DELTA A Series Temperature Controller

Instruction Sheet

2013/03/27

Precautions

DANGER! Caution! Electric Shock!

  1. Do not touch AC terminals while power is supplied to prevent electric shock.
  2. Ensure power is disconnected before checking the unit internally.
  3. The symbol indicates double insulation or reinforced insulation (Class II of IEC 536).

WARNING!

This controller is an open-type temperature controller. Evaluate any dangerous application to prevent serious human injury or property damage.

  1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5. Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm², 12AWG to 24AWG. Tighten properly.
  2. Prevent dust or foreign objects from falling inside the controller.
  3. Never modify or disassemble the controller.
  4. Do not connect anything to "No used" terminals.
  5. Ensure all wires are connected to the correct polarity of terminals.
  6. Do not install or use in environments with: dust or corrosive gases/liquids, high humidity, high radiation, vibration/shock, high voltage/frequency.
  7. Turn power OFF when wiring or changing a temperature sensor.
  8. Use compensating wires matching thermocouple types when extending or connecting thermocouple wires.
  9. Use resistance wires when extending or connecting platinum resistance thermometer (RTD).
  10. Keep RTD wires short and route power wires away from load wires to prevent interference and noise.
  11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust, electric shock, or vibration.
  12. Ensure power cables and signal wires are properly installed before energizing the controller.
  13. Do not touch terminals or attempt to repair the controller when power is applied.
  14. Wait at least one minute after power disconnection for capacitors to discharge before touching internal circuits.
  15. Do not use acid or alkaline liquids for cleaning. Use a soft, dry cloth.
  16. This instrument has no power switch or fuse. Install protection close to the instrument if required. Recommended fuse rating: 250V, 1A (Time-lag fuse).
  17. Note: This controller does not provide overcurrent protection. Suitable overcurrent protection device(s) must be added (Rated 250V, 15 Amps max). A suitable disconnecting device should be provided near the controller.

Ordering Information

Series Panel Size (W x H) Output Selection Communication (Optional) Current Transformer (CT) Function (Optional)
DTA: Delta A Series Temperature Controller 4848: 1/16 DIN W48 x H48mm
4896: 1/8 DIN W48 x H96mm
7272: W72 x H72mm
R: Relay output, SPDT (SPST: 1/16 DIN size), 250VAC, 5A
V: Voltage Pulse output, 14V+10% ~ -20% (Max. 40mA)
C: Current output, 4 ~ 20mA
0: No interface
1: RS-485
None: No CT function
T: Current transformer is provided (only DTA7272 series support this function)

Display, LED & Pushbuttons

PV Display: Displays the process value or parameter type.

SV Display: Displays the set point, parameter operation read value, manipulated variable, or set value of the parameter.

AT: Flashes when Auto-tuning operation is ON.

OUT: Lights when the output is ON.

SET: Function key. Press to select desired function mode or confirm a setting value.

: Mode key. Press to set parameters within each function mode.

°C, °F: Temperature unit LEDs. °C LED lights for Celsius, °F LED lights for Fahrenheit.

: Up key. Press to increase values on SV display. Hold to speed up incremental action.

: Down key. Press to decrease values on SV display. Hold to speed up decrements.

ALM1 / ALM2: Alarm output LEDs. Lights when Alarm 1 or Alarm 2 output is ON.

Specifications

Parameters List

1. Operation Mode

LED Display Explanation Default
RUN/STOP Control setting begins. Run (RUN) or Stop (STOP) mode on the SV display. RUN
AL1H ALARM1 HIGH: Upper-limit alarm 1 4.0°C
AL1L ALARM1 LOW: Lower-limit alarm 1 4.0°C
AL2H ALARM2 HIGH: Upper-limit alarm 2 4.0°C
AL2L ALARM2 LOW: Lower-limit alarm 2 4.0°C
LOC Setting lock: Lock 1 (LOC 1), Lock 2 (LoC2) or OFF. Lock 1 locks all settings. Lock 2 locks settings other than SV value. When OFF, the lock function is disabled. Press SET and keys simultaneously to release lock. OFF
OUT Output value display and adjustment in manual tuning control. Not available in ON/OFF or Auto-tuning. 0
CT Displays current value measured by CT when control output is ON. Read only

