Easergy VPIS V3

Voltage Presence Indicating System for Medium Voltage Cubicles

Schneider Electric

Product at a glance

VPIS V2 and VPIS V3

The VPIS V3 is a self-powered voltage presence indicating system, in compliance with the IEC 62271-206 standard.

It includes:

It consists of two parts:

Retrofit of a VPIS V1 or VPIS V2 to VPIS V3 is easy: see VPIS Installation and Maintenance manual (reference NT00395-EN) for more details.

Product Description

The 3 plugs on the front panel of VPIS V3 are designed for connection of Phase Concordance unit VPI62421. Never inject any current or voltage signal in these plugs.

VPIS V3 is designed to indicate the voltage presence according to IEC 62271-206. It does not provide any guarantee of voltage absence.

Phase concordance can be carried out between 2 VPIS V3 using Phase Concordance unit reference VPI62421. This is the same Phase Concordance Unit as for VPIS V2. It is not possible to carry out Phase Concordance between a VPIS V2 and a VPIS V3. See VPI62421 User Manual (reference NT00214-FR-EN) for more details. VPIS V3 is not designed to be used with other Phase Concordance Unit than VPI62421.

Threshold

In compliance with the IEC 62271-206 standard, the 3 VPIS V3 indication LEDs are lit or flashing when the network voltage or the relevant phase is > 45% of the rated voltage.

IEC 62271-206: Equivalent percentage of network voltage U Equivalent percentage of rated voltage V Status of VPIS indicator LEDs
Phase-to-phase Voltage value 10% 45% Extinguished
Phase-to-ground (earth) 17% 78% Lit or flashing

The flashing frequency increases with the network voltage value. At rated voltage, the indicator LEDs seem to be lit steadily.

Characteristics

Electromagnetic compatibility

Standards Criteria Test levels
Emitted radiation IEC 62271-1 § 6.9.1.2 30 MHz-1 GHz
Immunity test
Immunity to electrostatic discharge IEC 61000-4-2
IEC 62271-1 § 6.9.2.1
B +6 kV contact discharge
+8 kV discharge in air
Radiated, radio-frequency, electromagnetic field immunity IEC 61000-4-3
IEC 62271-1 § 6.9.2.1
A 10 V/m 80% AM at 1 kHz
80 MHz to 3 GHz
Immunity to electrical fast transients IEC 61000-4-4
IEC 62271-1 § 6.9.2.3
B ±2 kV: mains power supply
± 1 kV in differential mode
Slow damped oscillatory wave immunity IEC 61000-4-18
IEC 62271-1 § 6.9.2.4
B ±2.5 kV in common mode
Radiated magnetic field immunity IEC 61000-4-8
IEC 62271-1 § 6.9.2.1
B Permanent magnetic field at 100 A/m,
1000 A/m during 1 s

Climatic tests

Standards Test levels
Operating temperature IEC 60068-2-14 -25°C to +85°C
Storage temperature -40°C to +85°C
Ageing test Not in compliance with a standard Climatic cycles including damped heat (+85°C with 95%RH) and rapid temperature variations from -40°C to +85°C. Full test duration: 1000 hours

Mechanical tests

Standards Test levels
Mechanical Protection IEC 60529 IP3X
Impacts IEC 61958-1
IEC 60068-2-75
IK52 Joules
3 impacts in the weakest places

Mechanical Description

Dimensions

Diagram showing dimensions: 70mm, 10mm, 35mm, 64mm, aperture 32 x 53 mm, Ø M3.

VPIS V3 Components

Diagrams showing VPIS V3 components: "Open" seal, Standard surge protection, Voltage presence indication, Rubber shutter.

Diagrams showing connection components: Coupling elements cable with 4-pin connector, Voltage output cable, Ethernet cable, VPIS Adapter.

Connection

Installation recommendation

It is important to respect certain rules regarding the installation of the cable from cubicle coupling elements. It must be fixed so that in case of condensation, water flowing along the wires is guided to the ground and not to the wiring harness input of the VPIS.

VPIS V3 references selection table

The range of use for each VPIS-V3 depends on Service voltage, network frequency and the switchgear capacitor. Here are typical range of use for 50Hz/60Hz. In case of use only for 50Hz or only 60Hz, the range of use could be expanded, please consult the switchgear offer manager.

