Schneider Electric Easergy P3U REL52052 Protection Relay
Product data sheet
Characteristics
REL52052
Easergy P3U 3CT 1lo ringlug 1VT 8DI 8DO 48-230V DI110V 2RJ45 ANSI
Product availability: Stock - Normally stocked in distribution facility
Price*: 2276.56 USD
Main
Range of Product | Easergy P3 |
Product or Component Type | Protection relay |
Relay application | Universal |
Device short name | P3U20-6AAA2AHAB |
Device mounting | Flush |
[Us] rated supply voltage | 48...230 V AC/DC |
Input type | 3 1/5 A CT phase current, 1 1/5 A CT residual current, 1 100 V/110 V VT voltage |
Number of sensors | 0 temperature, 0 arc |
Digital input number | 8.0 |
Number of Outputs | 8 DO |
Analogue input number | 0 |
Analogue output number | 0 |
Integrated connection type | Front USB port 1, Rear RJ45 2 |
Communication port protocol | IEC 61850 ed. 1, IEC 61850 ed. 2, IEC 60870-5-101, DNP3 TCP, Modbus TCP, EtherNet/IP |
Redundancy communication port protocol | RSTP, PRP |
Cybersecurity | Password protection, Port hardening |
Protection Type
- Phase overcurrent 50/51
- Earth fault overcurrent 50N/51N
- Directional earth fault 67N
- Transient earth fault 67NI
- Capacitor bank unbalance 51C
- Broken conductor 46 12/11
- Cold load pick-up
- H2 detection 68H2
- H5 detection 68H5
- Breaker failure 50BF
- Switch ON to fault (SOTF)
- Recloser 79
- Phase undercurrent 37
- Excessive starting time, locked rotor 48/51LR
- Motor restart inhibition 66
- Capacitor overvoltage 59C
- Negative sequence overcurrent 46
- Earth fault overvoltage 59N
- Rate of change of frequency 81R
- Lockout relay 86
- CT supervision 60
- Programmable stages 99
- Programmable curve
Arc flash protection
No
Type of measurement
- Current 3-phase
- Current zero sequence
- Current positive sequence
- Current negative sequence
- Current ratio of negative and positive
- Voltage zero sequence
- Earth fault reactance
- Frequency
- Current phasor diagram view
- Current 2nd, 15th harmonics with THD
- Condition monitoring CB wear
Control Type
- Switchgear control and monitoring
- Programmable switchgear interlocking
- Local control on single-line diagram
- Local control with I/O keys
- Local/Remote control
- 2 function keys
- Mobile application with Easergy SmartApp
- Web-server
4 controlled + 4 displayed
Setting
4
Monitoring function
- Trip circuit supervision 74
- Circuit breaker monitoring
- Relay self-monitoring
Network and machine diagnosis type
- Event recording
- Disturbance recording
- Tripping context
Switchgear diagnosis type
- CT supervision
- Trip circuit supervision TCS
Connections - terminals
- Screw removable (digital input/output)
- Pin removable (current transformer)
- Pin removable (voltage transformer)
Complementary
Operating threshold | 110 V AC/DC |
Time synchronisation protocol | SNTP |
Web server | Embedded HTTP server |
Display type | LCD |
Number of key | 2 customizable |
Local signalling | 4 LEDs |
Height | 6.67 In (169.5 mm) |
Dimensions
Width | 6.69 In (170 mm) |
Depth | 8.07 In (205 mm) |
Net weight | 5.51 Lb(US) (2.5 kg) maximum |
Environment
Electromagnetic compatibility
Emission tests IEC/EN 60255-26 ed. 3, Emission tests class A CISPR 11, Emission tests class A CISPR 22, EMC immunity IEC/EN 60255-26 ed. 3, EMC immunity EN/IEC 61000-4-18, EMC immunity IEC 60255-22-1, EMC immunity level 4 EN/IEC 61000-4-2, EMC immunity IEC 60255-22-2, EMC immunity level 3 EN/IEC 61000-4-3, EMC immunity IEC 60255-22-3, EMC immunity level 4 EN/IEC 61000-4-4, EMC immunity IEC 60255-22-4, EMC immunity level 3 EN/IEC 61000-4-5, EMC immunity IEC 60255-22-5, EMC immunity level 3 EN/IEC 61000-4-6, EMC immunity IEC 60255-22-6, EMC immunity EN/IEC 61000-4-8, EMC immunity level 5 EN/IEC 61000-4-9, EMC immunity EN/IEC 61000-4-29, EMC immunity EN/IEC 61000-4-11, EMC immunity EN/IEC 61000-4-17, EMC immunity IEC 60255-27, EMC immunity class III IEC 60255-5, EMC immunity EN/IEC 60255-1
