General Safety and Installation Precautions
Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations. The document also provides instructions in French, German, Spanish, Italian, Dutch, Japanese, Chinese, and Arabic.
To avoid proximity sensor false triggering, please ensure all unearthed metal structures and mains cables are more than 30 cm (11.81 in) away from the user interface.
Important Warnings:
- Do not connect inputs to mains.
- Disconnect power before connecting or separating modules.
- Refer to the Service Guide for full cleaning recommendations.
Operating temperature range: 0° C (32° F) to 50° C (122° F). Humidity: ≤90%.
IEC Pollution Degree II.
IEC Overvoltage Category III.
Installation Steps
- Mounting the Device:[Diagram 1: Shows the device being mounted into a wall or backbox, with multiple mounting points indicated.]
- Wiring Connections:[Diagram 2: Illustrates connecting wires to the device terminals. Wires enter from the side and connect to labeled terminals.]
Connection terminals include: +V, D-, D+, GND, SHLD.
- Physical Dimensions:[Diagram 3: Provides physical dimensions of the device. Key dimensions are 63 mm (2.48 in) width, 52 mm (2.05 in) height, 88 mm (3.46 in) depth, with a 38 mm (1.49 in) and 60 mm (2.36 in) detail, and a 10.5 mm (0.41 in) DACM measurement.]
- Wire Specifications and Torque:[Diagram 4: Details wire gauge and torque. Wire gauge: 0.3-2.5 mm² (22-12 AWG). Torque: 0.4 Nm (3.5 Lb-in) for some connections, and 1.0 Nm (8.8 Lb-in) for others.]
The system uses SELV/Class 2 (UL) rated wiring for communication.
Communication protocol: RS-485 DyNet.
- Cable Management:[Diagram 5: Depicts routing and securing cables for neat management.]
- Final Assembly:[Diagram 6: Shows the front faceplate being attached to the installed device. Model variant 2/4/8 is indicated.]
- Certification Labels:[Diagram 7: Displays various certification labels including IEC Pollution Degree II, CE, UKCA, FC, and others.]
- Power and Data Specifications:
RS-485 DyNet communication.
- 12V input: ≤ 120 mA
- 24V input: ≤ 60 mA
- General current rating: ≤ 2A
Compliance Information
Federal Communications Commission (FCC) Compliance Notice: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user's authority to operate this device.
This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la Classe B est conforme a la norme NMB-003 du Canada: CAN ICES-3(B)/NMB-3(B).
Installation of a home and building automation and control system shall comply with IEC 60364 (all parts). The temperature limits and current-carrying capacities for the communication wires specified in IEC 60364-5-52 shall not be exceeded.