Easergy T300 range SC150 Switch control unit

Installation Guide

Description

The SC150 module of the Easergy T300 range is the interface for control of the MV cubicle's equipment.

NOTICE: HAZARD OF INCORRECT CURRENT MEASUREMENTS

Failure to follow these instructions can result in equipment damage.

NOTE: Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

The SC150 is formed of the following components:

Port 1: Double Ethernet ports LAN 1 and 2

Characteristics: 10/100 Base-T RJ45 connector.

Description: Double ports dedicated to internal communication between Easergy T300 modules or for connecting a PC. Isolation: 2 kVAC. 10 Ethernet jumpers (Ref: EMS59528) provide as accessories allow the internal Ethernet connection between the modules HU250, SC150 and LV150.

Port 2: Switch states

Characteristics: 9-pin plug-in screw connectors.

Description: 8 digital inputs: 6 inputs allocated to information and states coming from the switch, 2 unassigned inputs customizable by configuration (via the advanced configuration tool Easergy Builder).

Port 3: Current inputs

Characteristics: 6-pin plug-in screw connector.

Description: 4 inputs for connecting CTs: 3 phase CTs, 1 core balanced CT. Allows the following types of setup: Type A setup: 3 phase CTs, Type C setup: 1 core balanced CT, Type D setup: 3 phase CTs + 1 core balanced CT. Note: Wire S2 of the CT (blue wire) is connected internally to the CT grounding wire.

Switch controls

Characteristics: 3-pin plug-in screw connector.

Description: The control polarity of the motor pack (common) is customizable via output DO1. This can be done by +V or -V (0V), and the polarization voltage (V) must comply with the following values: 12 VDC < V < 127 VDC, 90 VAC < V < 220 VAC. Max. permissible current: 15 A peak; 8 A permanent (48 VDC); 5 A permanent (60 VDC); 2 A permanent (90 VDC); 1 A permanent (110 VDC).

Port 5: Voltage inputs

Description: Connecting cable SC150 - Voltage sensor adapter can be supplied as an accessory. The wiring of the RJ45 connector on the SC150 side is given solely for information's sake. This connecting cable is supplied for the following adapters: PPACS adapter (ref EMS59575), VPIS VO adapter (ref EMS59570), VDS adapter (ref EMS59571), LPVT adapter (ref EMS59573), SC150-VT adapter - 2 KV/1 mn insulation (ref EMS59574).

Refer to the Installation Guide of each adapter (if available) to have more information about the installation and connection of the adapter.

Connecting cable with the voltage sensor including an RJ45 connector on the SC150 side.

SC150 VPIS output input

SC150 VDS output input

SC150 PPACS adapter

SC150 LPVT adapter

SC150 VT adapter

Recommendation for lengths of cable less than 2 meters

Power supply

The SC150 module is fastened to a DIN rail. No tool is needed for mounting. Simply clip it in order to fasten it as shown below.

External dimensions of the SC150 enclosure

NOTICE: HAZARD OF TERMINAL DAMAGE OR INCORRECT POWER SUPPLY

Failure to follow these instructions can result in equipment damage.

Installation and connecting CTs in the cubicle

Depending on the type of kit supplied, the setup will concern: 3 split-core phase CTs, 3 split-core phase CTs + 1 core balanced CT, or 1 core balanced CT. The setup remains the same irrespective of the type of kit used. The CTs are of the split-core type and have an automatic retaining system for cables of dia. 30 to 45 mm (1.18 to 1.77 in).

NOTICE: HAZARD OF INCORRECT CURRENT MEASUREMENTS

Failure to follow these instructions can result in equipment damage.

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Failure to follow these instructions will result in death or serious injury.

VT adapter for SC150

The SC150-VT adapter is the interface between the Medium Voltage sensors and the SC150. An Ethernet RJ45 cable connecting the VT adapter and the SC150 can be supplied as accessory. Refer to the SC150-VT adapter Installation Guide (ref: NT00394-xx) to have more information about the installation and connection of the SC150-VT adapter.

DANGER: HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Failure to follow these instructions will result in death or serious injury.

Power supply

The SC150 includes two connectors to connect the power supply. These two connectors are connected together internally in the SC150. Having two power supply connections can facilitate connection between the modules. No strapping is necessary. Connect the SC150 as shown in the following diagram.

Parameters setup

Installation of the SC150 module requires no parameters setup. This is performed during the commissioning/configuration stages. Refer to the User manual and the T300 Quick start for any further information.

Identification

The serial number of the SC150 is formed as follows: Year - Week - Work order, e.g. 15340265 (265th product manufactured, week 34 of the year 2015)

Grounding

The SC150 module must be connected to the ground: Either via the mounting DIN rail. The DIN rail helps ensure electrical continuity (preferably use a DIN rail in 304L stainless steel to withstand the climatic conditions). Either by means of an eye lug and a M4 screw (max. Length 10 mm), screwed in the threaded hole at the back of the SC150 housing (see diagram opposite). Use a green/yellow wire of length 300 mm maximum (11.81 in) and 4 mm² section (11 AWG) for the connection between the eye lug and the ground.