3 kV 6 kV 10 kV 15 kV 20 kV 30 kV 40 kV
SM6-24 First choice: VPI626x3
Second choice: VPI626x4 (2kV-4kV)
First choice: VPI626x4 (4kV-8kV)
Second choice: VPI626x4 (4kV-7kV)
First choice: VPI626x7 (3.4 kV-6.3 kV)
Second choice: VPI626x5 (5 kV-11 kV)
First choice: VPI626x5 (7 kV-13 kV)
Second choice: VPI626x6 (8 kV-15 kV)
First choice: VPI626x7 (9 kV-17 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (13 kV-25 kV)
Second choice: VPI626x8 (17 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)
RM6 First choice: VPI626x3 (2.5 kV-5 kV)
Second choice: VPI626x3 (3 kV-7 kV)
First choice: VPI626x4 (4 kV-7 kV)
Second choice: VPI626x4 (3 kV-7 kV)
First choice: VPI626x5 (5 kV-11 kV)
Second choice: VPI626x5 (5.8 kV-12 kV)
First choice: VPI626x6 (8 kV-15 kV)
Second choice: VPI626x6 (9.8 kV-21 kV)
First choice: VPI626x7 (10.1 kV-24 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (14kV-30.5 kV)
First choice: VPI626x8 (20.5 kV-44.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)
Flusarc 50 Hz and 60 Hz First choice: VPI626x1 (3.3 kV-7.5 kV)
Second choice: VPI626x2 (3.3 kV-7.5kV)
First choice: VPI626x3 (5.8 kV-12 kV)
Second choice: VPI626x3 (5.8 kV-12 kV)
First choice: VPI626x5 (7.6kV-12 kV)
Second choice: VPI626x5 (7.6kV-12 kV)
First choice: VPI626x6 (9.8 kV-21 kV)
Second choice: VPI626x6 (9.8 kV-21 kV)
First choice: VPI626x7 (10.1 kV-24 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (14 kV-30.5 kV)
First choice: VPI626x8 (20.5 kV-44.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)
Ringmaster RN2D First choice: VPI626x3 (3 kV-7 kV)
Second choice: VPI626x3 (3 kV-7 kV)
First choice: VPI626x3 (3 kV-7 kV)
Second choice: VPI626x4 (4.5 kV-12 kV)
First choice: VPI626x5 (6 kV-13 kV)
Second choice: VPI626x5 (6 kV-13 kV)
First choice: VPI626x6 (9.8 kV-21 kV)
Second choice: VPI626x6 (9.8 kV-21 kV)
First choice: VPI626x7 (10.1 kV-24 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (14 kV-30.5 kV)
First choice: VPI626x8 (20.5 kV-44.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)
FBX C, RE, T1 First choice: VPI626x3 (3 kV-7 kV)
Second choice: VPI626x3 (3 kV-7 kV)
First choice: VPI626x4 (4.5 kV-12 kV)
Second choice: VPI626x4 (4.5 kV-12 kV)
First choice: VPI626x5 (6 kV-13 kV)
Second choice: VPI626x5 (6 kV-13 kV)
First choice: VPI626x6 (9.8 kV-21 kV)
Second choice: VPI626x6 (9.8 kV-21 kV)
First choice: VPI626x7 (10.1 kV-24 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (14 kV-30.5 kV)
First choice: VPI626x8 (20.5 kV-44.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)
FBX T2, CB First choice: VPI626x3 (3 kV-7 kV)
Second choice: VPI626x3 (3 kV-7 kV)
First choice: VPI626x4 (4.5 kV-12 kV)
Second choice: VPI626x4 (4.5 kV-12 kV)
First choice: VPI626x5 (6 kV-13 kV)
Second choice: VPI626x5 (6 kV-13 kV)
First choice: VPI626x6 (9.8 kV-21 kV)
Second choice: VPI626x6 (9.8 kV-21 kV)
First choice: VPI626x7 (10.1 kV-24 kV)
Second choice: VPI626x7 (10.1 kV-24 kV)
First choice: VPI626x8 (14 kV-30.5 kV)
Second choice: VPI626x8 (14 kV-30.5 kV)
First choice: VPI626x8 (20.5 kV-44.5 kV)
Second choice: VPI626x8 (20.5 kV-44.5 kV)

For VPI626x.. references, x = 0 for the non VO VPIS variant, x =1 for the VPIS VO variant.

(*) These references are no longer manufactured.

