Delta Temperature Controller

User Manual

Foreword

The user manual details the process of using Delta DT series temperature controllers step by step for beginners to easily set up all kinds of parameters in a short time.

CHAPTER 1: DEFAULT SETTINGS OF PARAMETERS

1.1 Default Settings in Temperature Controller

The following tables show default settings for DTA, DTB, and DTC models.

DTA Model: DTA4896R1

Parameter PV SV
Cont
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62
EPUN
EP-H 500.0
EP-L -20.0
CEFL PCd
5-HC HEAL
ALR1 0
ALR2 0
COSH OFF
C-SL 1
C-NG 1
C-LE 1
C-P6 1
C-6P 1

DTB Model: DTB4896RR

Parameter PV SV
Cont
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
OPE PE
EPUN C
EP-H 600.0
EP-L -99.9
CEFL P08
5-HC HERE
ALR1 0
ALR2 0
COSH OFF
C-SL ASC1
C-NG 1
C-LE 7
C-P6 ELEN
C-6P 1

DTC Model: DTC1000R

Parameter PV SV
Sensor Connection Not connected 0.0
Set up control modes
Control mode PID control
Run/stop Run
Output 1 Heating
Output 2 Heating
Status of key Normal
Auto-tuning End
Set up temperature
Input type PT100
Input unit °C
Set value 0.0
Maximum input temperature 600.0
Minimum input temperature -20.0
Position of decimal point 1 digit after decimal point
Set up PID parameter
Proportional band (P) 47.6
Integral time (I) 260
Derivative time (D) 41
Control cycle 1 20
Integral default value 0.0
Control cycle 2 20
Input compensation 0.0
Password of DTC
Level 1 password Disabled
Level 2 password Disabled
Level 3 password Disabled

1.2 How to Return to Default Settings in DTA

Follow these steps to reset DTA to default settings:

Display PV SV Explanations
Cont Status of the temperature controller
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Select the sensor connected. Default = PT100
EPUN C Temperature unit. Default = °C
EP-H 500.0 Upper limit of temperature range
EP-L -20.0 Lower limit of temperature range
CEFL P08 The control modes include: PID, ON/OFF, MANUAL. Default = PID. Select "ON/OFF" here.
5-HC HEAL Select heating or cooling mode. Default = heating
ALR1 0 Set up Alarm mode 1. Default = alarm output disabled
ALR2 0 Set up Alarm mode 2. Default = alarm output disabled
COSH OFF ON/OFF of communication write-in. Default = OFF
C-SL 1 Communication address
C-NG 9600 Communication speed
C-LE 7 Data length (in bits)
C-P6 ELEN Parity bit
C-6P 1 Stop bit
Back to top Return to the first item in the initial setting mode: CF. Return to PV/SV screen in the operation mode.

Communication

  1. Make sure RS-485 hardware communication cable in DTA has been connected to the computer.
  2. Make sure the communication parameters in DTA are consistent with those in the computer.
Display PV SV Explanations
25.0 00 Status of the temperature controller. Example displayed values
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Example displayed value: PT100 Sensor
COSH OFF ON/OFF of communication write-in
COSH ON OFF: communication write-in disabled ON: communication write-in enabled

DTCOM Software

A description of the DTCOM software interface for single command test is provided. It includes fields for ADDRESS (e.g., 01), COMMAND (e.g., Write One W), FUNC ADDR (e.g., 471B), WRITE DATA (e.g., 1234), LRC (e.g., 51), SEND, and RECEIVED. A warning states: "Function address = 471B; Write data =1234. (Please DO NOT modify this value; otherwise system confusion may occur.)"

After completing the procedures, DTA will display information on the left hand side, indicating successful return to default settings. A return to default value message states: "Return to default value. The default sensor is PT100, which will be displayed when DTA is not connected to a sensor or thermocouple." The adopted model is DTA4896R1 with firmware V3.50.