2. Regulation Mode

LED Display Explanation Default
AT Auto-tuning setting. When AT key is set to ON (AT), PID auto-tuning starts automatically. (PID control) OFF
P Proportional Band (PID control) 47.6
I Integral Time (PID control) 260
d Derivative Time (PID control) 41
Pdof Offset output when P or PD control is ON. (PID control and Ki=0) 0
Iof Integral volume default value when PID control is ON and integral time constant is not zero. AT can automatically set this parameter. (PID control and Ki≠0) 0
HTS Set Heating hysteresis when ON/OFF control function is ON. 0
CTS Set Cooling hysteresis when ON/OFF control function is ON. 0
HTPD PID heating control cycle setting (PID control) Output Selection: V: 4 sec, R: 20 sec.
CLPD PID cooling control cycle setting (PID control) 0
TPOF Regulate temperature deviation value 0
CRHI Regulate 20mA output deviation value (1unit = 0.1mA) 0
CRLO Regulate 4mA output deviation value (1unit = 0.1mA) 0

3. Initial Setting Mode

LED Display Explanation Default
INPUT Select input temperature sensor type (Refer to "Temperature Sensor Type and Temperature Range"). Pt2
UNIT Temperature display unit, °C (C) and °F (F). °C
T-HIGH Upper limit for temperature range 500.0
T-LOW Lower limit for temperature range -20.0
CONTROL Control method setting: PID, ON/OFF, or manual tuning. PID
5-HC Select Heating (HEAT) or Cooling (Cool) action. HEAT
AL1 SET Alarm 1 setting. 0
AL2 SET Alarm 2 setting. 0
C-SL ASCII, RTU communication formats selection. ASCII
C-WE Write-in function disable/enable. OFF
C-NO Address setting. 1
BPS Baud rate setting. 9,600
LENGTH Data length setting. 7
PARITY Parity bit setting. E
STOP BIT Stop bit setting. 1

Note: Alarm values should be set in the initial setting mode so AL1H, AL1L, AL2H and AL2L display in operation mode.

Operation

There are three modes: operation, regulation, and initial setting. The controller starts in operation mode upon power application.

Press the key to switch to regulation mode. Pressing the key for more than 3 seconds switches to initial setting mode. Pressing the key in regulation or initial setting mode returns to operation mode.

PV/SV: Sets the temperature set point and displays the process value. Use the and keys to set the temperature set point.

Setting method: In any function mode, press the key to select the function, then use the and keys to change settings. Press to save changes.

The following flowchart illustrates switching between settings and internal functions:

Flowchart:

Switching for settings:

Heating and Cooling Control

Temperature control is achieved by heating or cooling. Heating starts when process temperature (PV) decreases, and cooling starts when PV increases. Both functions cannot operate simultaneously.

Temperature Sensor Type & Temperature Range

Input temperature sensor type Register value LED display Temperature range
Platinum resistance (Pt100) type 3 15 Pt3 0.0~100.0°C
Platinum resistance (Pt100) type 2 14 Pt2 -20.0~500.0°C
Platinum resistance (Pt100) type 1 13 Pt1 -200~600°C
Platinum resistance (JPt100) type 2 12 JPE2 0.0~100.0°C
Platinum resistance (JPt100) type 1 11 JPE1 -20.0~400.0°C
Copper resistor (Cu50) type2 20 CU2 -50.0~150.0°C
Copper resistor (Cu50) type1 19 CU1 -50~150°C
Thermocouple (TC) B type 10 B 100 ~ 1,800°C
Thermocouple (TC) S type 9 S 0~1,700°C
Thermocouple (TC) R type 8 R 0~1,700°C
Thermocouple (TC) N type 7 N -200 ~ 1,300°C
Thermocouple (TC) E type 6 E 0~600°C
Thermocouple (TC) T type 2 5 T2 -20.0~400.0°C
Thermocouple (TC) T type 1 4 T1 -200~400 °C
Thermocouple (TC) J type 2 3 J2 -20.0~400.0°C
Thermocouple (TC) J type 1 2 J1 -100~850°C
Thermocouple (TC) K type 2 1 K2 -20.0~500.0°C
Thermocouple (TC) K type 1 0 K1 -200~1300°C
Thermocouple (TC) L type 16 L -200~850 C
Thermocouple (TC) U type 17 U -200~500°C
Thermocouple (TC) Txk type 18 Txk -200 ~ 800°C

Input Error Indication

Set value Explanation
PV Temperature sensor not connected no
Cont
Unknown input
SV Measured temperature value exceeds temperature range ouEr Err

Alarm Outputs

Two groups of alarm outputs with 13 alarm types. Alarm output activates when PV is higher or lower than the alarm limit set point.