Commercial references

Reference Designation
VPI62601 VPIS V3 LED VOLTAGE INDICATION 3.5 muA
VPI62602 VPIS V3 LED VOLTAGE INDICATION 5.1 muA
VPI62603 VPIS V3 LED VOLTAGE INDICATION 7.4 muA
VPI62604 VPIS V3 LED VOLTAGE INDICATION 10.7 muA
VPI62605 VPIS V3 LED VOLTAGE INDICATION 15.5 muA
VPI62606 VPIS V3 LED VOLTAGE INDICATION 22.4 muA
VPI62607 VPIS V3 LED VOLTAGE INDICATION 32.5 muA
VPI62608 VPIS V3 LED VOLTAGE INDICATION 47.2 muA
VPI62609 VPIS V3 LED VOLTAGE INDICATION 68.4 muA
VPI62611 VPIS V3 VO LED VOLTAGE INDICAT. 3.5 muA
VPI62612 VPIS V3 VO LED VOLTAGE INDICAT. 5.1 muA
VPI62613 VPIS V3 VO LED VOLTAGE INDICAT. 7.4 muA
VPI62614 VPIS V3 VO LED VOLTAGE INDICAT. 10.7 muA
VPI62615 VPIS V3 VO LED VOLTAGE INDICAT. 15.5 muA
VPI62616 VPIS V3 VO LED VOLTAGE INDICAT. 22.4 muA
VPI62617 VPIS V3 VO LED VOLTAGE INDICAT. 32.5 muA
VPI62618 VPIS V3 VO LED VOLTAGE INDICAT. 47.2 muA
VPI62619 VPIS V3 VO LED VOLTAGE INDICAT. 68.4 muA

Environmental Protection

Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.

SCHNEIDER ELECTRIC Industries SAS
35, rue Joseph Monier
F - 92506 Rueil Malmaison (France)
www.schneider-electric.com

NRJTDS17764EN_092020
©2020 Schneider Electric SE. All rights reserved. All Schneider Electric trademarks and service marks are the property of Schneider Electric SE, its subsidiaries and affiliated companies.

PDF preview unavailable. Download the PDF instead.

VPISV3- NRJTDS17764EN-092020 Adobe PDF Library 15.0 Adobe InDesign 15.1 (Windows)

Related Documents

Preview Schneider Electric Medium Voltage Switchgear Components Catalog 2021
Explore the comprehensive 2021 catalog from Schneider Electric, featuring a wide range of components for Medium Voltage switchgear. Discover solutions for circuit breakers, contactors, switches, disconnectors, and fuses, designed for enhanced connectivity, flexibility, and efficiency.
Preview Schneider Electric Easergy SC150 Installation Guide
Installation guide for the Schneider Electric Easergy SC150 Switch Control Unit, part of the Easergy T300 range. Covers connections, operation, indicators, and safety precautions for MV electrical network management.
Preview Easergy T300 HU250 Control and Communication Unit Installation Guide
This guide provides detailed instructions for the installation and operation of the Schneider Electric Easergy T300 HU250 Control and Communication Unit, covering its components, connections, and indicators.
Preview Easergy P5 User Manual: Communication Protocols and Configuration
Comprehensive guide to the Schneider Electric Easergy P5 protection relay's communication capabilities. This manual details protocols like IEC 61850, DNP3, Modbus, and EtherNet/IP, essential for power system automation and integration.
Preview Easergy P5 Communication User Manual: Protocols and Configuration
Comprehensive user manual for Schneider Electric's Easergy P5 protection relay, detailing communication protocols like IEC 61850, DNP3, IEC 60870-5-101, IEC 60870-5-103, Modbus, and EtherNet/IP, along with configuration guides for power utility automation systems.
Preview Schneider Electric SM6 Modular Units Catalog: Air Insulated Switchgear up to 36kV
Explore the Schneider Electric SM6 modular units, a comprehensive catalog detailing air insulated switchgear solutions up to 36kV for Medium Voltage Distribution. Discover features, benefits, and applications.
Preview Schneider Electric Easergy T300 HU250 Communication Gateway Installation Guide
Installation guide for the Schneider Electric Easergy T300 HU250 communication gateway. Details product features, ports, modem options (3G, 4G, Zigbee), digital/analog I/O, installation procedures, operation indicators, power supply, and compliance information for industrial network management.
Preview Schneider Electric Altivar Process ATV6xx DTM Library V3.3.1 Release Notes
Release notes for Schneider Electric's Altivar Process ATV6xx DTM Library software component, detailing new features, bug fixes, and compatibility information for firmware versions.