1.3 How to Return to Default Settings in DTB

Follow these steps to reset DTB to default settings:

Display PV SV Explanations
Cont Status of the temperature controller
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Select the sensor connected. Default = PT100
EPUN C Temperature unit. Default = °C
EP-H 600.0 Upper limit of temperature range
EP-L -99.9 Lower limit of temperature range
CEFL ANAF The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID. Select "ON/OFF" here.
5-HC HEAL Select heating/cooling/heating 1 cooling 2/heating 2 cooling 1. Default = heating
ALR1 0 Set up Alarm mode 1. Default = alarm output disabled.
ALR2 0 Set up Alarm mode 2. Default = alarm output disabled.
ALR3 0 Set up Alarm mode 3. Default = alarm output disabled.
SBLR OFF Set up system alarm
COSH OFF ON/OFF of communication write-in. Default = OFF
C-SL ASC1 Select communication format
C-NG 1 Communication address
C-LE 9600 Communication speed
C-P6 7 Data length (in bits)
P-69 ELEN Parity bit
SBLP 1 Stop bit
Back to top Return to the first item in the initial setting mode: CF. Return to PV/SV screen in the operation mode

Communication

  1. Make sure RS-485 hardware communication cable in DTB has been connected to the computer.
  2. Make sure the communication parameters in DTB are consistent with those in the computer.
Display PV SV Explanations
15.0 00 Status of the temperature controller. Example displayed value
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Example displayed value: PT100 Sensor
COSH OFF ON/OFF of communication write-in

DTCOM Software

A description of the DTCOM software interface for single command test is provided. It includes fields for ADDRESS (e.g., 01), COMMAND (e.g., Write One W), FUNC ADDR (e.g., 472A), WRITE DATA (e.g., 1234), LRC (e.g., 42), SEND, and RECEIVED. A warning states: "Function address = 472A; Write data =1234. (Please DO NOT modify this value; otherwise system confusion may occur.)"

After completing the procedures, DTB will display information on the left hand side, indicating successful return to default settings. A return to default value message states: "Return to default value. The default sensor is PT100, which will be displayed when DTB is not connected to a sensor or thermocouple." The adopted model is DTB4896RR with firmware V1.50.

1.4 How to Return to Default Settings in DTC

Follow these steps to reset DTC to default settings:

Communication

  1. Make sure RS-485 hardware communication cable in DTC has been connected to the computer.
  2. Make sure the communication parameters in DTC are consistent with those in the computer.

DTCOM Software

A description of the DTCOM software interface for single command test is provided. It includes fields for ADDRESS (e.g., 01), COMMAND (e.g., Write One W), FUNC ADDR (e.g., 472A), WRITE DATA (e.g., 1234), LRC (e.g., 42), SEND, and RECEIVED. A warning states: "Function address = 472A; Write data = 1234 (Please DO NOT modify this value; otherwise system confusion may occur.)"

Another DTCOM software description is provided for a different function address: ADDRESS (e.g., 01), COMMAND (e.g., Write One W), FUNC ADDR (e.g., 474E), WRITE DATA (e.g., 1234), LRC (e.g., 1E), SEND, and RECEIVED. A warning states: "Clear the user's settings. Function address = 474E; Write data = 1234 (Please DO NOT modify this value; otherwise system confusion may occur.)"

After switching off DTC and re-powering it, it will return to default settings. The adopted model is DTC1000R with firmware V1.40.

CHAPTER 2: CONTROL MODES IN DTA

2.1 ON/OFF

There are three control modes in DTA: ON/OFF, MANUAL and PID. First, press SET for 3 seconds to enter the "initial setting" mode. See below for how to switch between each mode:

A diagram shows mode switching: Press SET to enter Operation Mode. Press SET for more than 3 secs to enter Initial Setting Mode. From Initial Setting Mode, press SET to return to Operation Mode. From Operation Mode, press SET to enter Regulation Mode. Regulation Mode, Operation Mode, and Initial Setting Mode are depicted as distinct states.

