Delta DTC Series Digital Controller Instruction Sheet

Thank you for purchasing the DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure proper operation, and keep this instruction sheet handy for quick reference.

! Caution

DANGER! Caution! Electric Shock!

The DTC series is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock, and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g., key or specific tools are required to open the enclosure) in case danger and damage to the device may occur.

! WARNING!

  1. Prevent dust or metallic debris from falling into the controller that will cause malfunction. DO NOT modify or disassemble the controller. DO NOT use extra terminals.
  2. Do not install and/or use the controller in places subject to: (a) dust or corrosive gases and liquid; (b) high humidity and high radiation; (c) vibration and shock.
  3. Switch off the power when wiring or changing input sensors.
  4. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
  5. Shorten the wire when wiring a platinum resistance thermometer (RTD) to the controller, and separate the power cable from load wires to prevent interference and conductive influence.
  6. Make sure the power cable and signals device are installed correctly before switching on the power of DTC; otherwise, serious damage may occur.
  7. DO NOT touch the terminals or repair the controller when the power is on to prevent electric shock.
  8. Wait at least one minute after the power is off to allow the capacitor to discharge. DO NOT touch any internal circuit within this period.
  9. DO NOT touch the internal terminals no matter the power is on or off.
  10. DO NOT place other heating source (e.g., power supply) in parallel with DTC during the installation. Please keep proper space in between.

Model Name Explanation

Series name DTC: Delta C series temperature controller
1 Controller position 1: First controller 2: Controller connected in parallel
2 Auxiliary output groups 0: standard, 2 outputs, no auxiliary output
1: 1 auxiliary output. Not available now.
2: 2 auxiliary outputs. Not available now
3 4 Optional 00: Standard
01: CT input
02: EVENT input. Not available now
5 Main output type R: Relay output SPST, 250VAC, 3A
V: Voltage pulse output 12V +10% ~ -20%
C: Current output 4 ~ 20mA
L: Linear voltage output 0~10V

(DTC1000/2000 model): DC24V input, 2 outputs, relay output for output 2, RS-485 communication.

(DTC1001/2001 model): DC24V input, 1 output, 1 CT input, and RS-485 communication.

Function & Specification

Power supply
DC24V. Isolated switching power
Voltage range
Rated voltage: 90% ~ 110%
Power consumption
Rated 24 VDC, Max. 24 W combined, 3W + 3W x number of DTC2000 controllers (Max. 7)

Input sensors
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum RTD: Pt100, JPt100
Linear DC input: 0~5V, 0~10V, 0~20mA, 4~20mA, 0 ~ 50mV
Sampling rate
Analog input: 0.15 sec. Thermocouple or platinum RTD: 0.4 sec.
Control method
PID, programmable PID, Manual, ON/OFF
Output types
Relay: SPST, Max. load 250VAC, 3A resistive load
Voltage pulse: 12VDC, Max. output current: 40mA
Current: DC 4~20mA (Load resistance: < 500Ω)
Analog voltage: 0~10V (Load resistance: > 1,000Ω)
Output function
Control output, alarm output, proportional output
Proportional output is available only when output 1 is linear voltage/current output.
Alarm
13 alarm modes
Communication
RS-485 digital communication, 2,400bps ~ 38,400bps
Communication protocol
Modbus protocol, ASCII/RTU format
Internal connection
Internal terminals available to transmit 24V power supply and communication signals
Vibration resistance
10 ~ 55Hz, 10m/s² for 10mins, each in X, Y and Z direction
Shock resistance
Max. 300m/s², 3 times in each 3 axes, 6 directions
Ambient temperature
0 ~ 50°C
Storage temperature
-20 ~ +65°C
Altitude
< 2,000m
Ambient humidity
35% ~ 85% RH (non-condensing)
Pollution degree
2

Product Profile & Outline

DTC1000/1001 R/V/C/L

DTC2000/2001 R/V/C/L

Input

DTC series supports the following input sensors:

Input Sensor Register Value Available Range
0~50mV linear voltage input 17 0~50mV
4~20mA linear current input 16 4~20mA
0~20mA linear current input 15 0~20mA
0~10V linear voltage input 14 0~10V
0~5V linear voltage input 13 0~5V
Platinum RTD (Pt100) 12 -200 ~ 600°C (-328 ~ 1,112°F)
Platinum RTD (JPt100) 11 -20 ~ 400°C (-4 ~ 752°F)
Thermocouple TXK type 10 -200 ~ 800°C (-328 ~ 1,472°F)
Thermocouple U type 9 -200 ~ 500 °C (-328 ~ 932°F)
Thermocouple L type 8 -200 ~ 850°C (-328 ~ 1562°F)
Thermocouple B type 7 100 ~ 1,800°C (212 ~ 3,272°F)
Thermocouple S type 6 0~1,700°C (32 ~ 3,092°F)
Thermocouple R type 5 0~1,700°C (32 ~ 3,092°F)
Thermocouple N type 4 -200 ~ 1,300°C (-328 ~ 2,372°F)
Thermocouple E type 3 0~600°C (32~1,112°F)
Thermocouple T type 2 -200 ~ 400°C (-328 ~ 752°F)
Thermocouple J type 1 -100 ~ 1,200°C (-148 ~ 2,192°F)
Thermocouple K type 0 -200 ~ 1,300°C (-328 ~ 2,372°F)

Note 1: The current input is built-in with 2490 precision resistor. See "How To Set up Current Input" section.

Note 2: Default setting: Pt100 input.

The range of linear input and feedback value is adjustable. Range of input feedback: -999~9,999. Take 0 ~ 20mA input as example, -999 refers to 0mA input, and 9,999 refers to 20mA input. If we change the range to 0 ~ 2,000, 0 will refer to 0mA input, and 2,000 will refer to 20mA input. 1 display scale = 0.01mA.

Output

There are several output types available from DTC series: Control Output (heating/cooling), Alarm Output and Proportional Output.

Control Output

DTC series offers 2 outputs for heating or cooling control. If you require dual loop output, the 2 outputs should be set to different actions (heating or cooling). If you require the 2 outputs are set to the same control action, only the control cycle of output 1 will be valid, and the 2 outputs will act at the same time.

The control methods include: PID control, ON/OFF control, Manual control and programmable PID control.

Single Output Control:

Figure 1: ON/OFF Control

Figure 2: PID Control, Cooling) Control

Figure 3: PID Control, Heating Control

Dual Output Control:

Figure 4: ON/OFF Control

Figure 5: PID control

Figure 6: PID Control

Programmable PID Control & Parameters Setting

The programmable PID control includes 8 patterns (Pattern 0 ~ 7). Each pattern contains 8 steps (Step 0~7) and parameters: "link pattern", "cycle" and "the number of steps".

Start Pattern:

The user can set up which pattern is the start pattern for the programmable control.

Steps:

Includes the settings of the two parameters, set point X and execution time T, indicating that the set point (SV) has to rise to temperature X after the period of execution time T. If the result of the set point X is the same as that of the previous setting, the process is called "Soak"; otherwise, it is called "Ramp". Therefore, the programmable control is also known as Ramp/Soak control. The default setting of the first step is Soak control. The temperature will first rise to the set point X and remain at X. The total execution time is T.

Link Pattern:

The pattern to be executed following the current pattern. If the setting is not 0 ~ 7, the set point will remain at the last pattern.

Cycle:

The additional number of cycles for a pattern. For example, if the parameter is set to 2, it refers to the pattern has to execute additional twice, totaling the execution to 3 times including the original one.

The Number of Steps:

The number of steps in each pattern (range: 0~7). For example, if the parameter is set to 2, it refers to the pattern will execute Step 0 ~ Step 2, and other steps will not be executed.

The Execution:

Available settings include "run", "program hold", "program stop" or "stop".

