1 APPLICATION & SAFETY INSTRUCTION
IP 65 RATED
APPLICATION:
- The powerCON® TRUE1® system is certified as appliance couplers with breaking capacity according to IEC 60320-1, EN IEC 60320-1, UL 60320-1, CSA C22.2 No. 60320-1.
- It serves to supply power to an appliance and from an appliance to other equipment.
- To be installed by qualified person only.
- Appliance couplers acc. to IEC 60320-1 are suitable to be used in cord sets and interconnection cord sets acc. to IEC 60799.
Connector Types:
- POWER IN APPLIANCE INLET: NAC3MPX-TOP, NAC3MPX-WOT-TOP
- POWER OUT APPLIANCE OUTLET: NAC3FPX-TOP, NAC3FPX-WOT-TOP, NAC3FPX-ST-TOP
- POWER IN / POWER OUT Combination APPLIANCE INLET / APPLIANCE OUTLET: NAC3PX-TOP
- CONNECTOR: NAC3FX-W-TOP
- PLUG CONNECTOR: NAC3MX-W-TOP
Products are in compliance with:
Compliance Standard | Ratings | Conductor cross section |
---|---|---|
IEC 60320-1 EN IEC 60320-1 |
16A 250V AC | 1.5 - 2.5 mm² |
UL 60320-1 CSA C22.2 No. 60320-1 |
20A 250V AC | 16 - 12 AWG |
CABLE LIST
Approved cables (3 x 1.5 mm²):
Cable Type | Status |
---|---|
H07RN-F | ✔️ |
H05VV-F | ❌ |
Approved cables (3 x 2.5 mm²):
Cable Type | Status |
---|---|
H07RN-F | ❌ |
H05VV-F | ❌ |
Approved cables (AWG):
Cable Type | 16/3 AWG | 14/3 AWG | 12/3 AWG |
---|---|---|---|
SOOW | -S | -L | -L |
SJOOW | -S | -L | -S |
2 ASSEMBLY INFORMATION
Follow these steps for assembly:
-
Step A: Prepare Cable and Bushing
Place the bushing (1) and chuck (2) over the cable. Important: Chuck and Bushing cannot be placed over the cable after the assembly of the insert.
Recommendation for easier assembly: Use a cable lubricant, such as Wire Pulling Lubricant - LUB-I/0.95 from 3M™.
-
Step B: Separate Housing
Separate the housing from the bushing, ensuring the cable remains in the bushing.
-
Step C: Place Chuck
Place the chuck over the cable.
-
Step D: Prepare Cable Stripping
Prepare the cable as shown in the diagram. This involves stripping the cable to specific lengths:
- Outer jacket strip: 40-50 mm
- Inner wire insulation strip: 20 mm [0.787"]
- Ground wire (PE) exposure: 8 mm [0.32"]
- Overall PE wire length from jacket edge: 23 mm [0.9"]
Torx size: T8
Torque Value: 0.7 Nm (6.2 inch-pound / 0.52 lb-ft)
Typical Wiring Standards:
Typical Wiring IEC 60320-1 / EN IEC 60320-1 UL 60320-1 / CSA C22.2 No. 60320-1 L (Line) brown black N (Neutral) blue white PE (Ground) green/yellow green -
Step E: Insert Cable into Contacts
Slide the cable into the contacts and clamp with the screw using the T8 Torx size. Ensure proper torque is applied.
-
Step F: Assemble Insert and Housing
Slide the chuck onto the insert (1) and then both into the housing (2). Important: Align the chuck by positioning the nose into the keyway.
-
Step G: Secure Cable Clamp
Slide the cable clamp (3) bushing up the cable and tighten it with the tool (4) as shown (5). Important: Ensure the black O-ring is correctly positioned to achieve IP protection (6).
Tool available: Art. No. HTAC
3 FOR DISASSEMBLY
OPEN TWIST LOCK!
- Press with a screwdriver to unlock.
- Turn the bushing 360°.
- Repeat steps 1 and 2 until the bushing is fully unscrewed.
4 SAFETY INFORMATION
[Caution Symbol] CAUTION
To ensure the protection category, do not expose the connection to bending forces. For example, do not attach loads to the cable, and avoid free-dangling cable windings.
[Warning Symbol] SAFETY WARNING
For safety and certification reasons, the connector must be replaced in case of any broken parts or excessive wear and tear.
5 Application and Safety Instructions
A Assembly
- When assembling and processing the product, ensure the use of appropriate personal protective equipment.
- Neutrik components must only be assembled with designated and specified components.
- Replacement parts are suitable only when used in combination with the designated components. The product's characteristics are guaranteed only in the intended combination.
B Application
- The product is exclusively intended for installation in electronic equipment or similar devices.
- The product is not intended for use in medical applications.
- The product is not intended for use in potentially explosive or flammable environments.
- Appliance couplers are not intended for use as climbing aids. Caution: Electrical hazards!
- Ensure that the connectors are either plugged in or protected against moisture with a suitable protective cap in potentially humid environments.
C Operation
- Before plugging in, check the contact area for dry surfaces.
- Product surfaces may cause burns at elevated ambient temperatures. Ensure the use of appropriate protective equipment.
- Neutrik products should only be combined with products from Neutrik Group brands.
D Cleaning
- Clean only with dry and lint-free materials or compressed air.
- The product must not be cleaned while under load. The product may only be cleaned while it is not connected to any voltage and without the use of cleaning agents.
E Damages
- Handle products with care.
- In case of visible damages, check the suitability of the product for use.