Display PV SV Explanations
Cont Status of the temperature controller
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Select the sensor connected. Default = PT100
EPUN C Temperature unit. Default = °C
EP-H 500.0 Upper limit of temperature range
EP-L -20.0 Lower limit of temperature range
CEFL ANAF The control modes include: PID, ON/OFF, MANUAL. Default = PID. Select "ON/OFF" here.
5-HC HEAL Select heating or cooling mode. Default = heating
ALR1 0 Set up Alarm mode 1. Default = alarm output disabled
ALR2 0 Set up Alarm mode 2. Default = alarm output disabled
COSH OFF ON/OFF of communication write-in. Default = OFF
C-SL 1 Communication address
C-NG 9600 Communication speed
C-LE 7 Data length (in bits)
C-P6 ELEN Parity bit
C-6P 1 Stop bit
Back to top Return to the first item in the initial setting mode: CF. Return to PV/SV screen in the operation mode.

2.2 MANUAL

Press SET for 3 seconds in the main screen to enter the "initial setting mode". Press several times until the parameter 6860 is displayed.

Display PV SV Explanations
CERL 6860 Status of the temperature controller. The control modes include: PID, ON/OFF, MANUAL. Default = PID. Select "MANUAL" here.
Back to top Press SET to return to the main screen.

Parameters relevant to MANUAL control

Press SET in the main screen of DTA to enter the "regulation mode".

Display PV SV Explanations
HEPB 20 Set up heating or cooling control cycle. Default = heating, 20 seconds per cycle.
CEPA 20

Press [down arrow] in the main screen of DTA to enter the "operation mode".

Display PV SV Explanations
r-5 LOC Run/stop
606 0 Manually adjust the output percentage. Assume the percentage value = 50 and the cycle = 20 seconds plus heating control, the system will conduct heating output for 10 seconds and stop for the other 10 seconds.

2.3 PID

Press SET for 3 seconds in the main screen to enter the "initial setting mode". Press several times until the parameter CEFL is displayed.

Display PV SV Explanations
CEFL PCD Status of the temperature controller. The control modes include: PID, ON/OFF, MANUAL. Default = PID. Select "PID" here.
Back to top Press SET to return to the main screen.

Parameters relevant to PID control

Press SET in the main screen of DTA to enter the "regulation mode".

Display PV SV Explanations
AE OFF ON/OFF of auto-tuning
P 47.6 Default value for proportional control
I 260 Default value for integral control
D 4 Default value for derivative control
COF 0 Default integral value
HEPA 20 Heating/cooling control cycle
EPOF 0.0 Temperature inaccuracy adjustment value

Press [down arrow] in the main screen of DTA to enter the "operation mode".

Display PV SV Explanations
r-5 RUN Run/stop
LOC OFF Key-locked function
606 0 Output volume. In PID control mode, this is a read-only parameter and cannot be modified.

CHAPTER 3: CONTROL MODES IN DTB

3.1 ON/OFF

There are four control modes in DTB: ON/OFF, MANUAL, PID and PID PROG. To switch to ON/OFF mode, first press SET for 3 seconds to enter the "initial setting" mode. See below for how to switch between each mode:

A diagram shows mode switching: Press SET to enter Operation Mode. Press SET for more than 3 secs to enter Initial Setting Mode. From Initial Setting Mode, press SET to return to Operation Mode. From Operation Mode, press SET to enter Regulation Mode. Regulation Mode, Operation Mode, and Initial Setting Mode are depicted as distinct states.