  1. When this parameter is set to "run", the program will start its execution from step 0 of the start pattern.
  2. When this parameter is set to "program hold", the program will stop and the temperature will stop at the SV before the program stops. If the user sets to "run" again, the program will resume the step before the program stops and execute by the remaining time.
  3. When this parameter is set to "program stop", the program will stop and the temperature will stop at the SV before the program stops. If the user sets to "run" again, the program will execute again from Step 0 of the start pattern.
  4. When this parameter is set to "stop", the program will stop, and the control output will be disabled.

Proportional Output:

If Output 1 of this DTC series is linear voltage or current, the user can set it to "Proportional Output". Proportional output refers to the output varies with the input. For example, if the input range is set to 0 ~ 1,000, and when the input value is 0, the output will be 0mA or 0V. When the input value is 1,000, the output will be 20mA or 10V.

Figure 7: Proportional Output

Alarm Output

DTC series offers 13 alarm modes. When the PV exceeds or falls below SV, the alarm output will be enabled. See the table below for the 13 modes.

Mode Alarm Type Alarm Output Operation
0 No alarm OFF
1 Alarm output will be enabled when the temperature reaches upper and lower limits.
• Alarm will be enabled when the PV exceeds SV + AL-H or falls below SV – AL-L.
ON
OFF
AL-L SV AL-H
2 Alarm output will be enabled when the temperature reaches the upper limit.
• Alarm will be enabled when the PV exceeds SV + AL-H.
ON
OFF
SV AL-H
3 Alarm output will be enabled when the temperature reaches the lower limit.
• Alarm will be enabled when the PV falls below SV - AL-L.
ON
OFF
AL-L SV
4 • Alarm will be enabled when the PV is between SV + AL-L and SV - AL-L. ON
OFF
AL-L SV AL-H
5 Alarm output will be enabled when the temperature reaches the absolute value of the upper and lower limits.
• Alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
ON
OFF
AL-L AL-H
6 Alarm output will be enabled when the temperature reaches the absolute value of the upper limit.
• Alarm will be enabled when the PV exceeds AL-H.
ON
OFF
AL-H
7 Alarm output will be enabled when the temperature reaches the absolute value of the lower limit.
• Alarm will be enabled when the PV falls below AL-L.
ON
OFF
AL-L
8 Standby upper/lower limit alarm
• Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H or falls below SV - AL-L.
ON
OFF
AL-L SV AL-H
9 Upper limit standby alarm
• Alarm will be enabled when the PV reaches SV and exceeds SV + AL-H.
ON
OFF
SV AL-H
10 Lower limit standby alarm
• Alarm will be enabled when the PV reaches SV and falls below SV - AL-L
ON
OFF
AL-L SV
11 Upper limit hysteresis alarm
• Alarm will be enabled when the PV exceeds SV + AL-H and disabled when the PV falls below SV + AL-L.
ON
OFF
AL-L AL-H
12 Lower limit hysteresis alarm
• Alarm will be enabled when the PV falls below SV – AL-H and disabled when the PV exceeds SV - AL-L.
ON
OFF
AL-H AL-L
13 CT alarm output:
• This alarm operates when the current measured by transformer (CT) is lower than AL-L or higher than AL-H
ON
OFF
AL-L AL-H

Note: AL-H and AL-L include AL1H, AL2H, AL1L and AL2L. When Output 1 is set to Alarm Output, use AL1H (1024H) and AL1L (1025H). When Output 2 is set to Alarm Output, use AL2H (1026H) and AL2L (1027H).

CT Function

  1. When CT is adopted, the communication address 106AH of the alarm output should be set to 02H only.
  2. When CT is adopted, the alarm mode should be set to 13 and the communication address 1021H to 0DH only.
  3. The user can adjust the upper limit and lower limit of CT Alarm. If the current detected by CT exceeds the upper/lower limit, ALM 2 will be set to "1".