NOTICE: HAZARD OF INCORRECT CURRENT MEASUREMENTS

Failure to follow these instructions can result in equipment damage.

Meaning of indicator colors and states

Once the SC150 has been powered up, some indicator lamps on the front panel may be lit to indicate certain operating states. The buttons allow the user to perform actions. These indications and actions are summarized in the table below:

SC150 states:

Local/Remote

Note: The Local/Remote position displayed on the SC150 is a duplication of the display managed on the HU250 module.

Automatic control states and checks

Note: The automatic control states displayed on the SC150 are a duplication of the display managed on the HU250 module.

Customizable indicator lamps

Local control on switch

Switch state

Switch position symbolized by an illustration in two colors:

Earthing/Grounding switch state

Earthing/Grounding switch position symbolized by two states and one color:

Voltage presence

Fault current detection

Fault current detection is symbolized by two arrows that can indicate the direction of the fault current (for directional fault current type only):

Indicator state table:

Part Indicator Red Green Orange Description
1.1 ON Start-up OK
Fault Major fault Com OFF
Minor fault
1.2 OK
2.1 Local
2.2 Remote Remote Local
3.1 ON ON
3.2 OFF OFF
3.3 Locked Locked Non-locked
4.1 Closed Open Undetermined
4.2 Invalid Int. state Closed Invalid Int. state
4.3 Open Open
6.1 Closed
6.2 Open
7.1 Invalid Interm. state Closed
8 Open
8.1 ON ON Invalid or OFF (1 or 2 ph.) (3 ph. or D16)
9 No fault No fault
9.1 Fault det. in progress Fault det. in progress
9.2 Fault det. in progress ammetric fault

(1) Indicators customizable by configuration. Only default values shown. Note: The indications in bold letters correspond to normal operation (first power up without existence of a potential issue indication). The switchgear and voltage presence states cannot be determined for normal operation, because that depends on the state of the network and the position of the switchgear.

Schneider Electric Contact Information

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison - France
Phone: +33 (0)1 41 29 70 00
www.schneider-electric.com

Publication: Schneider Electric
©2015-2017 Schneider Electric. All Rights Reserved.
As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.
Made in France
This document was printed on environmentally friendly paper
Printing: Schneider Electric
NHA91857-04
06-2017

PDF preview unavailable. Download the PDF instead.

SC150 installation guide Adobe PDF Library 15.0 Adobe InDesign CC 2017 (Windows)

Related Documents

Preview Easergy T300 HU250 Control and Communication Unit Installation Guide
This guide provides detailed instructions for the installation and operation of the Schneider Electric Easergy T300 HU250 Control and Communication Unit, covering its components, connections, and indicators.
Preview Schneider Electric Easergy T300 HU250 Communication Gateway Installation Guide
Installation guide for the Schneider Electric Easergy T300 HU250 communication gateway. Details product features, ports, modem options (3G, 4G, Zigbee), digital/analog I/O, installation procedures, operation indicators, power supply, and compliance information for industrial network management.
Preview Schneider Electric Medium Voltage Switchgear Components Catalog 2021
Explore the comprehensive 2021 catalog from Schneider Electric, featuring a wide range of components for Medium Voltage switchgear. Discover solutions for circuit breakers, contactors, switches, disconnectors, and fuses, designed for enhanced connectivity, flexibility, and efficiency.
Preview Easergy VPIS V3 Voltage Presence Indicating System for Medium Voltage Cubicles
Detailed information on the Schneider Electric Easergy VPIS V3, a self-powered voltage presence indicating system for medium voltage cubicles. Includes product overview, technical specifications, characteristics, and reference selection.
Preview Schneider Electric UPS Network Management Card 2 User Guide
Comprehensive user guide for Schneider Electric's UPS Network Management Card 2 (AP9630, AP9631, AP9635), detailing features, installation, configuration, monitoring, and troubleshooting for network-based UPS management.
Preview Schneider Electric ABLS1A48100 Regulated Power Supply Data Sheet
Technical data sheet for the Schneider Electric ABLS1A48100 regulated power supply, featuring 100-240V AC input, 48V DC output, and 10A current. Includes specifications, environmental data, ordering information, and performance curves.
Preview Schneider Wiser CCT5011-0002 Micro Module Light Switch: Installation, Specs, Safety
Comprehensive guide to the Schneider Electric Wiser CCT5011-0002 micro module light switch. Includes installation instructions, wiring diagrams, technical specifications, load capacities, and safety warnings. Zigbee 3.0 certified for smart home automation.
Preview Schneider Electric ARGUS Light-Sensitive Switches: Installation and Operation Guide
Comprehensive guide for installing and operating Schneider Electric ARGUS light-sensitive switches (MTN544819, MTN544894, MTN544829), covering safety, connection, installation, and technical specifications.