted or floor-standing enclosure. The remote keypad display kit includes a seal for IP65 protection and a 9.82 ft (3 m) cable with connectors. Communication is via the RJ-45/MODBUS connection on the starter (see Figure 10). The remote keypad display has the same signaling display and configuration buttons as the controller's integral keypad display. A switch to lock access to the parameters is located at the rear of the keypad display.

Figure 9: Remote Keypad Display, Front and Rear Views - Shows the front of the display with 3-character segments and the rear with a connector access switch.

The access switch on the remote keypad display is used as follows:

  • Locked Position: Only monitoring parameters can be accessed. When the starter is running, it is not possible to select a different parameter to be displayed.
  • Partial Locked Position: Limited access to the SEt, PrO, and SUP menu parameters.
  • Unlocked Position: All parameters are accessible.

Any display restrictions to the starter by the access switch will still be in force once the controller has been disconnected and even if power to the controller is cycled.

Figure 10: Remote Keypad Display Cable Assembly and Connectors - Illustrates the connection between the ATS48 controller's RJ-45 port and the remote keypad display cable.

Section 5: Wiring

Installation Precautions

Good wiring practice requires the separation of control circuit wiring from all power (line and load) wiring. Power wiring to the motor must have the maximum possible separation from all other power wiring. Do not run them in the same conduit. This separation reduces the possibility of coupling electrical noise between circuits.

Follow these precautions when installing the ATS48 controller:

⚠️ DANGER: HAZARDOUS VOLTAGE

  • Read and understand this manual in its entirety before installing or operating ATS48 controllers. Installation, adjustment, repair, and maintenance of these controllers must be performed by qualified personnel.
  • The user is responsible for conforming to all applicable code requirements with respect to grounding all equipment. See Figures 11–15 on pages 25–29 for grounding points.
  • Many parts in this controller, including printed wiring boards, operate at line voltage. DO NOT TOUCH. Use only electrically-insulated tools while making adjustments.
  • DO NOT touch unshielded components or terminal strip screw connections with voltage present.
  • Before installing or servicing the controller:
    • Disconnect all power.
    • Place a "DO NOT TURN ON" label on the controller disconnect.
    • Lock the disconnect in the open position.
  • Install all covers before applying power or starting and stopping the controller.

Failure to follow this instruction will result in death, serious injury, or equipment damage.

  • Voltage and frequency specifications for the input line must match the controller configuration.
  • A disconnect switch must be installed between the input line and the controller.

⚠️ DANGER: HAZARDOUS VOLTAGE

The solid state switches of the ATS48 controller's power circuit do not provide complete isolation from the AC line. Due to leakage currents through the solid-state switches, hazardous voltages can be present on the controller load-side power circuit whenever power is applied to the line side of the controller.

Disconnect all power before servicing the controller or motor. Electrical shock will result in death or serious injury.

  • When using an isolation contactor, the contactor must close before or at the same time as the application of the controller run command. If line power is not detected at the L1, L2, and L3 terminals of the controller within 500 ms of this run command, a Phase Failure fault will occur.
  • External overcurrent protection devices (OCPD), either fuses or a circuit breaker, must be installed on the line-side connections of the ATS48 controller. The maximum recommended OCPD rating, along with the associated controller short circuit withstand rating, is listed in Table 8 on page 14.

⚠️ WARNING: OVERCURRENT DEVICES MUST BE PROPERLY COORDINATED

An OCPD must be installed on the line-side of the ATS48 controller to achieve published short-circuit withstand ratings. Do not exceed the maximum OCPD ratings shown in Table 8 on page 14. Do not connect the controller to a power feeder whose short circuit capacity exceeds the controller short circuit withstand rating shown in Table 8 on page 14. Failure to follow this instruction can result in death or serious injury.

Power factor correction capacitors should not be connected to a motor controlled by an ATS48 controller. If power factor correction is required, the capacitors must be located on the line-side of the controller. A separate contactor should be used to switch the capacitors off when the motor is off, or during acceleration and deceleration.

⚠️ CAUTION: EQUIPMENT DAMAGE HAZARD

Do not connect power factor correction capacitors to the load-side power circuit of the ATS48 controller. Failure to follow this instruction can result in injury or equipment damage.

The ATS48 controller uses solid-state power switches to control motor power. When checking the condition of conductor or motor insulation, do not connect the high potential dielectric test equipment or insulation resistance tester to the controller since the test voltages used may damage the controller. Always disconnect the controller from the conductors or motor before performing such tests.

⚠️ CAUTION: EQUIPMENT DAMAGE HAZARD

Do not perform high potential dielectric tests on circuits while the circuits are connected to the ATS48 controller. Any circuit requiring high potential dielectric tests must be disconnected from the controller prior to performing the test. Failure to follow this instruction can result in injury or equipment damage.

The ATS48 controller contains electronic protection to detect and signal failure of the solid-state switches. Since the solid-state switches may be incapable of completely blocking the motor power should a fault occur, auxiliary isolation on the line side of the controller is required. Use either a circuit breaker equipped with a shunt trip coil or an electromagnetic contactor. Connect the isolation device to the fault relay of the controller so that it opens the controller power circuit in the event of a controller fault. The isolation device must be capable of interrupting motor locked rotor current.

Refer to Appendix A beginning on page 73 for typical circuit diagrams that display the logic controlling the isolation device via the fault relay.

⚠️ CAUTION: MOTOR OVERHEATING

Failure of the solid-state switches on the ATS48 controller can cause single-phase operation of the motor.

  • Use an isolation device consisting of either a circuit breaker equipped with a shunt trip coil or an electromagnetic contactor to open the line-side of the controller.
  • The isolation device must be capable of interrupting the motor locked rotor current.
  • Connect the fault relay of the controller to open the isolation device in the event of a controller fault.

Failure to follow this instruction can result in injury or equipment damage.

⚠️ WARNING: BRANCH CIRCUIT CONDUCTOR HAZARD

If system grounding is not adequate to handle ground fault levels which can exceed 1300% of motor full load amps (FLA), then this device may not protect the branch circuit conductors. In this case, external ground fault protection must be properly coordinated. Recommended solutions include:

  • Time delay fuses coordinated to 125% of motor FLA. The fuses listed in Appendix B beginning on page 79 are sized to ensure proper coordination and may be used for applications that do not require start times longer than 50 seconds at 300% current limit or 20 seconds at 500% current limit.
  • External overload relay. For multi-motor applications, applications in which motor does not match the controller size, or applications that use a full voltage bypass scheme, an external overload relay can be coordinated to protect conductors from a high-impedance ground fault.

Failure to follow this instruction can result in death or serious injury.

General Wiring Practices

When wiring ATS48 controllers, follow the wiring practices required by national and local electrical codes. In addition, follow these guidelines:

  • Use metallic conduit for all controller wiring. Do not run control and power wiring in the same conduit.
  • Separate metallic conduits carrying power wiring or low-level control wiring by at least 3 in (80 mm).
  • Separate non-metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low-level control wiring by at least 12 in (305 mm).
  • Always cross power and control wiring at right angles.

Adaptation to Line Input

The control circuit is completely independent of the power circuit. To apply control voltage, follow the instructions on the label located on the controller terminal strip. Remove the terminal cover label and connect single phase voltage of 110 to 230 Vac supply to terminals CL1 and CL2.

The power circuit adapts automatically to the input line voltage and frequency over a range of 208 to 690 V (+10% to -15%) for standard controllers.

