1. Introduction
Thank you for choosing an Ecotap® charging station. This manual pertains to the Duo Wide AC44 charge point. It contains vital information for the proper and safe installation and usage of the charging station. This charging station is designed for vehicles equipped with a mode 3 charging system compliant with IEC 61815-1 (version 2.0) and a plug system compliant with VDE-AR-E 2623-2-2. In conjunction with the vehicle and system, the charging station optimizes charging speed and safety. The entire charging station adheres to the 2014/35/EU directive concerning the harmonization of regulations for electrical equipment within specific voltage limits. This manual guides you through the safe installation and use of the charging station, ensuring its maximum functionality and lifespan. Ecotap® B.V. cannot be held responsible for any injury or damage to goods if the charging station is altered, damaged, refitted, or expanded with other components, or if it is not used in accordance with the provided instructions and conditions.
Copyright: No part of this publication may be copied, reproduced, or saved in a retrieval system without Ecotap® B.V's prior written consent. This is an English translation of the original Dutch manual.
2. General
2.1 Warranty
The Ecotap® B.V. General terms and conditions for delivery apply. Ecotap® B.V. cannot be held accountable for any injury or damage to goods should the charging station be altered, damaged, refitted or expanded upon with other components, or not used in accordance with the instructions and conditions set out herein.
2.2 Symbols used in this manual and on the charging system
Symbol | Meaning |
---|---|
⚠️ | Pay attention! Important instruction |
⚡ | Electrical hazard. For maintenance: first disconnect the installation from its power supply and test it to make sure there is no voltage left, before engaging in any maintenance activities. |
? | Wear special gloves. |
? | Disconnect the electrical installation from its power supply. |
3. Device Description
3.1 Use
This charging station is designed for public areas and can be installed in various environments, including paved areas, open soil/sand, or asphalt surfaces. It is not suitable for grounds that can flood, loading quays, or slopes exceeding 4%.
3.2 Accessories
The following accessories are not provided: tools, foundation.
3.3 Safety provisions
- 2 half euro profile cylinders
- Extra caps behind front cap
- 12 Volt control voltage
- Components comply with IP2 at least
- Strain reliefs
- 4 mm steel casing
- IP54 (lowest waterproof class for Mennekes outlets).
4. Safety
Read the following safety regulations carefully before you install and use the charging station.
4.1 Safety regulations
Before installing the charging station, ensure the location is safe for all bystanders. Never allow children or unauthorized personnel onto the worksite. Avoid distractions during work. Maintain a healthy posture at all times. Do not leave tools or charging station components unattended. Ensure all tools are clean and dry. Protect the charging station, tools, and components from moisture, especially during rain. After maintenance, ensure all doors and panels are closed and locked before resuming operation. Be mindful of tripping hazards when digging for the foundation. Wear suitable gloves for all installation and connection processes.
⚠️ Make sure there is no danger of anyone tripping over objects or paving while you are digging the hole for the foundation.
? Make sure to wear good, suitable gloves for any special actions throughout the entire installation and connection process.
? Always check any measuring instruments before use to ensure they are working properly.
5. Mandatory Checks Before Initial Use
⚠️ The following checks are mandatory before the charging station goes live. Never use the charging station if any of these checks indicate insufficient power supply or stability. Check insulation resistance of conductors according to NEN1010 provision 61.3.3.
? Always perform the checks below before voltage is applied to the DUO charging station.
- All activities must be performed in accordance with NEN 3140.
- Check wire connections to terminals for correct order.
- Verify conductors on terminals are securely screwed (4 to 5 NM).
- Ensure the grounding connector is connected to the coded terminal and the grounding electrode/device. The grounding system must comply with NEN1010/EU/35.
- Confirm the charging station is stable.
- Check seals on charging station caps for proper installation (IP54).
- Ensure all necessary actions are completed safely.
- Verify no obstacles surround the worksite.
- Before applying voltage, contact Ecotap® B.V. at 0031 (0) 411-210210 to activate the station's software, providing the station's unique code.
6. User / Installation Manual
6.1 Mounting the casing on the foundation
- The foundation must be installed in a hole measuring 50x50 cm and 80 cm deep.