1039H: Status of CT Alarm

1026H: Upper limit of CT Alarm (unit: 0.1A) Max. setting: 40.0A; Default setting: 100 (10.0A)

1027H: Lower limit of CT Alarm (unit: 0.1A) Min. setting: 0; Default setting: 5 (0.5A)

102BH: Current detected by CT (unit: 0.1A)

CT only measures current when there is control output; otherwise only the previous CT value will be displayed.

LED Display

  1. When power is normal, POWER LED will be on.
  2. After DTC is switched on, all LED will be on. The communication protocol will be displayed in 1 second, followed by the communication address in the next second.
  3. RUN LED is on when the control is executing.
  4. ERROR LED is on when errors occur in input, memory or communication.
  5. When an output is executing, its corresponding output LED will be on.
  6. AT LED flashes when PID parameters are being auto-tuned.
  7. RX LED flashes when DTC receives communication signals. TX LED flashes when DTC sends out communication signals.

Communication protocol displayed on LED after the power of DTC is switched on:

AT TX RX Err Run
000: 2,400bps
011: 19,200bps
001: 4,800bps
100: 38,400bps
010: 9,600bps
Parity 00: None
10: Odd
01: Even
0: ASCII
1: RTU
0: 2 Stop bits
1: 1 Stop bit

Communication address display: AT (bit 6) and Run (bit 0) are combined to binary code.

Password Function

The default setting of the password is disabled. To enable the password function, enter the 4-character password in the specific communication address. The password is protected by 3 levels.

  1. Level 1: Only LED status, SV and PV can be read. No settings can be modified.
  2. Level 2: Only LED status, SV and PV can be read. Only SV can be modified.
  3. Level 3: All SV can be read. Only SV and auto-tuning can be modified.
  4. Level 4: No password protection.

When a password is set (in 106EH ~ 1070H), the protection will enter Level 1. To enter other levels, enter the corresponding password (in 106BH ~ 106DH). After DTC is switched off, the protection will return to Level 1. To unlock the password protection, the user has to remove all the passwords (in 106EH ~ 1070H).

The password protection level can be read in 106EH ~ 1070H:

bit Status bit Status bit Status bit Status bit Status bit Status
b0 Level 1 b1 Level 2 b2 Level 3 b3 Level 1 locked b4 Level 2 locked b5 Level 3 locked

bit = 0 refers to no password is set. bit = 1 refers to the password has been set (b0 ~ b2). b3 ~ b6 display the current level status.

Synchronous Communication Protocol & Auto ID Setup

This function allows the user to set the communication protocol of DTC2000/2001 to the same protocol as set in the first DTC1000/1001. The station IDs of DTC are arranged in decreasing order. Follow the steps below.

  1. Set the auto communication ID of DTC1000/1001 to "1" (communication address: 1022H).
  2. Switch off DTC1000/1001 before connecting it to DTC2000/2001. Switch it on again.
  3. Default communication protocol: 9,600bps, 7 bits, Even, 1 stop bit, communication address 01.
  4. This function will consume 3 ~ 5 seconds more when you switch on your DTC.