Power Connections

Table 13: Wire Size and Tightening Torque

TerminalsModel Group
ATS48D17Y– D47YATS48D62Y– C11YATS48C14Y– C17YATS48C21Y– C32YATS48C41Y– C66YATS48C79Y– M12Y
Power Input, Power Output, Bypass/Shorting ContactorL1 / L2 / L3A2 / B2 / C28 AWG (16 mm²)2/0 AWG (50 mm²)2/0 AWG (95 mm²)Bus Bar (240 mm²)Bus Bar (2x240 mm²)Bus Bar (4x240 mm²)
Max. Wire Size 1 AWG (mm²)8 AWG (16 mm²)2/0 AWG (50 mm²)2/0 AWG (95 mm²)Bus Bar (240 mm²)Bus Bar (2x240 mm²)Bus Bar (4x240 mm²)
Tightening Torque lb-in (N·m)26 lb-in (3 N·m)88 lb-in (10 N·m)300 lb-in (34 N·m)300 lb-in (34 N·m)500 lb-in (57 N·m)500 lb-in (57 N·m)
Ground ConnectionsGND8 AWG (10 mm²)4 AWG (16 mm²)Bus Bar (120 mm²)Bus Bar (120 mm²)Bus Bar (240 mm²)Bus Bar (2x240 mm²)
Max. Wire Size AWG (mm²)8 AWG (10 mm²)4 AWG (16 mm²)Bus Bar (120 mm²)Bus Bar (120 mm²)Bus Bar (240 mm²)Bus Bar (2x240 mm²)
Tightening Torque 2 lb-in (N·m)15 lb-in (1.7 N·m)26 lb-in (3 N·m)238 lb-in (27 N·m)238 lb-in (27 N·m)238 lb-in (27 N·m)238 lb-in (27 N·m)

¹ Power terminals are suitable for use with 75 °C rated conductors; copper only.

² Requires user supplied lug.

Figure 11: Power Connections ATS48D17Y to C11Y - Shows a wiring diagram for smaller ATS48 models, illustrating connections for L1, L2, L3, T1, T2, T3, A2, B2, C2 to a motor (M).

Figure 12: Power Connections ATS48C14Y to C17Y - Shows a wiring diagram with dimensions for ATS48C14Y to C17Y models.

Figure 13: Power Connections ATS48C21Y to C32Y - Shows a wiring diagram with dimensions for ATS48C21Y to C32Y models.

Figure 14: Power Connections ATS48C41Y to C66Y - Shows a wiring diagram with dimensions for ATS48C41Y to C66Y models.

Figure 15: Power Connections ATS48C79Y to M12Y - Shows a wiring diagram with dimensions for ATS48C79Y to M12Y models.

Control Connections

Although all control inputs and outputs of the controller are isolated from the input lines, follow these control wiring precautions:

  • Keep control wiring conductor runs short and direct.
  • Ensure that the control contacts used with the controller inputs are rated for operation at open circuit voltages of 24 Vdc and closed circuit currents of 10 mAdc.
  • The analog output requires twisted cable with a pitch of 1/2 inches. Use a cable shield. The shield must be terminated to ground at one end.
  • Ensure that the coils of all relays and solenoids connected to the output contacts of the controller are equipped with appropriate transient suppressors.
  • For proper control wiring, route conductors to avoid contact with other voltage potentials in the controller. Wire insulation must have the appropriate voltage rating for the voltage present.
  • The control terminals are fitted with one way plug-in connectors with:
    • Maximum wire size: 12 AWG (2.5 mm²)
    • Maximum tightening torque: 3.5 lb-in. (4 N·m)
  • On ATS48C17Y to ATS48M12Y the protective cover must be removed in order to access the control terminals.

Figure 16: Control Terminals - Depicts the layout of control terminals on the ATS48 controller, including relay outputs, logic inputs/outputs, analog output, common, PTC probes, and an RJ-45 connector.

Table 14: Control Terminal Blocks

TerminalFunctionCharacteristics
CL1, CL2Control power supply90 to 270 Vac, 50/60 Hz; Switch mode power supply with 25 VA consumption
R1A, R1CR1 Relay: N.O. programmable contactMinimum switching capacity: 10 mA for 6 Vdc; Maximum switching capacity on inductive load: 1.8 A for 230 Vac and 30 Vdc; Maximum voltage 400 Vac.
R2A, R2CR2 Relay: N.O. starting relay contact--
R3A, R3CR3 Relay: N.O. programmable contactMinimum switching capacity: 10 mA for 6 Vdc; Maximum switching capacity on inductive load: 1.8 A for 230 Vac and 30 Vdc; Maximum voltage 400 Vac.
STOPStop controller--
RUNRun controller--
LI3, LI4Programmable inputs4 logic inputs with 4.3 kΩ impedance; State 1: V > 11V, I > 5 mA; State 0: V < 5V, I < 2 mA
+24VLogic input power supplyVoltage (V): 30 V max., Current (I): 8 mA max.
LO+Logic output power supply+24 V ±25% isolated and protected against short circuits and overloads, maximum current of 200 mA. Connect to 24 V or an external supply source.
LO1Programmable logic outputs2 open collector outputs, compatible with Level 1 [PLC], IEC 60065A-68 standard.
LO2Programmable logic outputs2 open collector outputs, compatible with Level 1 [PLC], IEC 60065A-68 standard.
AO1 COMProgrammable analog outputOutput can be configured as 0–20 mA or 4–20 mA; Accuracy ±5% of the maximum value, maximum impedance 500 Ω.
PTC1, PTC2Input for PTC probes0 V; Total resistance of probe circuit: 750 Ω at 25 °C; For example, three 250 Ω probes in series.
RJ-45Connector for: Remote keypad display, PowerSuite, Communication busRS-485 MODBUS

Section 6: Application and Protection

Soft Starter Applications

The ATS48 soft starter must be selected for the nominal power of the motor and for the type of application, standard or severe duty. Standard and severe define the limiting values of the current and the duty cycle characteristics. The ATS48 controller is factory preset to start the motor in standard duty applications.

  • Standard Duty Applications: In standard duty applications, the ATS48 soft starter is designed to provide:
    • Starting at 400% of IN for 23 seconds, or 300% of IN for 46 seconds, from a cold state.
    • Starting at 400% of IN for 12 seconds, or 300% of IN for 23 seconds, with a load factor of 50% and 10 starts per hour or an equivalent thermal cycling.
    • The motor thermal protection conforms to Class 10 overload protection.
  • Severe Duty Applications: In severe duty applications, the ATS48 soft starter is designed to provide:
    • Starting at 400% of IN for 48 seconds, or 300% of IN for 90 seconds, from a cold state.
    • Starting at 400% of IN for 25 seconds with a load factor of 50% and 5 starts per hour or an equivalent thermal cycling.
    • The motor thermal protection conforms to Class 20 thermal overload protection.

Reduced Torque

The key to applying a soft start successfully is matching the load to the motor capability while starting with reduced voltage applied. The asynchronous motor associated with the ATS48 soft starter must be able to accelerate the driven load when supplied with reduced voltage and current. When reduced voltage is applied to a motor during acceleration, the current the motor draws is reduced by the ratio of the voltage applied. The torque produced by the motor varies with the square of the voltage at a fixed frequency. Figure 17 on page 32 shows the speed/torque characteristics as a function of the supply voltage.

Figure 17: Torque as a Function of Applied Voltage - Graph showing torque vs. % rated speed, with curves for Vn, 0.85Vn, and 0.6Vn, illustrating how torque decreases with reduced voltage.

