Easergy T300 HU250 Control and Communication Unit

Installation Guide

IMPORTANT NOTE

Only qualified personnel should carry out the installation, operation, servicing, and maintenance of electrical equipment. Schneider Electric accepts no liability regarding any consequences of the use of this documentation. A qualified person is a technician who is competent regarding the construction, installation, and operation of electrical equipment and is trained in safety procedures, and is therefore capable of detecting and preventing the risks involved.

Product Description

The HU250 module of the Easergy T300 range is the communication gateway dedicated to remote control applications for T300 units.

Components and Ports

Port Characteristics Description
1, 2 Communication ports RS232/RS485: RJ45 connector including the following connections:
RS232: TXD, RXD, CTS, DTR, DSR, RTS, DCD, GND
RS485 (2-wire): D1 (B), D0 (A), GND
RS422 (4-wire): RXD0 (A'), RXD1 (B'), TXD1 (B), TXD0 (A), GND (C/C')
Customizable modem boxes including:
- RS232/485: for remote link to control center (up to 115200 baud, 2kVAC isolation).
- 2G/3G: for remote link to control center.
- 2G/3G + GPS: for remote link with GPS time synchronization.
- 3G/4G: for remote link to control center.
Note: Ports 1 and 2 can include only one 2G/3G or 3G/4G modem.
3 Local communication Ethernet port (EETXHT1) 10/100 Base-T RJ45 connector Ethernet port for link to an external device in the MV substation or for connection to a PC. Isolation: 2kVAC
4 Remote communication Ethernet port (EETXHT2) 10/100 Base-T RJ45 connector Ethernet port for remote link to the control center, via a modem or router. Isolation: 4kVAC
5 Double Ethernet ports LAN 1 and 2 (Flair 23DM) 10/100 Base-T RJ45 connectors Double ports for internal communication between T300 modules or for connection to a PC. Isolation: 2kVAC. 10 Ethernet jumpers (Ref: EMS59528) allow internal Ethernet connection between HU250, SC150, and LV150 modules.
6 RS485 port RJ45 connector Port for internal Modbus communication with Easergy PS50 power supply module or other Modbus devices (up to 38400 baud, 2kVAC isolation).
7 WI-FI port Dual-band concurrent WI-FI (2.4GHz/5GHz) Secure WI-FI port for local connection of a PC, tablet, or smartphone to the T300's embedded Web server or Easergy Builder tool.
8 Expert USB port Mini USB connector Mini USB port for equipment maintenance (reserved for qualified personnel). Requires specific driver installation.
9 Host USB port A type USB connector Multi-purpose USB peripheral port.
10 Digital inputs Plug-in screw connectors 8 digital inputs: 4 unallocated, 4 dedicated (voltage presence, door open switch, external Local/Remote switch).
11 Digital outputs Plug-in screw connector 2 dry-contact digital outputs for free use (Breaking capacity: 2000VA, Max. voltage: 60VDC, Max. current: 2A, Isolation: 2kVAC).
12 Analog inputs Plug-in leaf-spring connector 2 analog inputs for one 3-wire PT100 temperature sensor (Measurement: -55°C to 250°C, Resolution: 1°C).
13 Indicator outputs Plug-in screw connector 2 polarized indicator outputs for external indication (e.g., fault detection). Voltage: 5V, Max. current: 100 mA. Note: Comply with connection direction (+ and -).
14 Power supply Plug-in screw connectors 2 power supply connectors (12-48V DC) connected internally, facilitating serial connections and power supply looping between T300 modules.

NOTICE: HAZARD OF DAMAGE TO THE DEVICE

Failure to comply with these instructions can result in material damage.

NOTICE: HAZARD OF MATERIAL DAMAGE

Failure to comply with these instructions can cause material damage.

Installation

Installing the enclosure

The HU250 module is fastened to a DIN rail. No tool is needed for mounting. Clip it to fasten as shown in the diagrams.