Display PV SV Explanations
Cont Status of the temperature controller
Initial Setting Mode Entry Press SET for more than 3 seconds to enter initial setting mode
P62 Select the sensor connected. Default = PT100
EPUN C Temperature unit. Default = °C
EP-H 600.0 Upper limit of temperature range
EP-L -99.9 Lower limit of temperature range
CEFL ANAF The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID. Select "ON/OFF" here.
5-HC HEAL Select heating/cooling/heating 1 cooling 2/heating 2 cooling 1. Default = heating
ALR1 0 Set up Alarm mode 1. Default = alarm output disabled.
ALR2 0 Set up Alarm mode 2. Default = alarm output disabled.
ALR3 0 Set up Alarm mode 3. Default = alarm output disabled.
SBLR OFF Set up system alarm
COSH OFF ON/OFF of communication write-in. Default = OFF
C-SL ASC1 Select communication format
C-NG 1 Communication address
C-LE 9600 Communication speed
C-P6 7 Data length (in bits)
P-69 ELEN Parity bit
SBLP 1 Stop bit
Back to top Return to the first item in the initial setting mode: CF. Return to PV/SV screen in the operation mode

Parameters relevant to ON/OFF control

Press SET in the main screen of DTB to enter the "regulation mode".

Display PV SV Explanations
HES 00 Set up hysteresis. Can be set as cooling hysteresis as well. Both default values are "0".
CES 00

3.2 MANUAL

Press SET for 3 seconds in the main screen to enter the "initial setting mode". Press several times until the parameter 6860 is displayed.

Display PV SV Explanations
CERL 6860 Status of the temperature controller. The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID. Select "MANUAL" here.
Back to top Press SET to return to the main screen.

Parameters relevant to MANUAL control

Press SET in the main screen of DTB to enter the "regulation mode".

Display PV SV Explanations
HEPB 20 Set up heating or cooling control cycle. Default = heating, 20 seconds per cycle.
CEPA 20

Press [down arrow] in the main screen of DTB to enter the "operation mode".

Display PV SV Explanations
r-5 RUN Run/stop
SP 1 Set up the position of decimal point. 1 = value with decimal point; 2 = value without decimal point
LOC OFF Key-locked function
606 0 Manually adjust the output percentage. Assume the percentage value = 50 and the cycle = 20 seconds plus heating control, the system will conduct heating output for 10 seconds and stop for the other 10 seconds.

3.3 PID

Press SET for 3 seconds in the main screen to enter the "initial setting mode". Press several times until the parameter CEFL is displayed.

Display PV SV Explanations
CEFL PCD Status of the temperature controller. The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID.
Back to top Press SET to return to the main screen.

Parameters relevant to PID control

Press SET in the main screen of DTB to enter the "regulation mode".

Display PV SV Explanations
AE OFF ON/OFF of auto-tuning
P 47.6 The 0th default value for proportional control
I 260 The 0th default value for integral control
D 4 The 0th default value for derivative control
COF 0 The 0th default integral value
HEPA 20 Heating/cooling control cycle
EPOF 0.0 Temperature inaccuracy adjustment value

Press [down arrow] in the main screen of DTB to enter the "operation mode".

Display PV SV Explanations
r-5 RUN Run/stop
SP 1 Set up the position of decimal point
LOC OFF Key-locked function
606 0 Output volume. In PID control mode, this is a read-only parameter and cannot be modified.

3.4 PID PROG

Press SET for 3 seconds in the main screen to enter the "initial setting mode". Press several times until the parameter 6860 is displayed.

Display PV SV Explanations
E-L P2.5 Status of the temperature controller. The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID. Select "PID PROG" here.

DTB offers 8 patterns and 8 steps for each pattern, totaling 64 steps. Range of a pattern: OFF ~ 7. OFF = the function disabled.

Pattern/Step SV Time SV
Pattern 0, Step 0 00.00 00:00
Pattern 0, Step 1 00.00 00:00
... ... ...
Pattern 0, Step 7 00.00 00:00
Parameter Value
Actual number of steps executed in pattern 0 P520
Actual number of loops executed in pattern 0 0
Pattern linked after the execution of pattern 0 is completed. OFF = end of linking patterns 0

Back to top: Press SET to return to the main screen. Return to the main screen to switch to the functions below.

