Neutrik powerCON Locking 3-Pole Power Connector
Assembly & Assembly Instruction
Models: NAC3FXXA-W-* & NAC3FXXB-W-*
A. APPLICATION & SAFETY INSTRUCTION
APPLICATION:
The powerCON system is a connector with breaking capacity certified according to IEC/EN/UL/CSA-C22.2 No. 60320-1. It is intended for use as an appliance coupler and interconnection coupler. It serves to supply power to an appliance and from an appliance to other equipment. Installation should be performed by qualified personnel only.
Connector Combination & Keyways:
The system features two non-interchangeable connector types (A and B) to prevent short circuits. Mating connectors are identified by mechanical keyways and color coding.
APPLIANCE INLET
A type (color coding blue): Power IN
NAC3FXXA-W-*
APPLIANCE OUTLET
B type (color coding gray): Power OUT
NAC3FXXB-W-*
Approval based:
IEC/EN 60320-1 | UL 60320-1 CAN/CSA-C22.2 No. 60320-1 | |
---|---|---|
Rating: | 250 V ac / 16 A | 127 V ac / 20 A |
Wire size: | 1.5 - 2.5 mm² | 16 - 12 AWG |
Cable O.D.: | 6.0 - 12.0 mm (0.24 - 0.47") | 6.0 - 12.0 mm (0.24 - 0.47") |
*-S: | 10.0 - 16.0 mm (0.39 - 0.63") | 10.0 - 16.0 mm (0.39 - 0.63") |
*-L: |
CABLE LIST
Cable: IEC/EN 60320-1 | 3 x 1.5 mm² | 3 x 2.5 mm² |
---|---|---|
H07RN-F | -S | -L |
H05RN-F | -S | -L |
H05VV-F | -S |
Cable: UL 60320-1, CAN/CSA-C22.2 No. 60320-1 | 16/3 AWG | 14/3 AWG | 12/3 AWG |
---|---|---|---|
SOOW | -S | -L | -L |
SJOOW | -S | -S | -L |
SJTOOW | -S | -S | -S |
B. ASSEMBLY INSTRUCTION
ASSEMBLY INFORMATION
- Place the bushing (1) and chuck (2) over the cable. Important: Chuck and Bushing cannot be placed over the cable after the assembly of the insert. For easier assembly, use a cable lubricant.
- Prepare cable as shown.
- Slide the cable into the contacts and clamp with the screw using a Torx size T8. Torque Value: 0.7 Nm (6.2 inch pound / 0.52 lb.ft).
IEC/EN 60320-1 Wiring
Typical Wiring | IEC/EN 60320-1 | UL 60320-1 CAN/CSA-C22.2 No. 60320-1 |
---|---|---|
N | blue | black |
L | brown | white |
PE | green/yellow | green |
- Position chuck (1) on insert (2).
- Slide insert (2) with chuck (1) together into housing (3). Important: Align the chuck by positioning the nose into the keyway.
- Slide bushing (4) over chuck (1).
Important: Push and turn simultaneously.
Hold the connector with the NEUTRIK tool (5) and tighten the bushing with the NEUTRIK tool (6) as shown. For exact mounting position, use a torque wrench with a 27 mm (1 1/8 inch) hex bit (7) and tighten it with 2.5 Nm (22 inch pound / 1.8 lb-ft).
NEUTRIK tool Information:
- (5) HTLACA
- (6) HTLACB
C. DISASSEMBLY INFORMATION
FOR DISASSEMBLY!
- Use the Neutrik tool HTLACB.
- Position the tool on the surfaces and open the clamping sleeve.
D. SAFETY INFORMATION
CAUTION
To ensure protection category, do not expose the connection to bending forces (e.g., do not attach loads to the cable, no free-dangling cable windings, etc.).
SAFETY WARNING
For safety and certification reasons, the connector must be replaced in case of any broken parts or excessive wear and tear.
E. More Information on the www.neutrik.com