Diagrams show the process of clipping the HU250 module onto a DIN rail and onto a PS50 enclosure.

External dimensions of the HU250 enclosure are approximately 90mm (width) x 140mm (height) x 104.5mm (depth).

Installation of a modem box

Modem boxes can be installed or interchanged easily and quickly in the HU250. To install a modem box:

To withdraw a modem box, reverse the procedure. Note: Changing a modem box requires configuration changes via the Easergy Builder tool. Refer to the Easergy Builder user guide.

Operation

Indicator lamps on the front panel show operating states. Buttons allow user actions. The table below summarizes indications and actions:

Part Description of indications and actions
1 HU 250 states
1.1: HU 250 operating
1.2: Equipment fault
1.3: Wi-Fi access operating (activated by Local mode)
1.4: Modules communication fault (SC150, PS50,...)
2 Local/Remote
2.1: Local position: All remote controls locked.
2.2: Remote position: All local controls on switches via SC150 module locked.
2.3: Push button to change Local/Remote state. Note: Switching to local mode activates Wi-Fi access.
3 & 8 Automatic control states and checks
3.1: Automatic control enabled
3.2: Automatic control disabled
3.3: Automatic control locked
3.4: Automatic control change-of-state button (ON/OFF).
8.1: Change-of-state enabling button. Both buttons must be pressed simultaneously. Note: Change of state is possible only in Local mode.
4 Power supply
4.1: Mains power supply operating
4.2: 48V/24V motor pack power supply operating
4.3: Transmission equipment power supply operating
4.4: Over consumption on Transmission equipment power supply
4.5: Battery fault.
Note: These states are retransmitted by the PS50 module. Indicators can be customized via Easergy Builder.
5 Customizable indicator lamps
5.1, 5.2, 5.3: 3 unassigned indicator lamps configurable for customized states. Refer to the Quick start manual.
6 2G/3G or 3G/4G modem box indicator lamps
6.1: Mobile network activity indicator.
6.2: Modem fault indicator (SIM card fault, connection problem).
6.3: GPS signal reception status indicator.
7 RS232-RS485 modem box indicator
7.1: TX: RS232/RS485 data transmission indicator.
7.2: RX: RS232/RS485 data reception indicator.
9 Reset
9.1: Reset button reinitializes fault indications and automatic control locking.
10 Indicator test
10.1: Indicator test button forces lighting of all indicator lamps. Helps detect anomalies.

Note: Refer to the table for the meaning of flashing states and indicator lamp colors. Some indicators are customizable.

2G/3G or 3G/4G Modem

This modem allows insertion of a SIM card into one of two slots. GPS and GSM antenna connectors and SIM cards are accessible on the front. Mount the GPS antenna to the substation wall (preferably outside) and connect its cable to the 'GPS' connector. Insert SIM card(s) with the HU250 switched off. The GSM antenna is internal and requires no outside mounting.

DANGER: HAZARD OF BURNING, ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC

Failure to comply with these indications will result in death or serious injury.

Power Supply

The HU250 has two internal power supply connectors that facilitate serial connections and power supply looping between modules. No strapping is necessary. This architecture ensures continuity of power supply. Connect the HU250 as shown in the diagram for power supply loopback benefits.

Diagram shows power supply connections between HU250, SC150, and PS50 modules.

Parameters Setup

Installation of the HU250 module does not require parameter setup. This is performed during commissioning/configuration stages. Refer to the User Manual and Expert Guide for details.

Identification

The serial number format is: Year - Week - Work order (e.g., 15340265).

Grounding

The DIN rail must be grounded and metallic. If installed on a PS50 module, grounding is performed on the PS50's power supply input, not the DIN rail. Refer to the PS50 Installation Guide.

Indicator Lamp States

The table below details the meaning of indicator states (flashing, steady) for various colors (Red, Green, Orange) and their corresponding states (Boot, Fault, OK, etc.).