Figure 18: Torque as a Function of Starting Current - Graph showing torque vs. % rated speed, illustrating starting current Id and current limit Id1 during soft start.

A soft start progressively increases voltage to the motor. By ramping the voltage, the ATS48 soft starter limits the amount of current the motor can draw during starting to a user-defined setting. Figure 18 shows the speed/torque characteristics of a motor as a function of starting current. The ATS48 soft starter provides optimal acceleration by ramping the acceleration torque within the envelope of curve Td1.

INTELE™ Braking

When using INTELE braking, the stop time (t3) is less than the freewheel stopping time (t1). INTELE braking is a two-part braking process which does not require external components. It produces less motor heat than traditional DC injection braking.

INTELE braking is best used when all of the criteria below are met:

  • 4-pole or 6-pole motors only
  • motor slip is less than or equal to 3%

The formula for calculating braking time is: t(sec) = WK² x rpm / (308 x (TFLT x 0.40)), where WK² is the connected motor load inertia (lb-ft²), rpm is the change in rpm or synchronous speed, and TFLT is the Full Load Torque (lb-ft). The calculated value must be equal to or less than 40.

Motor Protection and Diagnostics

The ATS48 controller provides state-of-the-art motor protection. On all controllers, the motor protection features are available even if a shorting/bypass contactor is used to bypass the SCRs after the motor is up to speed. To assist with troubleshooting, the 3-digit LCD displays fault status codes. The controller memory registers and maintains the previous 5 faults, even following power loss.

The ATS48 controller is a UL Listed motor controller with integrated motor and controller thermal protection. The motor and controller temperature are continuously calculated based on the controller nominal current and the current that is actually drawn. An electronic circuit, which stores the thermal state of the motor even if the supply power is disconnected, simulates the cooling curve.

Thermal Overload Protection

Overload of any kind over any duration can cause the motor temperature to rise. As Figure 19 shows, the ATS48 controller creates a digital model of the motor temperature based on two thermal images. The first (T1) represents the level of temperature rise corresponding to iron (motor frame). The second (T2) represents the temperature rise of copper (stator, windings). For each thermal image, two levels of alarm are detected.

An overload pre-alarm is signaled by logic output LO1 when the motor has exceeded its nominal temperature rise threshold. A pre-alarm is signaled when the thermal state exceeds 105% for T1 and/or 130% for T2.

A thermal fault signal stops the motor when the temperature rise exceeds the critical threshold. A thermal fault is signaled by relay R1 when the motor thermal state exceeds 110% for T1 and 140% for T2.

Figure 19: Thermal Trip Curves - Graph showing time vs. I/IN ratio, illustrating pre-alarm and fault trip points for T1 and T2 thermal models.

The ATS48 controller is preset to provide Class 10 thermal overload protection for standard duty applications. The ATS48 controller can be adjusted to provide Class 2, 10A, 10, 15, 20, 25, or 30 thermal overload protection, as necessary. Class 2 protection is available for applications such as submersible pumps, where very tight control of motor temperature is required. Class 30 protection is available for applications such as high inertia loading, where a longer than normal starting time is required to accelerate the load to full speed. In addition, the internal overload protection may be disabled if motor protection is provided externally. The various thermal overload protection classes are defined to meet the standards of IEC 60947-4-2 for starting from both cold and hot states. A cold state is defined as the stabilized motor thermal state when the motor is off. Figure 20 shows the approximate trip times for starting from a cold state.

Figure 20: Cold Start Curves - Graph showing time (s) vs. I/IN ratio, illustrating trip times for Class 2, 10A, 10, 15, 20, 25, 30 protection classes during cold starts.

Table 15: Cold Start Trip Time

Application3 IN5 IN
Standard Application (Class 10 Thermal Overload Protection)46 s15 s
Severe Application (Class 20 Thermal Overload Protection)63 s29 s

Figure 21: Hot Start Curves - Graph showing time (s) vs. I/IN ratio, illustrating trip times for protection classes during hot starts.

Table 16: Hot Start Trip Time

Application3 IN5 IN
Standard Application (Class 10 Thermal Overload Protection)23 s7.5 s
Severe Application (Class 20 Thermal Overload Protection)32 s15 s

Motor Thermal Protection with PTC Probes

PTC probes integrated in the motor to measure the motor temperature can be connected to the control card terminals. This analog value is managed by the controller.

The PTC probe thermal overshoot value can be processed and used in two ways:

  • To stop the machine in the event of a fault if the signal is active.
  • To activate an alarm if the signal is active. This alarm can be displayed in a controller status word (serial link) or on a configurable logic output.

NOTE: PTC probe protection does not deactivate the motor thermal protection provided by the calculation. Both types of protection can operate in parallel.

Preventive Maintenance

The following steps should be done at regular intervals:

  1. Check the condition and tightness of the connections.
  2. Make sure ventilation is effective and the temperature around the controller remains at an acceptable level.
  3. Remove any dust and debris from the controller, if necessary.

Section 7: Programming

Programming and Setup

⚠️ WARNING: LOSS OF CONTROL

  • The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure.
  • Examples of critical control functions are Emergency Stop and Overtravel Stop.
  • Separate or redundant control paths must be provided for critical control functions.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

If starting the soft starter from line power, limit operations to the duty cycle ratings described on page 31. Use inputs LI1 to LI4 to control the soft starter.

When changing the factory configuration, record your parameter settings in the Factory Settings table beginning on page 69.

When first commissioning an ATS48 controller on a 60 Hz system, perform a factory parameter reset (see FCS on page 50).

Programming the ATS48 controller is simplified by internal sequence selections and interlocks. For ease of setup, Square D recommends accessing the menus in the following order:

  1. IO – Assignment of the inputs/outputs
  2. drC – Advanced settings
  3. SEt – Settings

Some steps may not be necessary.

Copy and use the Factory Settings table on pages 69–72 to record your settings.

Display Unit and Programming

Figure 22: Display Functions - Shows the controller's display interface with navigation buttons (ESC, ENT, Up/Down arrows) and their functions.

NOTE: Pressing Up or Down arrows does not store the choices. To store the displayed choice, press ENT. The display flashes when a value is stored.

Display Principle

The display principle for numbers differs depending on the maximum scale of the parameter and its value, see Table 17 for examples.

Table 17: How to Read Displayed Numbers

RangeDisplay ExampleValue
Max. scale 999005.55.5
55.055
55.555.5
555555
Max. scale 999005.555550
0055
05555
550550
5.555550
55.555500

Menus

Menus are accessible in the order shown in Figure 23.

Figure 23: Accessing Menus - Flowchart showing the navigation path through the main menus (XXX, SEt, PrO, drC, IO, St2, COP, SUP).

Figure 24: Accessing Parameters - Illustrates how to navigate within a menu to select and modify a parameter value.

To store the displayed choice, press ENT. The display flashes when a value is stored. Navigate through the menus, depending upon the button pressed, as shown in Figure 24.

Table 18: Soft Starter Status Codes

Status CodeCondition
nLPSoft starter without run command and: Power not supplied
rdYPower supplied
tbSStarting time delay not elapsed
HEAMotor heating in progress
brLSoft starter with run command
StbSoft starter braking
--Waiting for a command (RUN or STOP) in cascade mode

Table 18 also lists monitoring parameters selected by the user (SUP menu), with factory setting as motor current.