- Ensure the bottom of the hole is stable and flat. Place the foundation in the hole and level it using a spirit level. Minor deviations can be corrected when closing the hole.
- Position the charging station on the foundation without its 2 bent steel cap sections and secure using the supplied bolts and nuts (nuts on top).
- Keep the transparent lids on the front of the charging station in place for now. Ensure the station is oriented correctly (connecting side at the front).
- Close the hole with approximately 20 cm of soil/sand.
- Install the cap at the back using the supplied nuts.
- Maintain at least 1 meter of free space around the charging station for proper operation.
6.2 Opening and closing the charging station
⚠️ Always de-energize the charging column and read the operating instructions before handling maintenance or malfunctions.
The lock for the Duo Wide charging column is located at the back of the charging point, at the bottom of the door. A cover protects the lock from sand and dirt.
- Remove the cover plate using Allen 2.5.
- Open the charging point with the supplied key.
- Insert the key into the right lock.
- Turn the key fully to the right.
- Turn the cylinder (including 2 locks) completely counter-clockwise using a flat screwdriver in the slot.
- After unlocking, disconnect the door: grab the door, slide it up (approx. 1 cm), and then move the bottom away and down.
Diagram T 1.4 shows the rear view of the charging station with the lock mechanism.
6.3 Installing the protective casing
The casing pipe is provided in the box. After mounting the charging station on the foundation, remove the transparent plastic protective plate from the bottom. Fit the casing as shown in drawing 1.3 and secure with the provided strain relief.
6.4 Insert cable and secure with supplied strain relief
Feed the power cable through the casing pipe, avoiding excess length. Attach the cable clamp to the cable and secure it (max. 3 Nm).
6.5 Connecting the power cable
The meter board setup must be installed according to the network manager's specifications. Network operator materials (connection box, cable, meter) must be connected by a contractor appointed by the network operator, following installation instructions, guidelines, and BEI safety instructions.
6.6 Connecting the grounding electrode/grounding conductor
Connect the earth wire of the connection cable to the main earth bar (HAR). Also connect the earth wire from the earth connector to the main earth bar (HAR) terminal as shown in Drawing 1.3. Ensure proper earthing in compliance with NEN1010 /EU/35 regulations.
6.7 LED indication
Status | LED Indication |
---|---|
Charger not powered | No LED indication |
Charger powered and not used | 1 green blink per 10 seconds ? |
Charger powered and used not in charge | Continuous green ? |
Charger powered and used in charge | Continuous blue ? |
Refer to the table for error states.
6.8 Fuses per connection value
The following table explains the required fuses per socket per phase, based on the network operator's connections. Software selectivity can be applied via the back office.
Net connection value | Fuses to be placed per socket |
---|---|
3x25 A | 20 A Gg fuses per socket per phase |
3x35 A | 25 A Gg fuses per socket per phase |
3x50 A | 32 A Gg fuses per socket per phase |
3x63 A | 32 A Gg fuses per socket per phase |
3x80 A | 32 A Gg fuses per socket per phase |
SAFETY NOTICE: This charger uses NOARK fuseholders. For charging at a maximum of 32A, use only EATON, MERSEN, or SIBA gG 400Vac, 100kA, 10x38mm, 32A fuses.
7. Maintenance
⚠️ Always disconnect the charging station from its power supply before performing maintenance or fixing malfunctions. Repairs or component replacements must use supplier-approved products. Contact Ecotap® for any doubts. Maintenance must be performed by an authorized person/specialist and comply with NEN3140 and NEN50110 low voltage European standards. Check the charging station for leaks. Test the heating element and thermostat. Ensure the thermostat is set to five degrees or frost protection mode. Check power supply cable connections and ensure a fixed connection of 4-5 Nm. Touch up minor damage with corrosion-resistant paint (Ecotap® green ral.6018 & white ral.9016). Lubricate cylinder locks with graphite powder or suitable oil if needed.
8. Transportation and Storage
Transport the charging station upright to prevent coating damage, which could lead to corrosion. Caps can be transported in various positions if protected. Store the charging station in a dry, damp-free area.