Parameters relevant to PID PROG control

Press SET in the main screen of DTB to enter the "regulation mode".

Display PV SV Explanations
PE88 00 The 0th PID parameter. There are 4 groups of PID parameters built in DTB. When the parameter is set ass PID4, the system will automatically adopt the PID value of the current temperature closest to PID0 ~ 3.
500 0.0 The 0th SV
PO 47.6 The 0th default value for proportional control
260 The 0th default value for integral control
80 4 The 0th default value for derivative control
COF 0 The 0th default integral value
HEPA 20 Heating/cooling control cycle
EPOF 0.0 Temperature inaccuracy adjustment value

Press [down arrow] in the main screen of DTB to enter the "operation mode".

Display PV SV Explanations
r-5 Stop/run/program stop/program hold Program stop: Run the system again, and DTB will start from the initial step. Program hold: Run the system again, and DTB will follow and start from the previous step.
SP 1 Set up the position of decimal point
LOC OFF Key-locked function
606 0 Output volume. In PID PROG control mode, this is a read-only parameter and cannot be modified.

CHAPTER 4: CONTROL MODES IN DTC

4.1 ON/OFF

There are four control modes in DTC: ON/OFF, MANUAL, PID and PID PROG. Due to that DTC has no display panel, the settings and monitoring of parameters have to rely on communication. Therefore, you have to check the following 2 items to ensure normal communication.

  1. Make sure RS-485 hardware communication cable in DTC has been connected to the computer.
  2. Make sure the communication parameters in DTC are consistent with those in the computer.

Next, open DTCOM Software and switch to ON/OFF control mode.

The DTCOM software interface for ON/OFF control is shown. It includes sections for Control (Ctrl. Method: ON-OFF, Run/Stop: Run, Out1: Heat, Out2: Heat, Lock Status: Normal), Input (Input Type: K-Type, Unit: C, SV: 0.0, Range Hi: 1300.0, Range Lo: -200.0, Pointer: 1, F/W Version: 1.40), ON-OFF (Hysteresis 1: 0.0, Hysteresis 2: 0.0), Alarm, and PV tuning (PV Offset: 0.0). Security settings are also present.

A note states: "Set up hysteresis. Default = heating hysteresis. Can be set as cooling hysteresis as well. Both default values are "0"."

4.2 MANUAL

Switch the control mode to MANUAL mode.

The DTCOM software interface for MANUAL control is shown. It includes sections for Control (Ctrl. Method: Manual, Run/Stop: Run, Out1: Heat, Out2: Heat, Lock Status: Normal), Input (Input Type: K-Type, Unit: C, SV: 0.0, Range Hi: 1300.0, Range Lo: -200.0, Pointer: 1, F/W Version: 1.40), Manual (Output 1%: 0.0, Ctrl. Period1: 4, Output 2%: 0.0, Ctrl. Period2: 20, Tune Out High: 0, Tune Out Low: 0), Alarm, and PV tuning (PV Offset: 0.0). Security settings are also present.

Notes: "Set up heating or cooling control cycle. Default = heating, 20 seconds per cycle." and "Manually adjust the output percentage. Assume the percentage value = 50 and the cycle = 20 seconds plus heating control, the system will conduct heating output for 10 seconds and stop for the other 10 seconds."

4.3 PID

Switch the control mode to PID mode.

The DTCOM software interface for PID control is shown. It includes sections for Control (Ctrl. Method: PID, Run/Stop: Run, Out1: Heat, Out2: Heat, Lock Status: Normal, Auto tuning: Stop), Input (Input Type: K-Type, Unit: C, SV: 0.0, Range Hi: 1300.0, Range Lo: -200.0, Pointer: 1, F/W Version: 1.40), PID Parameter (Pb: 47.6, Ti: 260, Td: 41, Ctrl. Period1: 4, Offset: 0.0, Ctrl. Period2: 4), Alarm, and PV tuning (PV Offset: 0.0). Security settings are also present.