Figure 25: Settings Menu (SEt) - Overview of parameters within the Settings menu, including IN, ILt, ACC, tq0, StY, dEC, EdC, brC, EbA.

Table 19: Settings Menu (SEt) Parameters

CodeDescriptionSetting RangeFactory Setting
InNominal motor current0.4 to 1.3 ICL*
ILtCurrent limit150 to 700% of IN, limited to 500% of ICL400% of IN
ACCAcceleration ramp time1 to 60 s15 s
tq0Initial starting torque0 to 100% of TN20%
StYType of stop-d-, -b-, -F--F-
dECDeceleration ramp time1 to 60 s15 s
EdCFinal deceleration torque0 to 100%20%
brCInternal braking torque level0 to 100%50%
EbAInjection time at the end of braking20 to 100%20%

* The factory setting corresponds to the usual value of a 460 V standardized motor in accordance with NEC and with Class 10 thermal overload protection.

Figure 26: Protection Menu (PrO) - Overview of parameters within the Protection menu, including tHP, ULL, LUL, tUL, tLS, OIL, LOC, tOL, PHr, tbS, PHL, PtC, ArS, rtH.

Table 20: Protection Menu (PrO) Parameters

CodeDescriptionSetting RangeFactory Setting
tHPMotor thermal protectionOFF, 2, 10A, 10, 15, 20, 25, 3010
ULLActivation of motor underloadOFF, ALA, dEFOFF
LULMotor underload threshold20% to 100% of TN60%
tULMotor underload time1 to 60 s60 s
tLSExcessive starting time (fault)OFF, 10 to 999 sOFF
OILActivation of current overloadOFF, ALA, dEFOFF
LOCCurrent overload threshold50% to 300% of IN80%
tOLCurrent overload time0.1 to 60 s10 s
PHrProtection against line phase inversionno, 123, 321no
tbSTime before restarting0 to 999 s2 s
PHLPhase loss threshold5 to 10%10%
PtCActivation of motor monitoring by PTC probesOFF, ALA, dEFOFF
ArSAutomatic restartOFF, OnOFF
rtHReset motor thermal stateno, YESno

⚠️ CAUTION: UNINTENDED OPERATION

  • The factory configuration of a monitoring alarm (ALA) indicates the presence of a fault but will not directly protect the installation.
  • When using parameter ArS, ensure that an accidental start will not endanger personnel or equipment in any way.

Failure to follow this instruction can result in death or serious injury.

Figure 27: Advanced Setting Menu (drC) - Overview of parameters within the Advanced Setting menu, including tLI, bSt, SSt, CLP, LSC, tIG, CSC, ULn, FrC, rPr, FCS.

Table 21: Advanced Setting Menu (drC) Parameters

CodeDescriptionSetting RangeFactory Setting
tLITorque limitOFF, 10 to 200% or OFFOFF
bStVoltage boost level50 to 100% or OFFOFF
SStTests on small motorOn, OFFOFF
CLPTorque control (type of control)On, OFFOn
LSCStator loss compensation0 to 90%50%
tIGDeceleration gain (for torque control)10 to 50%40%
CSCActivation of the cascade functionOn, OFFOFF
ULnLine voltage180 to 790 V690 V
FrCLine frequency50, 60, AUtAUt
rPrReset kWh or the operating timeno, APH, trEno
FCSReturn to factory settingsno, YESno

⚠️ CAUTION: NO BRAKING AND LIMITED STOPPING

With parameter dLt, only freewheel type stopping is possible: Cascading is not possible, Preheating is not possible. This limitation can result in injury.

Figure 28: I/O Menu (IO) - Overview of parameters for assigning logic inputs, logic outputs, relay outputs, and analog output.

Table 22: I/O Menu (IO) Parameters

CodeDescriptionSetting RangeFactory Setting
LI3Logic inputsno, LIA, LIE, LIH, LIL, LII, LIt, LIC, LIR, LISLIA
LI4
IPrPreheating level0 to 100%0%
tPrTime delay before preheating0 to 999 minutes5 mn
LO1Logic outputsno, tAI, rnI, AIL, AUL, APC, AS2tAI
LO2
r1Relay R1no, r1F, r1Ir1F
r3
R2End of starting relay R2----
AOAnalog outputno, OCr, Otr, OtH, OCO, OPrOCr
ASCConfiguration of the analog output AO020, 420020
Scaling of the analog output50 to 500%200

Figure 29: Second Motor Parameters Menu (St2) - Overview of parameters for configuring a second motor or a second set of parameters.

Table 23: Second Motor Parameters Menu (St2) Parameters

CodeDescriptionSetting RangeFactory Setting
In2Nominal motor current0.4 to 1.3 ICLDepends upon starter rating.
IL2Current limit150 to 700% of IN, limited to 500% of ICL400%
AC2Acceleration ramp time1 to 60 s15 s
tq2Initial starting torque0 to 100% of TN20%
dE2Deceleration ramp time1 to 60 s15 s
Ed2Threshold for changing to freewheel stop mode at the end of deceleration0 to 100% of estimated torque20%
tL2Maximum torque limitOFF, 10 to 200%OFF
tI2Deceleration gain (for torque control)10 to 50%40%

Figure 30: Communication Menu (COP) - Overview of parameters for communication settings, including Add, tbr, FOr, tLP, PCt.

Table 24: Communication Menu (COP) Parameters

CodeDescriptionSetting RangeFactory Setting
AddSoft starter address by the RS-485 serial link0 to 310
tbrCommunication speed in kbps.4.8, 9.6, 19.219.2
FOrCommunication format8o1, 8E1, 8n1, 8n28n1
tLPSerial link timeout setting0.1 to 60 s5 s
PCtConfiguration of the serial link for communication with the remote keypad displayOn, OFFOFF

⚠️ WARNING: LOSS OF COMMUNICATION CAN CAUSE LOSS OF PROTECTION

When using parameter tLP, ensure that the time set will not interfere with the safe operation of the machine. Failure to follow this instruction can result in death or serious injury.

Figure 31: Parameter Displayed Menu (SUP) - Lists parameters that can be displayed, such as COS, tHr, LCr, rnt, LPr, Ltr, LAP, EtA, LFt, PHE, COd.