9. In Case of Malfunctions
If the DUO Wide charging station is not functioning correctly, contact the Ecotap® 24/7 helpdesk immediately at +31 (0) 411-745020 or a licensed mechanic with testing equipment.
WARNING: All work and modifications must comply with NEN1010 at minimum.
10. Operation and Control of Charging Column
The charging column can be operated using a charging card.
This charging station is operated via a charging pass. Registration is required via the Open Charge Point Protocol (OCPP). Contact Ecotap® B.V. at 0031 (0) 411-210210 during office hours for registration. After registration, the column can be used with any Electric Transport Charging Card (EV Charging Card), other suitable cards, mobile devices, or key holders. When idle, the charging column displays a regular green signal.
Operation: To start or stop charging, hold the charging card in front of the scan point. You will hear one sound signal, and the lamp will flash green. The plug locks into the Mennekes charging socket. The column communicates with the vehicle and the BackOffice system. Once safety and payment requirements are met, the maximum charging current is transmitted, and charging begins automatically, indicated by a blue light. To stop charging, hold the pass in front of the scan point again. You will hear two beeps, the lamp flashes green, and turns off once the plug is unlocked. You can then safely remove the plug.
11. Technical Specifications
General characteristics
- Reference number: 65345106 / 65004410 / 65020015 / 65020020
- Dimension H x W x D (mm): 1400 x 360 x 240
- Casing material: Steel 2.2 mm
- Standard colour: Body: Ral 6018 / Cover: Ral 9016
- Steel treatment: Anti-corrosion (KTL) and powder coating
- Weight (kg): 76 kg
- Number of charging points: 2
- Socket: Type 2
- Cable: Type 2
Electrical characteristics
- Power output per socket: 0 to 44kW
- Operating voltage (Ue) / Rates current (In A) for the charger: Single-phase: 230V~ (0-125A); Three-phase: 400V~ (0-125A) (at 20°C)
- Operating voltage (Ue) / Rates current (In A) per charge point: Single-phase: 230V~ (0-63A); Three-phase: 400V~ (0-63A) (at 20°C)
- Impulse voltage (Uimp): 4kV
- Insulation voltage (Ui): 230V single-phase, 500V three-phase
- Frequency (fn): 50Hz/60Hz
- Rated voltage: 1 phase + N: 230V; 3 phases + N: 400V
- Voltage tolerance (V): 195V - 265V
- Integrated protection system on charging station: Main switch 125A
- Integrated protection system per charge point: MCB 80A curve C, RCD 63A 30mA Type B
- Conditional short-circuit: 6000A IEC/EN 60898-1
- Allowable thermal stress in Short Circuit: 10kA IEC/EN 60947-2, 16,000 A²s
- Connection to the mains: Phase/Neutral, rigid cable, 2.5 to 50 mm², screw terminals H07 V R/U; Earth, rigid cable, 2.5 to 50mm², screw terminals H07 V R/U
- Type of load: Mode 3 charging terminal with a locking system for Mode 3
- Vehicle connection Mode 3 attache cable connector: Type 2 3P+N (single-phase compatible) with pilots compliant with IEC 62191-1 and IEC 62196-2. Use of extension and adapter prohibited. 10m straight 3x63A
- Phase rotation on channel 2 (Rightside): In case of monophase cabling (Ph+N), Channel 2 cannot start charging sessions until the phase rotation between contactor and socket is manually undone.
- AC meters: MID certified, Class B according to EN 50470-1, -3
- Back office protocol: OCPP 1.6 Json
- Positioning: GPS
- Connectivity Ethernet: RJ45 connector for 65345106 / 65020020
Environment
- Operating temperature: -25°C / +50°C
- Storage temperature: -25°C / +80°C
- Relative humidity: 0 to 90% without condensation
- Corrosivity class: C4 (IEC 9223, IEC 12944), 3C3/4C3 (IEC 60721-3)
- Protection rating: IP 54 (IEC 60529), IK 10 (EN 62262)
- Noise level: < 40 dBA at 1m
- Product: IEC 61851-1, IEC TS 61439-7 (AEVCS)
- Installation: Interior/exterior, limited access zone, for ordinary persons (DBO). Assembly in cabinet (wall mounted). Pollution Degree 3, TNS, TT, compatible earthing system. For IT earthing systems, an isolation transformer can be added locally.