Set value Alarm type Alarm output operation
0 Alarm function disabled Output OFF
1 Deviation upper- and lower-limit:
PV value higher than SV + (AL-H) or lower than SV - (AL-L).
ON/OFF
2 Deviation upper-limit:
PV value higher than SV + (AL-H).
ON/OFF
3 Deviation lower-limit:
PV value lower than SV - (AL-L).
ON/OFF
4 Reverse deviation upper- and lower-limit:
PV value in the range of SV + (AL-H) and SV - (AL-L).
ON/OFF
5 Absolute value upper- and lower-limit:
PV value higher than AL-H or lower than AL-L.
ON/OFF
6 Absolute value upper-limit:
PV value higher than AL-H.
ON/OFF
7 Absolute value lower-limit:
PV value lower than AL-L.
ON/OFF
8 Deviation upper- and lower-limit with standby sequence:
PV reaches SV, and value is higher than SV + (AL-H) or lower than SV - (AL-L).
ON/OFF
9 Deviation upper-limit with standby sequence:
PV reaches SV, and value is higher than SV + (AL-H).
ON/OFF
10 Deviation lower-limit with standby sequence:
PV reaches SV, and value is lower than SV - (AL-L).
ON/OFF
11 Hysteresis upper limit alarm:
PV value higher than SV + (AL-H). OFF when PV value is lower than SV + (AL-L).
ON/OFF
12 Hysteresis lower limit alarm:
PV value lower than SV - (AL-H). OFF when PV value is higher than SV - (AL-L).
ON/OFF
13 CT alarm output:
Current measured by CT is lower than AL-L or higher than AL-H. (Available only for controllers with CT)
ON/OFF

Note: AL-H and AL-L include AL1H, AL2H, AL1L, AL2L. With standby sequence: alarm output temporarily disabled until PV reaches the set value.

Current Transformer (CT) Function

The CT function is used with alarm output. When using a CT, change alarm output mode to 13. Set current lower-limit and upper-limit between 0.5A ~ 30A. Display resolution is 0.1A, accuracy is +/- 0.5A.

Communication Parameters List

Controller offers RS-485 port for serial communication.

Address Content Explanation
4700H (R) Process value (PV) Measuring unit is 0.1, updated every 0.5 second.
4701H Set point (SV) Unit: 0.1 (°C or °F)
4702H Upper-limit alarm 1
4703H Lower-limit alarm 1
4704H Upper-limit alarm 2
4705H Lower-limit alarm 2
4706H Upper-limit of temperature range Data content should not be higher than the temperature range.
4707H Lower-limit of temperature range Data content should not be lower than the temperature range.
4708H PB Proportional band 0.1~999.9, Unit: 0.1
4709H Ti Integral time 0~9,999
470AH Td Derivative time 0~9,999
470BH Heating/Cooling hysteresis 0~9,999
470CH Regulate 20mA current output deviation -100~54 (1 unit = 0.1mA)
470DH Regulate 4mA current output deviation -39~100 (1 unit = 0.1mA)
470EH Default value of integral volume 0~100%
4710H Input temperature sensor type Refer to "Temperature Sensor Type and Temperature Range".
4711H Control method 0: PID (default), 1: ON/OFF, 2: manual tuning
4712H Heating/Cooling control cycle 1~99 second
4713H Heating/Cooling control Selection Heating: 0 (default), Cooling: 1
4714H Temperature regulation value 0%~100%
4715H Control Run/Stop setting Run: 1 (default), Stop: 0
4716H Alarm 1 type Refer to "Alarm Outputs".
4717H Alarm 2 type Refer to "Alarm Outputs".
4718H Temperature unit display selection °C: 1 (default), °F : 0
4719H Communication write-in selection Disabled: 0 (default), Enabled: 1
471AH Software version V1.00 indicates 0 x 100
471BH Read LED status b2: °F, b3: °C, b4: AL2, b5: AL1, b6: OUT, b7: AT
471CH Read KEY status b0: SET, b1: Select, b2: Up, b3: Down
471DH Read output amount Unit: %
4729H AT Setting OFF: 0 (default), ON:1
472AH Write output amount Available on "manual control" only.
472BH (R) Code 0
Code 1
Code 2
Code 3
Code 4
Code 5
Code 6
Code 7
Normal operation (No error)
Initial process
Initial status (Temperature is not stable)
Temperature sensor is not connected
Temperature sensor input error
Measured temperature value exceeds the temperature range
No Int. error
EEPROM Error
4731H Read / Write lock status 0: No Lock, 1: Lock1, 11: Lock2, 21: Lock3
4732H Event input switch 0: Event disable, 1: SV switch, 2: Run/Stop
4733H CT monitor value Unit is 0.1A

Note: R refers to "read only" value.

Default Communication Response Setting

Write hex value 1234 into register at 471BH and 1234 again into register at 4724H. Re-power DTA to complete the default setting.

Communication Protocol

Command code to read N words: 03H. Maximum N is 3.