Table 25: Parameter Displayed Menu (SUP) Parameters

CodeParameterUnitDescription
COSPower Factor----
tHrMotor thermal state%Varies from 0 to 125%. 100% corresponds to the nominal thermal state for the current IN set.
LCrMotor currentA or kAIn amperes up to 999 A (examples: 01.5 is 1.5 A, 15.0 is 15 A, 150 is 150 A). In kiloamperes starting at 1000 A (examples: 1.50 is 1500 A, 1.15 is 1150 A).
rntOperating timeh or khOperating time in hours since the last reset. In hours up to 999 hrs (examples: 001 is 1 hr and 111 is 111 hrs). In kilo-hours from 1000 to 65535 (examples: 1.11 is 1110 hrs and 11.1 is 11100 hrs). Above 65535 hrs (65.5) the display resets to zero. Operating time is counted when the motor is not stopped, i.e. when the thyristors are fired (heating, acceleration, steady state, deceleration, braking) and in continuous bypass operation. The hour counter can be reset in line mode using the control word or via the keypad display with the motor stopped. When the power is removed from the 115 Vac control power supply the hour counter is saved in the EEPROM.
LPrActive power%Varies from 0 to 255%. 100% corresponds to the power at nominal current and at full voltage.
LtrMotor torque%Varies from 0 to 255%. 100% corresponds to the nominal torque.
LAPActive power in kWkWThis parameter requires configuration of the exact value of the line voltage ULn in the drC menu.
EtADisplay of the current state--nLP: soft starter without run command and power not supplied; rdY: soft starter without run command and power supplied; tbS: starting time delay not elapsed; ACC: acceleration in progress; dEC: deceleration in progress; rUn: steady state operation; brL: braking in progress; CLI: soft starter in current limiting mode; nSt: force to freewheel stop by serial link.
LFtLast fault detected--See page 63. If no faults have been saved, the display shows nOF.
PHEPhase rotation direction--123: forward (L1 - L2 - L3); 321: reverse (L3 - L2 - L1).
COdKeypad display locking code--OFF: no access locking codes. To lock access, enter a code (2 to 999). The number displayed can be increased using the q key. Now press ENT. On appears on the screen to indicate that the parameters have been locked. On: a code is locking access (2 to 999). To unlock access, enter the code (increasing the number displayed using the q key) and press ENT. The code remains on the display and access is unlocked until the next power down. Parameter access will be locked again on the next power-up. If an incorrect code is entered, On appears on the display and the parameters remain locked. XXX: parameter access is unlocked (the code remains on the screen). To reactivate locking with the same code when the parameters have been unlocked, return to On using the p button and then press ENT. On appears on the screen to indicate that the parameters have been locked. To lock access with a new code when the parameters have been unlocked, enter a new code (change the number displayed using the q or p keys) and press ENT. On appears on the screen to indicate that the parameters have been locked. To clear locking when the parameters have been unlocked, return to OFF using the p button and press ENT. OFF remains on the screen. The parameters are unlocked and will remain unlocked until the next restart. Remember to document your access code (password). Failure to do so could prevent use of the keypad in programming and configuration modes. When access is locked using a code, only the monitoring parameters can be accessed, and with only a temporary choice of parameter displayed.

Figure 32: Compatibility - Table showing compatibility between various functions like Soft stop, INTELE braking, Thermal protection, etc.

Section 8: Fault Management

As a general rule, if a problem arises when the soft starter is started, it is advisable to restore the factory settings and reprogram your settings one by one. If this does not fix the problem follow the instructions below.

Soft Starter Does Not Start, No Fault Displayed

Determine whether or not the code displayed corresponds to the normal state of the soft starter (see Table 17 on page 38).

If no fault is displayed and the soft starter does not start:

  • Check that the line supply is present on the control supply CL1/CL2 (see page 30).
  • Check for the presence of the RUN/STOP commands (see Appendix A).

Non-Resettable Faults

When a non-resettable fault appears the soft starter locks and the motor switches to freewheel mode.

The following are signals that a non-reset fault has occurred:

  • Relay R2 opens.
  • After the soft starter locks, Relay R1 opens.
  • The fault code flashes on the display.
  • The last 5 faults are stored and viewable with the PowerSuite software workshop.

Do the following before restarting the soft starter:

  • Remove the fault cause(s), see Table 26.
  • Disconnect and reconnect the control supply.

Table 26: Non-Reset Fault Correction

Fault DisplayedProbable CauseCorrective Action
InFInternal faultDisconnect and reconnect the control supply. If the fault persists, contact Schneider Electric product support.
DCFOvercurrent: impeding short-circuit on soft starter output, internal short-circuit, bypass contactor stuck, soft starter is overloadedDisconnect power to the soft starter, then: Check the connecting cables and the motor isolation. Check the thyristors. Check the bypass contactor for a stuck contact. Check the parameter value bSt in the menu drC (page 49).
PIFPhase inversion: The line phase inversion does not conform to the PHr parameter settingInvert two line phases or set PHr to no.
EEFInternal memory faultDisconnect and reconnect the control supply. If the fault persists, contact Schneider Electric product support.

Resettable Faults When Causes Disappear

When a resettable fault appears the soft starter locks and the motor switches to freewheel mode.

The following are signals that a resettable fault has occurred:

  • Relay R2 opens.
  • If relay R1 is configured as an isolating relay, it opens.
  • The fault code flashes on the display as long as the fault is present.
  • The last 5 faults are stored and viewable with the PowerSuite software workshop.

Do the following before restarting the soft starter:

  • Remove the cause of the fault, see Table 27.
  • In 2-wire control, maintain the run command on the RUN input.
  • In 3-wire control, initiate a new run command (rising edge) on the RUN input.

Table 27: Resettable Fault Correction

Fault DisplayedProbable CauseCorrective Action
CFFInvalid configuration on power-upRevert to the factory setting in the drive menu drC. Reconfigure the soft starter.
CFIInvalid configuration: The configuration loaded in the soft starter via the serial link is incompatible.Check the initial configuration. Load a compatible configuration.

Auto-Reset Faults (Customer Configurable)

When an auto-reset fault appears the soft starter locks and the motor switches to freewheel mode. When an auto-reset fault occurs, the soft starter will automatically restart when the fault has cleared.

The following are signals that an auto-reset fault has occurred:

  • Relay R2 opens.
  • If relay R1 is configured as an isolating relay, it opens. R1 remains closed if it is configured as a fault relay, see page 53.
  • The fault code flashes on the display as long as the fault is present.
  • The last 5 faults are stored and viewable with the PowerSuite software workshop.

In 2-wire control, perform the following steps for any of the faults listed in Table 28 before restarting the soft starter:

  • Remove the cause of the fault.
  • Maintain the run command on the RUN input.

NOTE: The soft starter attempts to restart six times at 60 second intervals. If the fault is still present at the 6th attempt it trips, requiring a manual reset (see "Manual-Reset Faults" on page 65). If relay R1 is configured as a fault relay it opens. The run command must be maintained.

Table 28: Auto-Reset Fault Correction (2-wire control)

Fault DisplayedProbable CauseCorrective Action
PHFLoss of a line phaseCheck the line, the connection to the soft starter, and any isolating devices located between the line and the soft starter (such as contactors, fuses, and circuit-breakers).
FrFLine frequency is out of tolerance. This fault can be configured in the Advanced settings menu drC, parameter FrC.Check the line. Ensure that parameter FrC is configured properly for the line used (generating set for example).

For any of the faults listed in Table 29 perform the following steps before restarting the soft starter:

  • Remove the cause of the fault.
  • In 2-wire control, maintain the run command.

Table 29: Auto-Reset Fault Correction

Fault DisplayedProbable CauseCorrective Action
USFPower supply fault on a run commandCheck the power supply circuit and voltage.
CLFControl line failureLoss of CL1/CL2 for more than 200 ms.

If the automatic restart function is not selected, see "Manual-Reset Faults" below for the indication of these faults and the restart instructions.

Manual-Reset Faults

When a manual reset fault appears, the soft starter locks and the motor switches to freewheel mode.

The following are signals that a manual-reset fault has occurred:

  • Relay R2 opens.
  • Relay R1 opens.
  • The fault code flashes on the display as long as the fault is present.
  • The last 5 faults are stored and viewable with the PowerSuite software workshop.

Perform the following steps before restarting the soft starter:

  • Remove cause of the fault.
  • In 2-wire and 3-wire control, initiate a new run command (rising edge) on the RUN input to reset the fault.

NOTE: A reset will not take place on a run command if LI is assigned to the fault reset (LIr) function. In 2-wire and 3-wire control, initiate another new run command (rising edge) on the RUN input to reset the fault.