Mechanical robustness
Vibrations class II) IEC 60255-21-1, VibrationsFc IEC 60068-2-6, Shocks class II) IEC 60255-21-2, ShocksEa IEC 60068-2-27, Seismic tests method A class II) IEC 60255-21-3
Environmental characteristic
Exposure to dry heat Bd EN/IEC 60068-2-2, Exposure to cold Ad EN/IEC 60068-2-1, Exposure to damp heat in service Db EN/IEC 60068-2-30, Exposure to damp heat in service Cab EN/IEC 60068-2-78
Ambient air temperature for operation: -40...149 °F (-40...65 °C)
Ambient Air Temperature for Storage: -40...158 °F (-40...70 °C)
IP degree of protection: IP54 conforming to IEC 60529
Relative humidity: 0...95%, without condensation
Operating altitude: 6561.68 ft (2000 m)
Protective treatment: Conformal coating
Ordering and shipping details
Category | 11405-EASERGY P3 PROTECTIVE RELAYS |
Discount Schedule | PL1S |
GTIN | 3606481465429 |
Returnability | No |
Country of origin | US |
Packing Units
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 11.42 In (29.0 cm) |
Package 1 Width | 11.81 In (30.0 cm) |
Package 1 Length | 15.75 In (40.0 cm) |
Package 1 Weight | 7.74 Lb(US) (3.51 kg) |
Product Life Status
Commercialised
Related Documents
![]() |
Easergy P5 User Manual: Communication Protocols and Configuration Comprehensive guide to the Schneider Electric Easergy P5 protection relay's communication capabilities. This manual details protocols like IEC 61850, DNP3, Modbus, and EtherNet/IP, essential for power system automation and integration. |
![]() |
Schneider Electric Easergy P3M32 Protective Relay (REL52121) - Data Sheet Detailed data sheet for the Schneider Electric Easergy P3M32 protective relay, covering its main characteristics, protection functions, measurement capabilities, communication protocols, environmental specifications, and ordering information. Features include motor protection, IEC 61850, Modbus TCP, and RS485 communication. |
![]() |
Easergy P5 Communication User Manual: Protocols and Configuration Comprehensive user manual for Schneider Electric's Easergy P5 protection relay, detailing communication protocols like IEC 61850, DNP3, IEC 60870-5-101, IEC 60870-5-103, Modbus, and EtherNet/IP, along with configuration guides for power utility automation systems. |
![]() |
Easergy P5 User Manual: Communication Protocols and Configuration Comprehensive user manual for the Schneider Electric Easergy P5 protection relay, detailing supported communication protocols like IEC 61850, DNP3, Modbus, and EtherNet/IP, along with configuration and network architecture information. |
![]() |
Schneider Electric REL52132 Easergy P3 Protection Relay Datasheet Detailed product data sheet for the Schneider Electric REL52132 Easergy P3 protection relay, covering characteristics, main features, protection types, measurement capabilities, control functions, environmental specifications, and shipping details. |
![]() |
SCADAPack E Operational Reference Manual This manual provides detailed operational information for the SCADAPack E RTU, covering aspects such as LED indicators, switch settings, startup and shutdown procedures, time conversion, I/O operations, communication port assignments, and command-line diagnostics. |
![]() |
LXM32M Ethernet TCP/IP Module Modbus TCP Fieldbus Manual Explore the Schneider Electric LXM32M Ethernet TCP/IP Module with this fieldbus manual. Learn about Modbus TCP communication, configuration, operation, and troubleshooting for industrial automation. |
![]() |
Easergy P3G30 and P3G32 Generator Protection User Manual | Schneider Electric Comprehensive user manual for Schneider Electric Easergy P3G30 and P3G32 generator protection relays, detailing machine differential protection, installation, configuration, and operational features. |