General Installation Requirements
Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
Dimensions
The unit has the following dimensions:
- Width: 88 mm (3.46 inches)
- Height: 60 mm (2.36 inches)
- Depth/Mounting Depth: 38 mm (1.49 inches)
Mounting hole patterns are indicated with these dimensions.
Environmental Specifications
- IEC Pollution Degree: II
- Operating Temperature: 0°C to 50°C (32°F to 122°F)
- Maximum Humidity: 90%
Electrical Specifications and Connections
Wire Specifications:
- Wire Gauge: 0.3-2.5 mm² (22-12 AWG)
- Terminal Torque Setting: 0.4 Nm (3.5 Lb-in)
Input Type: SELV/Class 2
Communication Interface: DyNet RS-485
Power Requirements:
- Voltage: 12 V or 24 V
- Current Draw (typical): 120 mA (at 12V), 60 mA (at 24V)
- Maximum Current: 2 A
Mounting Torque: 1.0 Nm (8.8 Lb-in)
Terminal Block Labels:
- +V: Positive power supply
- D-: RS-485 Data negative
- D+: RS-485 Data positive
- GND: Ground
- SHLD: Shield
Connection Points: The device features connection points labeled 2/4/8, potentially indicating different configuration or module types.
Safety Precautions
- Do not connect inputs to mains voltage.
- Always disconnect power before connecting or separating modules.
Regulatory Compliance
Federal Communications Commission (FCC) Compliance
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
Canadian Compliance
This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB003 du Canada: CAN ICES-3(B)/NMB-3(B).
Building Automation Standards
Installation of a home and building automation and control system shall comply with HD 60364-4-41. The temperature limits and current-carrying capacities for the communication wires specified in HD 384.5.523 shall not be exceeded.
Legal and Copyright Information
© 2021 Signify Holding. All rights reserved.
Specifications are subject to change without notice.
No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed.
Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V.
All other trademarks are owned by Signify Holding or their respective owners.
For more information, visit: www.lighting.philips.com/dynalite