Indicator state Flashing Red Steady Green Steady Red Steady Green Steady Orange Unit
1.1Boot-FaultOKCom fault-
1.2--Major Fault-Minor fault-
1.3---OK--
1.4--FaultOKIn progress-
2.1---Local-Local
2.2---Remote-Remote
2.3------
3.1---ON-ON
3.2---OFF-OFF
3.3---Locked-Locked
3.4------
4.1--AC OFFAC ON--
4.2--FaultOK--
4.3--FaultOK--
4.4------
4.5--FaultOK--
5.1---ON-ON
5.2---ON-ON
5.3---ON-ON
6.1-Active----
6.2--Fault---
6.3-Active and sync-No sync--
7.1 TX-Transmitting----
7.2 RX-Receiving----

(1) Indicators customizable by configuration. Only default values shown. Note: Indications in bold letters correspond to normal operation.

FCC Information

Easergy HU250 FCC ID: 2AHHK-EASERGYHU250. Easergy GSM/3G modem box FCC ID: QIPPHS8-P. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. This equipment complies with FCC Class B digital device limits for reasonable protection against harmful interference. It generates, uses, and can radiate radio frequency energy. If interference occurs, try reorienting the antenna, increasing separation, connecting to a different outlet, or consulting a technician. This device complies with FCC RF radiation exposure limits and must be installed at least 20cm from all persons, not co-located or operating with any other antenna or transmitter.

PDF preview unavailable. Download the PDF instead.

HU250 installation guide Adobe PDF Library 15.0 Adobe InDesign CC 2015 (Windows)

Related Documents

Preview Schneider Electric Easergy T300 HU250 Communication Gateway Installation Guide
Installation guide for the Schneider Electric Easergy T300 HU250 communication gateway. Details product features, ports, modem options (3G, 4G, Zigbee), digital/analog I/O, installation procedures, operation indicators, power supply, and compliance information for industrial network management.
Preview Schneider Electric Easergy SC150 Installation Guide
Installation guide for the Schneider Electric Easergy SC150 Switch Control Unit, part of the Easergy T300 range. Covers connections, operation, indicators, and safety precautions for MV electrical network management.
Preview Easergy P5 Communication User Manual: Protocols and Configuration
Comprehensive user manual for Schneider Electric's Easergy P5 protection relay, detailing communication protocols like IEC 61850, DNP3, IEC 60870-5-101, IEC 60870-5-103, Modbus, and EtherNet/IP, along with configuration guides for power utility automation systems.
Preview Easergy VPIS V3 Voltage Presence Indicating System for Medium Voltage Cubicles
Detailed information on the Schneider Electric Easergy VPIS V3, a self-powered voltage presence indicating system for medium voltage cubicles. Includes product overview, technical specifications, characteristics, and reference selection.
Preview Easergy P5 User Manual: Communication Protocols and Configuration
Comprehensive user manual for the Schneider Electric Easergy P5 protection relay, detailing supported communication protocols like IEC 61850, DNP3, Modbus, and EtherNet/IP, along with configuration and network architecture information.
Preview Schneider Electric Easergy P3M32 Protective Relay (REL52121) - Data Sheet
Detailed data sheet for the Schneider Electric Easergy P3M32 protective relay, covering its main characteristics, protection functions, measurement capabilities, communication protocols, environmental specifications, and ordering information. Features include motor protection, IEC 61850, Modbus TCP, and RS485 communication.
Preview Easergy P5 User Manual: Communication Protocols and Configuration
Comprehensive guide to the Schneider Electric Easergy P5 protection relay's communication capabilities. This manual details protocols like IEC 61850, DNP3, Modbus, and EtherNet/IP, essential for power system automation and integration.
Preview Schneider Electric Easergy P3U REL52052 Protection Relay Datasheet
Technical data sheet for the Schneider Electric Easergy P3U REL52052 protection relay, detailing its characteristics, main features, protection types, control types, environmental specifications, and ordering information.