Table 30: Manual-Reset Fault Correction

Fault DisplayedProbable CauseCorrective Action
SLFSerial link faultCheck the RS-485 connection.
EtFExternal faultCheck the custom fault. Check the mechanism for wear, mechanical play, lubrication, blockages, etc. Check the value of the tLs setting in the PrO menu, page 45. Make sure the soft starter and motor are sized properly for the load and application.
OLCCurrent overloadCheck the mechanism for wear, mechanical play, lubrication, blockages, etc. Check the value of parameters LOC and tOL in the PrO menu, page 46.
OLFMotor thermal faultCheck the mechanism for wear, mechanical play, lubrication, blockages, etc. Make sure the soft starter and motor are sized properly for the load and application. Check the value of parameter tHP in the PrO menu (page 45) and that of parameter IN in the SEt menu, page 41. Check the electrical isolation of the motor. Wait for the motor to cool before restarting.
OtFMotor thermal fault detected by the PTC probesCheck the mechanism for wear, mechanical play, lubrication, blockages, etc. Make sure the soft starter and motor are sized properly for the load and application. Check the value of the PtC setting in the PrO menu, page 46. Wait for the motor to cool before restarting.
ULFMotor underloadCheck the hydraulic circuit. Check the value of parameters LUL and tUL in the PrO menu, page 45.
LrFLocked rotor in steady stateThis fault is only active in steady state with soft starter bypass contactor. Check the mechanism for wear, mechanical play, lubrication, blockages, etc. It is detected if the current in a phase is greater than or equal to 5 IN for more than 0.2 s.

Reset Faults Using a Logic Input

If a logic input LI is configured to reset motor thermal fault, LIt, or any other resettable fault, LIr, for the motor to restart, the following conditions must be met:

  • The soft starter must send a pulse on logic input LI.
  • In 2-wire control, the run command must be maintained on the RUN input.
  • In 3-wire control, a new run command (rising edge) must be initiated on the RUN input.

Troubleshooting Procedure

When troubleshooting the soft starter, discuss the symptoms of the reported problem with the operating personnel. Ask the operator to describe the problem and to identify when and where it first occurred. Then directly observe the controller and process. Copy the Troubleshooting Sheet on page 68 and use it to record the controller, motor, and peripheral equipment nameplate data.

Technical Support

For more information, call, fax, or write:

Square D / Schneider Electric Technical Support
8001 Highway 64 East
Knightdale, NC 27545-9023
Telephone: 919-266-8600 or 1-888-SQUARED (1-888-778-2733)
Fax: 919-217-6508
e-Mail: drivespsg@squared.com

ATS48 Troubleshooting Sheet

When requesting after-sales service, it is important to disclose all conditions under which the Square D / Schneider Electric equipment currently operates. This will help in diagnosing the system quickly. FAX to: Technical Support @ 919-217-6508

DATE: CONTACT NAME: COMPANY: ADDRESS: CITY: STATE: PHONE: FAX:

SOFT START CONFIGURATION PART NUMBER: ATS48 APPLICATION/EQUIPMENT DESIGNATION:

SERIAL NUMBER: 6W-

MOTOR NAMEPLATE DATA

HORSEPOWER: SERVICE FACTOR: MOTOR CABLE TYPE: VOLTAGE (3 PHASE): MOTOR TYPE/DESIGN: FREQUENCY: POLES: FLA: NEMA A NEMA B NEMA C NEMA D APPROXIMATE CABLE LENGTH (IN FEET):

POWER SOURCE AND ENVIRONMENT

VOLTAGE BETWEEN L1 AND L2: SERVICE TRANSFORMER RATING: VOLTAGE BETWEEN L2 AND L3: VOLTAGE BETWEEN L3 AND L1: KVA, % Z FREQUENCY: 60HZ OR 50 HZ AMBIENT TEMPERATURES: MIN °C (°F) MAX °C (°F) HUMIDITY: ALTITUDE IF GREATER THAN 3300 FEET ABOVE SEA LEVEL, SPECIFY: FT

SOFT START FAULT CODES

REFER TO TABLES 28 THROUGH 33 FOR POSSIBLE CAUSES & CORRECTIVE ACTION

NON-RESET FAULTS

INF – INTERNAL FAULT OCF - OVERCURRENT PIF – PHASE INVERSION EEF – INTERNAL MEMORY

AUTO-RESET FAULTS (CUSTOMER CONFIGURABLE)

PHF – LOSS OF PHASE OR LOSS OF MOTOR PHASE FRF – LINE FREQUENCY (OUT OF TOLERANCE) USF – POWER SUPPLY CLF – CONTROL LINE FAILURE (CL1/CL2)

MANUAL RESET FAULTS

SLF – SERIAL LINK FAULT ETF – EXTERNAL FAULT STF – EXCESSIVE STARTING TIME OLC – CURRENT OVERLOAD OLF – MOTOR THERMAL FAULT OHF – STARTER THERMAL FAULT OTF – MOTOR THERMAL FAULT VIA PTC PROBES ULF – MOTOR UNDERLOAD LrF – LOCKED ROTOR (IN STEADY STATE)

RESETTABLE FAULTS WHEN CAUSES DISAPPEAR

CFF – INVALID CONFIGURATION (POWER UP) CFI – INVALID CONFIGURATION (COMM)

DETAILED DESCRIPTION OF PROBLEM (ATTACH WIRING DIAGRAM/SCHEMATICS IF APPLICABLE):

Appendices

Appendix A: Recommended Wiring Diagrams

Figures 33–35 illustrate circuit diagrams for typical non-reversing and reversing applications in 2-wire and 3-wire control. The recommended circuit diagrams include SCR fault isolation for optimal protection of the motor, driven machinery, and operating personnel.

Table 31: Description of Logic for Recommended Wiring Diagrams

ItemNameDescription
IC1Isolation Contactor (Fwd)The isolation contactor logic closes IC1 upon a start command and opens IC1 after the stop is complete. The RCR (or RFR and RRR for reversing) are timed contacts that must have a time delay greater than the deceleration ramp time or the INTELE braking time. When a coast stop is selected, the time delay must be set for a time that will allow complete decay of the motor residual voltage. The isolation contactor opens immediately upon a fault. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.
IC1A----
IC2Isolation Contactor (Rev)Used for reversing applications only, the IC2 must be mechanically interlocked to IC1. A reversing contactor may be used for the combination of IC1 and IC2. In general, the operation of IC2 is identical to IC1. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.
IC2A----
SCShorting ContactorThe shorting contactor is used to reduce the heat dissipated by the controller when the motor is operating at full speed and voltage. The controller provides proper sequencing of this contactor by the "end-start-up" relay. When the start is completed, the shorting contactor will be commanded to close. The controller will continue to monitor the motor thermal state and provide motor overload protection. Upon a stop command, the SC contactor will open, transferring the motor current to the SCRs to allow for controlled deceleration if desired. The pilot relay (SCA) is required when the SC contactor coil exceeds the relay rating.
SCAShorting Contactor and Pilot Relay--
TSTransient SuppressorsTransient suppression of all relay and contactor coils (except ST) is recommended to minimize the possibility of electrical interference with the controller electronics and to increase relay contact life.
RCRRun Command RelayUsed in all non-reversing logic (optional in shunt trip) for proper sequencing of contactor logic. When energized, RCR initiates the start sequence. When de-energized, stopping is initiated. Operator controls can be either on/off selector switch, HOA selector switch or start/stop push buttons. RCR remains energized during a fault. Once the fault condition has been cleared, RCR must be de-energized by a "stop" command then re-energized to restart the controller.
RFRRun Forward RelayUsed for reversing applications only, this coil duplicates the functionality of RCR for the forward direction and is interlocked with the RFR relay.
RRRRun Reverse RelayUsed for reversing applications only, this coil duplicates the functionality of RCR for the reverse direction and is interlocked with the RRR relay.
STShunt Trip CoilThis coil is attached to the shunt trip coil on the disconnect and will energize 2 seconds after a controller fault by the TR timer contact. The time delay is to prevent nuisance tripping of the circuit breaker during controller power-up or during line undervoltage conditions.
TRTrip RelayUsed in shunt trip circuit breaker logic only; coil energized upon a controller fault.
FRFault RelayUsed with logic diagrams that use an isolation contactor. The fault relay is energized during normal operation and de-energizes if the controller fault contacts open or if the motor thermal switch (if supplied) opens. FR also provides additional contacts for the controller fault output.