Electromagnetic compatibility
- European standards: Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU
- Radio technology type: GSM 2G/3G/4G, GPRS, RFID
- Suitable charging cards: Mifare, Ntag and iCODE SLI cards
Ecotap® B.V. reserves the right to change technical specifications without prior notice due to ongoing development. Specifications may vary by country.
12. Contact Details Supplier
Ecotap® B.V.
Kruisbroeksestraat 23
5281RV Boxtel - The Netherlands
Tel.: 0031 (0) 411-210210
E-mail: info@ecotap.nl
13. EC Declaration of Conformity
EC Declaration of Conformity for machines (Directive 2014/35/EU, Annex II page 96/369)
Ecotap® B.V., Industrieweg 4 5281RW Boxtel, The Netherlands, hereby declares that the charging stations stated below comply with the Machinery Directive and other relevant regulations and standards.
Name: Ecotap® Charging station Duo Wide AC44
Designed in: 2021
EC directives applied:
- Machinery Directive 2014/35/EU
- EMC Directive 2014/30/EU
Standards used as reference:
EN/IEC 60950-22:2017
EN/IEC61851-1:2017
EN/IEC61851-22:2002
EN/IEC 62196-2:2017
EN/IEC 61000-6-2:2016
EN/IEC 61000-6-3/2007 + A1:2011
EN/IEC 60335-1/2012 + A13:2017
EN/IEC 60364-4-41:2017
NEN/EN/IEC 60529
IEC 62262
NEN/EN/IEC 61439-1
IEC/TS 61439-7
Boxtel, March 2021
Ir. P.F.A. van der Putten (Technical Director)
File Info : application/pdf, 14 Pages, 1.47MB
DocumentDocumentReferences
Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)Related Documents
![]() |
Ecotap Homebox Installatie- en Gebruikershandleiding Uitgebreide handleiding voor het Ecotap Homebox laadstation voor elektrische voertuigen, inclusief installatie, veilige bediening, onderhoud en technische specificaties. |
![]() |
Ecotap Wallcharger Duo Manual: Installation, Operation, and Safety Guide This manual provides comprehensive instructions for the installation, operation, safety precautions, and technical specifications of the Ecotap Wallcharger Duo, a wall-mounted electric vehicle charging station designed for efficient and safe EV charging. |
![]() |
Ecotap Duo Wide AC44 EV Charger Specifications Detailed specifications for the Ecotap Duo Wide AC44 electric vehicle charging station, covering general characteristics, electrical features, environmental conditions, and electromagnetic compatibility. |
![]() |
Ecotap Duo Wide Plus EV Charging Station - Technical Specifications Detailed technical specifications for the Ecotap Duo Wide Plus electric vehicle charging station, covering general, electrical, environmental, and EMC properties. Includes model numbers and compliance standards. |
![]() |
Ecotap DC120 DC Charger Manual This manual provides comprehensive information on the installation, operation, safety, maintenance, and technical specifications of the Ecotap DC120 DC charger. |
![]() |
Ecotap Duo Wide AC44 Electric Vehicle Charging Station Specifications Detailed technical specifications for the Ecotap Duo Wide AC44 electric vehicle charging station, including general and electrical properties, environmental conditions, and electromagnetic compatibility. |
![]() |
Ecotap Duo Wide AC44 Electric Vehicle Charging Station Specifications Detailed specifications for the Ecotap Duo Wide AC44 electric vehicle charging station, covering general, electrical, environmental, and electromagnetic compatibility characteristics. Includes information on power output, voltage, current, protection systems, and connectivity. |
![]() |
Ecotap Duo Wide AC44 Electric Vehicle Charging Station Specifications Detailed specifications for the Ecotap Duo Wide AC44, a dual-port AC electric vehicle charging station. Includes technical data on dimensions, materials, electrical characteristics, environmental specifications, and electromagnetic compatibility. |