Philips Dynalite DDBC300-D DALI Driver Controller
Installation Instructions
Safety and Installation Requirements
Warning: Installation must be performed by a qualified electrician in an approved enclosure, adhering to all national and local electrical and construction codes and regulations.
IEC Pollution Degree II
IEC Overvoltage Category III
Product Specifications and Dimensions
Product: Philips Dynalite DDBC300-D DALI Driver Controller
Physical Dimensions:
- Width: 94 mm (3.70 in)
- Length: 211 mm (8.31 in)
- Depth: 75 mm (2.95 in)
- Mounting Hole Spacing: 45 mm (1.77 in)
Environmental Limits:
- Operating Temperature: 0°C to 40°C (32°F to 104°F) ?️
- Maximum Humidity: ≤90% ?
DALI Control Channel Ratings:
- Addressing: Addressable
- Channels per Device: ≤ 64
- Total Addressable Devices: < 192
- Guaranteed Current: 128 mA
- Maximum Current: 250 mA
- Insulation: Basic
Electrical Connections
Power Input
100-240 V~ 0.5 A
DALI Connections
Terminals for DALI 1, DALI 2, DALI 3 (DA-, DA+ pairs). Unused DALI loops should be marked "NOT CONNECTED LOOP".
Wire Gauge: ≤5.5 mm² / 10+ AWG for main DALI, ≤2.5 mm² / 12+ AWG for other DALI/DyNet.
Torque: 0.6 Nm (5.5 Lb-in) for main DALI, 0.5 Nm (4.4 Lb-in) for other DALI/DyNet.
DyNet/RS-485 Communication
Connections: SHLD, GND, D+, D-, +12V, AUX/UL924.
+12V and AUX/UL924 are SELV/Class 2 (UL) rated.
Maximum cable length for AUX/UL924 and RS-485 DyNet: < 20 m.
Wire Gauge: ≤2.5 mm² / 12+ AWG.
Torque: 0.5 Nm (4.4 Lb-in).
Other
RJ12 connector.
Important Notes
Note: This is a Class A product. In a domestic environment, it may cause radio interference; users may need to take corrective measures.
Installation must comply with IEC 60364 (all parts). Ensure communication wire temperature limits and current-carrying capacities per IEC 60364-5-52 are not exceeded.