Figure 33: Nonreversing with Shunt Trip Fault Isolation - Illustrates a wiring diagram for a non-reversing application using a circuit breaker with a shunt trip coil for fault isolation.

Figure 34: Nonreversing with Isolation Contactor - Illustrates a wiring diagram for a non-reversing application using an isolation contactor for fault isolation.

Figure 35: Reversing with Isolation Contactors - Illustrates a wiring diagram for a reversing application using isolation contactors for fault isolation.

Appendix B: Recommended Component Lists

Table 32: Suggested Components for Standard Duty Applications - Lists suggested components like induction motors, ATS48 controllers, contactors, fuses, and fuse blocks for various motor horsepower ratings.

Table 33: Additional Suggested Components for Standard Duty Applications

ATS48 Controller ModelIC1¹ ² ³ Isolation ContactorIC2¹ ² ³ Reversing Mechanical Contactor 6 InterlockSC¹ ² ³ Shorting Contactor (AC1)Fusible Disconnect 4Power Fuses Class/RatingFuse Block 7Molded Case Switch 8Thermal Magnetic Circuit Breaker 4, 8, 5
D17YLC1D18LC1D189 LC1D18J / 2560308JFHL36000MFAL36000M
D22YLC1D25LC1D259 LC1D25J / 3060308JFHL36000MFAL36040M
D32YLC1D32LC1D329 LC1D32J / 4060608JFHL36000MFAL36050M
D38YLC1D40LC1D409 LC1D40J / 5060608JFHL36000MFAL36060M
D47YLC1D50LC1D509 LC1D50J / 6060608JFHL36000MFAL36080M
D62YLC1D65LC1D659 LC1D65J / 8061038JFHL36000MFAL36090M
D75YLC1D80LC1D809 LC1D80J / 10061038JFHL36000MFAL36100M
D88YLC1D80LC1D809 LC1D80J / 12062003JKHL36000MKAL36110M
C11YLC1D115LC1D1159 LC1D115J / 15062003JKHL36000MKAL36150M
C14YLC1D150LC1D1509 LC1D150J / 20062003JKHL36000MKAL36200M
C17YLC1F185LC1F185LA9FF970 LC1F185J / 22564033JLHL36000MLAL36225M
C21YLC1F265LC1F265LA9FG970 LC1F265J / 30064033JLHL36000MLAL36250M
C25YLC1F265LC1F265LA9FJ970 LC1F265J / 35064033JLHL36000MLAL36350M
C32YLC1F400LC1F400LA9FJ970 LC1F400J / 40064033JLHL36000MLAL36400M
C41YLC1F400LC1F400LA9FJ970 LC1F400J / 5006633JMHL36000MMAL36500M
C48YLC1F500LC1F500LA9FJ970 LC1F500J / 6006633JMHL360006MMAL36600M
C59YLC1F630LC1F630LA9FJ970 LC1F630L / 7007MHL360008MMAL36800M
C66YLC1F800LC1F800LA9FJ970 LC1F800L / 9007MHL360008MMAL36900M
C79YLC1BL33LC1BL33LA9FL970 LC1BL33L / 11007MHL36000M10
M10YLC1BL33LC1BL33LA9FL970 LC1BL33L / 13507MHL36000M10
M12YLC1BP33LC1BP33LA9FX970 LC1BP33L / 16007NCL3600012M10

¹ All coils are selected for 120 V, 60 Hz operation. Refer to the Square D Digest for additional coil voltages or auxiliary contact configurations. One block may be added to each contactor.

² Power terminals are not included with LC1-F contactors. Refer to the latest editions of Square D / Schneider Electric's full line product catalogs for additional ordering information.

³ The use of transient suppressors across all contactor coils is recommended. Refer to the latest editions of Square D / Schneider Electric's full line product catalogs for selection of transient suppressors.

⁴ According to the National Electrical Code, branch circuit overcurrent protection must be provided for each controller. Short circuit protective devices recommended in this table are within NEC requirements for Type 1 coordination.

⁵ According to the National Electrical Code, branch circuit overcurrent protection must be provided for each controller. Short circuit protective devices recommended in this table are within NEC requirements for Type 1 coordination.

⁶ Reversing contactors for C11 through M12 controllers must be assembled from components. Parts quantities for a basic contactor assembly, minus the power connection links and terminals, are indicated before each part number. Refer to the latest editions of Square D / Schneider Electric's full line product catalogs for power connector link and terminal kits. Reversing contactor interlock units used for the C79 through M12 controllers are designed for vertical interlocking of the individual contactors. Horizontally interlocked contactors are used for D17 through C59 controllers.

⁷ Fuse holder part number references are for Class J fuses only based on Ferraz Shawmut spring reinforced with box type connectors acceptable for Al/Cu wiring. Class L fuses require bolt-on connections to user-supplied power bus work.

⁸ The molded case switches and circuit breakers selected require the addition of operator mechanisms to allow operation from the exterior of an enclosure. Refer to the latest editions of Square D / Schneider Electric's full line product catalogs for operator mechanism information. When using a shunt trip relay for SCR fault isolation, order a disconnect switch with suffix -1021 for addition of shunt trip coil.

⁹ The D Line contactor is available as a reversing configuration. For these applications, change the IC1 part number prefix from LC1- to LC2- to order the IC1 and IC2 combination complete with mechanical interlocks.

¹⁰ Devices rated above 660 A have not been coordinated with circuit breakers. You must use a Class L fuse for overcurrent protection with ATS48 controller models C79, M10, and M12.

Appendix C: Options and Accessories

Tables 34–36 show the accessories available for ATS48 soft start controllers.

Table 34: Documentation

Part NumberDescription
VVDED302023MODBUS Protocol User's Manual (multilingual)
DCICD398111Communications: Ethernet, FIPIO, DeviceNet, Profibus DP User's Manual (CD-ROM version only)

Table 35: Remote Keypad Display

Part NumberDescription
VW3G48101Remote mounting kit for keypad display (IP54).
  • 7-segment remote keypad display
  • Mounting kit containing cover, screws, and an IP54 seal on the front panel.
  • 9.8 ft (3 m) cable with a 9-way SUB-D connector for keypad display and an RJ-45 connector for connecting to an ATS48 controller.

Table 36: Protective Covers for Power Terminals

Part NumberDescription
LA9F702Set of six protective covers for ATS48C14Y to ATS48C17Y.
LA9F703Set of six protective covers for ATS48C21Y, ATS48C25Y, and ATS48C32Y

NOTE: The ATS48 controller has 9 unprotected power terminals.

