Schneider Electric Easergy P3M32 Protective Relay (REL52121)
Product Data Sheet - Characteristics
A front view of the Schneider Electric Easergy P3M32 protective relay, showing its compact design with a display screen and control buttons.
Main Characteristics
Range of Product | Easergy P3 |
---|---|
Product or Component Type | Protection relay |
Relay application | Motor |
Product reference | P3M32-CGG1A-AA1FA-BBAAB |
Device mounting | Flush |
Power supply | 48...230 V AC/DC |
Measuring inputs | 6 1/5 A CT phase current, 2 5/1 A CT residual current, 1 1/0.2 A CT residual current, 4 100 V/110 V VT voltage |
Number of sensors | 0 temperature, 0 arc |
Number of Digital Inputs (DI) | 12.0 |
Number of Digital Outputs (DO) | 14 DO, 1 watchdog |
Number of analogue inputs | 0 |
Number of analogue outputs | 0 |
Communication ports | Front USB port 1, Rear RJ45 1, Rear RS485 1 |
Communication protocols | IEC 61850 ed. 1, IEC 61850 ed. 2, IEC 60870-5-101, DNP3 TCP, Modbus TCP, EtherNet/IP, IEC 60870-5-103, DNP3, Modbus RTU, DeviceNet, SPAbus |
Cybersecurity | Password protection, Port hardening |
Protection Functions
- Synchro-check 25
- Undervoltage 27
- Directional active underpower 37P
- Phase undercurrent 37
- Negative sequence overcurrent 46
- Negative sequence overvoltage 47
- Excessive starting time, locked rotor 48/51LR
- Thermal overload protection 49
- Earth fault overcurrent 50N/51N
- Phase overcurrent 50/51
- Breaker failure 50BF
- Switch ON to fault (SOTF)
- Capacitor bank unbalance 51C
- Capacitor overvoltage 59C
- Overvoltage 59
- Earth fault overvoltage 59N
- Stator earth fault 64S
- Restricted earth fault 64REF
- Motor restart inhibition 66
- Directional phase overcurrent 67
- Directional earth fault 67N
- H2 detection 68H2
- H5 detection 68H5
- Underfrequency 81/81N
- Rate of change of frequency 81R
- Lockout relay 86
- Machine differential 87M
- Programmable stages 99
- Programmable curve
- Cold load pick-up
Arc flash protection: No
Relay Type: Differential current relay
Measurement Functions
- Current 3-phase
- Current zero sequence
- Current positive sequence
- Current negative sequence
- Current ratio of negative and positive
- Voltage phase to earth
- Voltage phase to phase
- Voltage zero sequence
- Voltage positive sequence
- Voltage negative sequence
- Voltage ratio of negative and positive
- Short circuit fault reactance
- Fault location current
- Earth fault reactance
- Frequency
- Active power
- RMS active power
- Reactive power
- RMS reactive power
- Apparent power
- RMS apparent power
- Active energy
- Reactive energy
- Cos φ
- Tan φ
- Power angle
- Power factor
- Voltage phasor diagram view
- Current phasor diagram view
- Current 2nd, 15th harmonics with THD
- Voltage 2nd, 15th harmonics with THD
- Condition monitoring CB wear
- Voltage interruption
Control Functions
- Switchgear control and monitoring
- Programmable switchgear interlocking
- Local control on single-line diagram
- Local control with I/O keys
- Local/Remote control
- 2 function keys
- Mobile application with Easergy SmartApp
- Web-server
Controllable switchgear devices: 6 controlled + 8 displayed
Number of setting groups: 4
Monitoring Functions
- Trip circuit supervision 74
- Circuit breaker monitoring
- Relay self-monitoring
- Event recording
- Disturbance recording
- Tripping context
- CT/VT supervision
- Trip circuit supervision TCS
Complementary Details
Operating threshold | 110 V AC/DC |
---|---|
Time synchronisation protocol | SNTP |
Web server | Embedded HTTP server |
Display type | LCD 128 x 128 pixels with single line diagram, LCD 128 x 128 pixels with ANSI symbols |
Number of key | 2 customizable |
Local signalling | 2 LEDs, 16 LEDs programmable |
Height | 6.93 in (176 mm) |
Width | 10.63 in (270 mm) |
Depth | 9.06 in (230 mm) |
Net weight | 9.26 lb(US) (4.2 kg) maximum |
Environment
Electromagnetic compatibility
- Emission tests IEC/EN 60255-26 ed. 3
- Emission tests class A CISPR 11
- Emission tests class A CISPR 22
- EMC immunity IEC/EN 60255-26 ed. 3
- EMC immunity EN/IEC 61000-4-18
- EMC immunity IEC 60255-22-1
- EMC immunity level 4 EN/IEC 61000-4-2
- EMC immunity IEC 60255-22-2
- EMC immunity level 3 EN/IEC 61000-4-3
- EMC immunity IEC 60255-22-3
- EMC immunity level 4 EN/IEC 61000-4-4
- EMC immunity IEC 60255-22-4
- EMC immunity level 3 EN/IEC 61000-4-5
- EMC immunity IEC 60255-22-5
- EMC immunity level 3 EN/IEC 61000-4-6
- EMC immunity IEC 60255-22-6
- EMC immunity EN/IEC 61000-4-8
- EMC immunity level 5 EN/IEC 61000-4-9
- EMC immunity EN/IEC 61000-4-29
- EMC immunity EN/IEC 61000-4-11
- EMC immunity EN/IEC 61000-4-17
- EMC immunity IEC 60255-27
- EMC immunity class III IEC 60255-5
- EMC immunity EN/IEC 60255-1
Mechanical robustness
- Vibrations class II) IEC 60255-21-1
- Vibrations Fc IEC 60068-2-6
- Shocks class II) IEC 60255-21-2
- ShocksEa IEC 60068-2-27
- Seismic tests method A class II) IEC 60255-21-3
Climatic withstand
- Exposure to dry heat Bd EN/IEC 60068-2-2
- Exposure to cold Ad EN/IEC 60068-2-1
- Exposure to damp heat in service Db EN/IEC 60068-2-30
- Exposure to damp heat in service Cab EN/IEC 60068-2-78
Ambient air temperature for operation: -40...149 °F (-40...65 °C)
Ambient Air Temperature for Storage: -40...158 °F (-40...70 °C)
IP degree of protection: IP54 conforming to IEC 60529
Relative humidity: 0...95 %, without condensation
Maximum operating altitude: 6561.68 ft (2000 m)
Protective treatment: Conformal coating
Ordering and Shipping Details
Category | 11405-EASERGY P3 PROTECTIVE RELAYS |
---|---|
Discount Schedule | PL1S |
GTIN | 3606481499943 |
Returnability | No |
Packing Units
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 8.27 in (21 cm) |
Package 1 Width | 10.24 in (26 cm) |
Package 1 Length | 12.48 in (31.7 cm) |
Package 1 Weight | 9.92 lb(US) (4.5 kg) |