Philips Dynalite DDTC001 Network Timeclock
Installation Instructions
Safety and Installation Requirements
Important: Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.
The device is rated for IEC Pollution Degree II and IEC Overvoltage Category III.
Device Overview and Specifications
The Philips Dynalite DDTC001 is a Network Timeclock designed for lighting control systems.
Physical Dimensions:
- Width: 35 mm (1.38 in)
- Depth: 58 mm (2.28 in)
- Height: 35 mm (1.38 in)
Operating Environment:
- Temperature: 0°C (32°F) to 40°C (104°F) ?️
- Humidity: ≤95% ?
Wiring and Connections
The device features a terminal block for connections:
- Terminals: Shld (Shield), Gnd (Ground), D+ (Data Plus), D- (Data Minus), +12V (Power).
- Power Input: 12V DC, 20 mA.
- Maximum Current: ≤ 2A.
- Wire Gauge Compatibility: 0.3-2.5mm² (22-12 AWG).
- Recommended Torque: 0.4 Nm (3.5 Lb-in).
The DDTC001 utilizes an RS-485 DyNet interface for communication.
It also includes a Service Switch and an RJ12 port for connectivity.
Connection Diagram Description:
A diagram illustrates the connection of multiple wires to the labeled terminals (Shld, Gnd, D+, D-, +12V). Another diagram shows the device connected to a network, likely via the RS-485 DyNet interface. A third visual depicts a hand carefully inserting wires into the terminal block.
Regulatory Compliance
The product bears CE and UKCA markings, indicating compliance with relevant European and UK standards.