PowerSuite Advanced Dialogue Solutions

PowerSuite solutions are compatible with software version 1.30, build 5.

Table 37: Pocket PC/PDA Kits

Part NumberDescription
VW3A8108EN (English)
VW3A8108FR (French)
VW3A8108SP (Spanish)
Complete PowerSuite Pak includes:
  • Palm size HP JORNADA 525 (Palm size PC terminal) with operating system, PC synchronization cable and power supply.
  • PowerSuite CD-ROM setup software [VW3A8014]
  • Connection cable [VW3A8111].
VW3A8102Pocket PC/PDA setup kit includes:
  • CD-ROM containing setup software.
  • Connection kit for the Palm size PC terminal.
Available in English, French, and Spanish operating systems.
VW3A8111Cable connection kit for the Palm size PC terminal to an ATS48 controller includes:
  • (2) connection cables, 9.8 ft (3 m) each with two RJ-45 connectors.
  • (1) RJ-45/9-way SUB-D adaptor.
  • (1) converter marked "RS-232/RS-485 PPC" with one 9-way male SUB-D connector and 1-RJ-45 connector.

Table 38: PowerSuite Software for Personal Computers

Part NumberDescription
VW3A8104PowerSuite Test and Commissioning Software on CD for use with Microsoft Windows 95, 98, and NT and Windows CE v3.0 for Pocket PCs/PDA.
VW3A8106Cable connection kit for the Personal Computer to an ATS48 controller.
  • two connection cables, 9.8 ft (3 m) each with two RJ-45 connectors.
  • one RJ-45/9-way SUB-D adaptor.
  • one converter marked "RS-232/RS-485 PPC" with one 9-way male SUB-D connector and one RJ-45 connector.

Factory repaired ATS48 controllers are available within 24 hours from a factory exchange pool, or your ATS48 controller can be factory repaired and returned. Contact your local Square D / Schneider Electric Distributor or Square D / Schneider Electric Customer Service Representative at 919-266-8666 for availability.

Index

A
AC2 55, 55
ACC 41, 41
Add 57, 57
AIL 53, 53
AO 53, 53
APC 53, 53
ArS 47, 47
AS2 53, 53
ASC 53, 53
AUL 53, 53
B
brC 43, 43
bSt 49, 49
C
CFF 64, 64
CFI 64, 64
circuit breaker 78, 78
CLF 65, 65
CLP 49, 49
COd 60, 60
contactor
isolation 78, 78
reversing 78, 78
shorting 78, 78
COS 59, 59
CSC 50, 50
D
dE2 56, 56
dEC 42, 42
DCF 63, 63
E
EbA 43, 43
Ed2 56, 56
EdC 42, 42
EEF 63, 63
EtA 59, 59
EtF 66, 66
F
factory settings 69, 69
faults
auto-reset 65, 65
manual-reset 66, 66
non-reset 63, 63
resettable 64, 64
FCS 50, 50
FOr 57, 57
FrC 50, 50
freewheel stop 41, 41
FrF 65, 65
fuses 14, 77, 78, 78
I
IL2 55, 55
ILt 41, 41
In 41, 41
In2 55, 55
InF 63, 63
INTELE braking stop 32, 41, 41
IPr 52, 52
isolation contactor 23, 78, 78
L
LAP 59, 59
LCr 59, 59
LFt 59, 59
LI3 52, 52
LI4 52, 52
LIA 52, 52
LIC 52, 52
LIE 52, 52
LIH 52, 52
LII 52, 52
LIL 52, 52
LIr 52, 52
LIS 52, 52
LIt 52, 52
LO1 53, 53
LO2 53, 53
LOC 46, 46
LPr 59, 59
LrF 66, 66
LSC 50, 50
Ltr 59, 59
LUL 45, 45
M
menus
access to 39, 39
advanced setting (drC) 48, 48
communication (COP) 57, 57
I/O (IO) 51, 51
parameter displayed (SUP) 58, 58
protection (PrO) 44, 44
second motor parameters (St2) 54, 54
settings (SEt) 40, 40
O
OCO 53, 53
OCr 53, 53
OIL 46, 46
OLC 66, 66
OLF 66, 66
OPr 53, 53
P
parameter access 39, 39
PCt 58, 58
PHE 60, 60
PHF 65, 65
PHL 46, 46
PHr 46, 46
PIF 63, 63
PtC 46, 46
R
r1 53, 53
r1F 53, 53
r1I 53, 53
r3 53, 53
reversing contactor 78, 78
rnI 53, 53
rnt 59, 59
rPr 50, 50
rtH 47, 47
S
setting factory 69, 69
shorting contactor 78, 78
shunt trip coil 23, 73, 73
SLF 66, 66
SSt 49, 49
starter status 40, 40
stop
freewheel 41, 41
INTELE braking 32, 41, 41
soft 41, 41
StY 41, 41
T
tAI 53, 53
tbr 57, 57
tbS 46, 46
tHP 45, 45
tHr 59, 59
tI2 56, 56
tIG 50, 50
tL2 56, 56
tLI 49, 49
tLP 58, 58
tLS 45, 45
tOL 46, 46
tPr 52, 52
tq0 41, 41
tq2 55, 55
tUL 45, 45
U
ULF 66, 66
ULn 50, 50
USF 65, 65

PDF preview unavailable. Download the PDF instead.

3007245061 Acrobat Distiller 5.0 (Windows)

Related Documents

Preview Schneider Electric Altistart 480 Soft Starter ATS480D88Y Technical Data
Detailed technical specifications, dimensions, electrical characteristics, environmental data, and ordering information for the Schneider Electric Altistart 480 soft starter, model ATS480D88Y.
Preview Altistart 48 Telemecanique: Manual de Operação e Instalação
Guia completo para o Altistart 48 da Telemecanique (Schneider Electric), cobrindo instalação, operação, características técnicas, esquemas de aplicação, proteções e manutenção de conversores de partida e parada progressivas.
Preview Altistart 48 Panel-Mount Soft Starts: Wiring Diagrams & Component Selection Guide
Comprehensive guide to recommended wiring diagrams and component selection for Schneider Electric's Altistart 48 Panel-Mount Soft Starts, including contactor and disconnect recommendations for various motor applications.
Preview Schneider Electric Altistart 22 Soft Starter Data Sheet
Detailed technical specifications, features, and performance data for the Schneider Electric Altistart 22 soft starter, designed for asynchronous motors.
Preview Schneider Electric Motor Logic® Plus Network Programming Guide
Comprehensive programming guide for Schneider Electric's Motor Logic® Plus Solid-State Overload Relay (SSOLR), detailing network configurations for Modbus and DeviceNet, parameter settings, and troubleshooting.
Preview Schneider Electric Altistart 22 Soft Starter Quick Start Guide for Motor Control Centers
Quick start guide for programming Schneider Electric Altistart 22 Soft Starters in Motor Control Centers (MCC). Includes installation, connection, and configuration instructions, safety warnings, and parameter settings.
Preview Schneider Electric Digest 176: Global Specialist in Energy Management Solutions
Explore Schneider Electric's Digest 176, a comprehensive guide to energy management and electrical distribution solutions. Discover products and services for buildings, industrial plants, data centers, and smart grids, focusing on efficiency, reliability, and sustainability.
Preview Schneider Electric TeSys Control: Contactors & Motor Starters Catalog
Explore the Schneider Electric TeSys Control catalog, featuring a wide range of SK, K, Deca, and Modular contactors, reversing contactors, and essential motor control components like circuit breakers and relays.