Operating Voltage (Ue) / Current (In A) per Charging Station |
Single-phase connection, Phase + N 230V~ from 0 to 125A (specified at 20°C); Three-phase connection, 3 Phases + N 400V~ from 0 to 125A (specified at 20°C) |
Operating Voltage (Ue) / Current (In A) per Charging Point |
Single-phase connection, Phase + N 230V~ from 0 to 63A (specified at 20°C); Three-phase connection, 3 Phases + N 400V~ from 0 to 63A (specified at 20°C) |
Impulse Voltage (Uimp) |
4kV |
Insulation Voltage (Ui) |
230V single-phase, 500V three-phase |
Frequency (fn) |
50Hz/60Hz |
Nominal Voltage |
1 Phase + N: 230V - 3 Phases + N: 400V |
Voltage Tolerance (V) Independent of Vehicle Requirements |
195V - 265V |
Integrated Protection System at Charging Station |
Main switch 125A |
Integrated Protection System per Charging Point |
MCB 80A curve C, RCD 63A 30mA Type B |
Conditional Short-Circuit Current |
6000A IEC/EN 60898-1; 10kA IEC/EN 60947-2 |
Admissible Thermal Load during Short Circuit |
16 000 A²s |
Connection to the Power Grid |
Phase/Neutral, rigid cable, 2.5 to 50 mm², screw terminals; HO7 V R/U Earth, rigid cable, 2.5 to 50mm², screw terminals H07 V R/U |
Charging Type |
Mode 3 charging station with a locking system for Mode 3 |
Vehicle Connection Socket Mode 3 |
Type 2 3P+N (single-phase compatible) with control devices according to IEC 62191-1 and IEC 62196-2. Use only a manufacturer-approved plug with silver-plated contacts. The use of extensions and adapters is prohibited. |
Phase Rotation on Channel 2 (Right Side) |
In case of a single-phase connection (Ph+N) to the power source, Channel 2 cannot start charging processes until the phase rotation between the contactor and the socket is manually reversed. |
AC Meter |
MID certified, Class B according to EN 50470-1, -3 |
Back-Office Protocol |
OCPP 1.6 Json |
Positioning |
GPS |
Ethernet Connectivity |
RJ45 connection for 65345106 / 65020020 |