A note states: "You can conduct auto-tuning on the default PID parameters according to the environment where your equipment is in or its temperature control capability, allowing the temperature controller to generate relevant PID parameters by itself in order to achieve an accurate temperature control."

4.4 PID PROG

Switch the control mode to PID PROG mode.

The DTCOM software interface for PID PROG mode is shown. It includes sections for Control (Ctrl. Method: Ramp Sc, Run/Stop: Run, Out1: Heat, Out2: Heat, Lock Status: Normal, Auto tuning: Stop), Input (Input Type: K-Type, Unit: C, SV: Time Left, Range Hi: 1300.0, Range Lo: -200.0, Pointer: 1, F/W Version: 1.40), PID Parameter (Pb: 47.6, Ti: 260, Td: 41, Ctrl. Period1: 4, Offset: 0.0, Ctrl. Period2: 4), and a Ramp Soak programmer section.

The Ramp Soak programmer section details patterns and steps. For Pattern 0, Step Max is 7. Set Value 0 to 7 and Execute Time 0 to 7 are listed with default values. Loop Count is 0. Link Pattern is 0.0. The table shows values for Pattern 0 through Pattern 4.

Notes: "The 64 steps come from the combination of 8 patterns and 8 steps for each pattern. You can establish maximum 64 steps according to different systems in use." and "There are 8 steps in each pattern. You can define the step, loop and link pattern in each pattern."

PDF preview unavailable. Download the PDF instead.

DELTA IA-TC DT UM EN 20070917 Acrobat Distiller 7.0.5 (Windows)

Related Documents

Preview Delta DTC Series Digital Controller Instruction Sheet
Instruction sheet for the Delta DTC Series Digital Controller, covering installation, specifications, functions, and operation. Includes details on input sensors, output types, alarm modes, communication protocols (RS-485), password protection, and programming.
Preview DELTA DT3 Series Temperature Controller Operation Manual
Comprehensive operation manual for the DELTA DT3 Series Temperature Controllers, covering features, specifications, operation modes, wiring diagrams, and installation.
Preview DELTA DTK Series Temperature Controller Instruction Sheet
Instruction sheet for the DELTA DTK Series Temperature Controller, detailing its features, specifications, operation modes, and installation.
Preview DELTA A Series Temperature Controller Instruction Sheet
Instruction sheet for the DELTA A Series Temperature Controller, providing details on precautions, ordering information, specifications, parameters, operation, and communication protocols.
Preview Delta DVP Series Programmable Logic Controllers (PLCs) - Product Catalog
Explore the Delta DVP Series Programmable Logic Controllers (PLCs), a comprehensive range of industrial automation solutions offering high performance, diverse models, and advanced motion control capabilities. This catalog details specifications, features, and ordering information for various DVP PLC series.
Preview 台達 NC300 系列 CNC 控制器快速入門指南
本指南提供台達 NC300 系列 CNC 控制器(包括 NC300A-MI-A、NC300A-MS-A、NC311A-MS-A、NC310A-MS-A、NC200A-MI-A 等型號)的安裝、操作與安全重要資訊,旨在協助使用者正確使用。
Preview DELTA ATLO-SW1-EWELINK Smart LED Lighting Controller User Manual
Comprehensive user manual for the DELTA ATLO-SW1-EWELINK Smart LED Lighting Controller, covering installation, features, technical specifications, safety guidelines, and operation with the eWeLink platform.
Preview Delta Industrial Automation Products Catalog: PLCs, HMIs, Servo Drives, and More
Comprehensive catalog of Delta industrial automation products, including Programmable Logic Controllers (PLCs) from various series (DVP, AS, AH, ES, EX, TP), Human Machine Interfaces (HMIs), AC servo drives and motors, industrial PCs, Ethernet switches, and accessories. Features detailed specifications, applications, and pricing.