Example for reading two words from controller 01 (address 01H) at starting data address 4700H in ASCII mode:

Command message: STX, ADR1='0', ADR0='1', CMD1='0', CMD0='3', Number of data (count by byte)='04', Starting data address='0', '0', '47', '00', 'H', Number of data (counted by word)='02', LRC CHK 1='B', LRC CHK 0='3', END 1=CR, END 0=LF

Response message: STX, ADR1='0', ADR0='1', CMD1='0', CMD0='3', Number of data='04', Content of start address 4700H='0', '1', Content of start address 4701H='0', '9', LRC CHK 1='6', LRC CHK 0='7', END 1=CR, END 0=LF

LRC check: LRC check is the added sum from "Address" to "Data content". Example: 01H + 03H + 47H + 00H + 00H + 02H = 4DH, then take the complementary of 2, B3H.

Command code to write 1 word: 06H

Example for writing 1000 (03E8H) in controller 01 (comm. address 01H) at starting data address 4701H in ASCII mode:

Command message: STX, ADR1='0', ADR0='1', CMD1='0', CMD0='6', Number of data='04', Starting data address='0', '7', '0', '1', 'H', Data content='0', '3', 'E', '8', LRC CHK 1='C', LRC CHK 0='6', END 1=CR, END 0=LF

Response message: STX, ADR1='0', ADR0='1', CMD1='0', CMD0='6', Number of data='04', Starting data address='0', '7', '0', '1', 'H', Data content='0', '3', 'E', '8', LRC CHK 1='C', LRC CHK 0='6', END 1=CR, END 0=LF

Terminal Identification

Diagrams showing terminal identification for DTA4848, DTA7272, and DTA4896/DTA9648/DTA9696 models.

Mounting

Step 1: Insert the controller through the panel cutout.

Step 2: Insert the mounting bracket into the mounting groove at the top and bottom of the controller and push until the bracket stops at the panel wall.

Step 3: Insert and tighten screws on the bracket to secure the controller. (Torque: 0.8kgf-cm to 1.5kgf-cm)

Mounting Bracket Installation: Diagrams illustrating bracket installation.

Panel Cutout & External Dimensions

Panel wall thickness: 1mm to 8mm.

Clearance: Provide at least 90 mm clearance around the controller for proper ventilation. (Dimensions are in millimeters and inches).

Diagrams showing panel cutouts and external dimensions for DTA4848, DTA4896, DTA9648, and DTA7272 models.

CT Wiring Method (if CT function is selected)

Diagram showing CT wiring method.

Models: DTA7272 A Series Temperature Controller, DTA7272, A Series Temperature Controller, Temperature Controller, Controller

File Info : application/pdf, 12 Pages, 943.10KB

PDF preview unavailable. Download the PDF instead.

DELTA IA-TC DTA OM EN 20130327 Acrobat Distiller 7.0 (Windows) CASPER.SHIH

Related Documents

Preview DELTA DTK Series Temperature Controller Instruction Sheet
Instruction sheet for the DELTA DTK Series Temperature Controller, detailing its features, specifications, operation modes, and installation.
Preview Delta DTC Series Digital Controller Instruction Sheet
Instruction sheet for the Delta DTC Series Digital Controller, covering installation, specifications, functions, and operation. Includes details on input sensors, output types, alarm modes, communication protocols (RS-485), password protection, and programming.
Preview DELTA DT3 Series Temperature Controller Operation Manual
Comprehensive operation manual for the DELTA DT3 Series Temperature Controllers, covering features, specifications, operation modes, wiring diagrams, and installation.
Preview Delta Temperature Controller User Manual
This user manual provides a comprehensive guide to the Delta DT series temperature controllers, detailing their default settings, various control modes (ON/OFF, MANUAL, PID, PID PROG), and operational procedures. It is designed for beginners to easily set up parameters and understand the functionality of these devices.
Preview Mitsubishi FX3U PLC to DELTA DOP Series HMI Connection Guide
Detailed connection guide for integrating Mitsubishi FX3U PLCs with DELTA DOP Series HMIs, covering RS-422, RS-232, and RS-485 interfaces. Includes PLC address definitions for registers and contacts.
Preview 台達 NC300 系列 CNC 控制器快速入門指南
本指南提供台達 NC300 系列 CNC 控制器(包括 NC300A-MI-A、NC300A-MS-A、NC311A-MS-A、NC310A-MS-A、NC200A-MI-A 等型號)的安裝、操作與安全重要資訊,旨在協助使用者正確使用。
Preview Delta DVP04PT-S and DVP06PT-S Temperature Measurement Module Instruction Sheet
This document provides detailed instructions for the Delta DVP04PT-S and DVP06PT-S temperature measurement modules, covering installation, wiring, electrical and functional specifications, and control register details.
Preview DVP04PT-S DVP06PT-S Temperature Measurement Module Instruction Sheet
Instruction sheet for Delta DVP04PT-S and DVP06PT-S temperature measurement modules. Details installation, specifications, wiring, and control registers for these RTD input modules.