RS-485 Communication

  1. Supports transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps;
  2. Does not support 7, N, 1/8, E, 2 / 8, O, 2 communication format;
  3. Communication protocol: Modbus ASCII/RTU;
  4. Function code: 03H (read Max. 8 words in register), 06H (write 1 word into register), 01H (read Max. 16 bits of data), 05H (write 1 bit into register).
Address Setting Content Explanation
1000H Present temperature value (PV) Unit: 0.1 degree. Analog input: 1EU.
The read values below indicate the occurrence of errors:
8002H: Temperature not acquired yet
8003H: Temperature sensor not connected
8004H: Incorrect sensor type
8006H: Unable to acquire temperature, ADC input error
8007H: Unable to read/write the memory
1001H Set point (SV) Unit: 0.1 degree. Analog input: 1EU.
1002H Upper-limit of temperature range The content shall not be bigger than the range. Unit: 0.1°
1003H Lower-limit of temperature range The content shall not be smaller than the range. Unit: 0.1°
1004H Input sensor type See the table in "Input" section.
1005H Control method 0: PID, 1: ON/OFF, 2: Manual, 3: programmable PID
1006H Control method for Output 1 0: Heating (default); 1: Cooling; 2: Alarm; 3: Proportional (required analog output)
1007H Control cycle of Output 1 0~99, 0: 0.5sec
1008H Control cycle of Output 2 0~99, 0: 0.5sec (Invalid when the 2 outputs are the same control.) (DTC1000/2000 model)
1009H Proportional band value 1~9,999, Unit: 0.1°. Analog input: 1EU
100AH Ti value 0~9,999
100BH Td value 0~9,999
100CH Default integration value 0~1,000, Unit: 0.1%
100DH Offset compensation value for proportional control (when Ti=0)) 0~1,000, Unit: 0.1%
100EH COEF setting when in dual control output 1~9,999, Unit: 0.01 (1000/2000 model)
100FH Deadband setting when in dual control output -999~9,999, Unit: 0.1° or 1EU (1000/2000 model)
1010H Hysteresis of Output 1 0~9,999, Unit: 0.1° or 1EU
1011H Hysteresis of Output 2 0~9,999, Unit: 0.1° or 1EU (1000/2000 model)
1012H Read/write output percentage of Output 1 Unit: 0.1%. "Write" is only applicable in manual mode.
1013H Read/write output percentage of Output 2 Unit: 0.1%. "Write" is only applicable in manual mode. (1000/2000 model)
1014H Upper-limit regulation for analog linear output 1 scale = 2.8μΑ = 1.3mV
1015H Lower-limit regulation for analog linear output 1 scale = 2.8μΑ = 1.3mV
1016H Temperature offset regulation value -999~ +999, Unit: 0.1° or 1EU
1020H Output mode for Alarm 1 See "Alarm Output" section.
1021H Output mode for Alarm 2 See "Alarm Output" section.
1022H Communication flag auto-set 0: Communication banned, 1: Communication auto-set
1023H Control method for Output 2 0: Heating (default); 1: Cooling; 2: Alarm (DTC1000/2000 model)
1024H Upper limit for Alarm 1 See "Alarm Output" section.
1025H Lower limit for Alarm 1 See "Alarm Output" section.
1026H Upper limit for Alarm 2 See "Alarm Output" section. (DTC1000/2000 model)
1027H Lower limit for Alarm 2 See "Alarm Output" section. (DTC1000/2000 model)
1028H Upper limit for CT Alarm CT Alarm lower limit ~ 400, 1 scale = 0.1A (DTC1001/2001 model)
1029H Lower limit for CT Alarm 0~ CT Alarm upper limit, 1 scale = 0.1A (DTC1001/2001 model)
102AH Read/write status b1: ALM2, b2: °C, b3: °F, b4: ALM1, b5: 02, b6:01, b7: AT
102BH Read current detected by CT Unit = 0.1A (DTC1001/2001 model)
102CH Positive/negative proportional output 0: positive, 1: negative
102EH LED status b0: RUN, b1: ERR, b2: O2, b3: 01, b4: RX, b5:TX b6: AT
102FH Software version V1.00 is indicated as 0x100
1030H No. of start pattern 0~7
1032H Remaining time of the executed step Unit: second
1033H Remaining time of the executed step Unit: minute
1034H No. of currently executed step 0~7
1035H No. of currently executed pattern 0~7
1036H Read dynamic value in programmable control 0~100% upper limit of analog output, Unit: 0.1%
1037H Upper limit of proportional output 0~100% upper limit of analog output, Unit: 0.1%
1038H Lower limit of proportional output 0~100% lower limit of analog output, Unit: 0.1%
1039H CT Alarm status 0: Disabled, 1: Enabled (DTC1001/2001 model)
1040H~1047H Number of steps in a pattern 0~7 = N refers to the pattern will be executed from Step 0 to Step N.
1050H~1057H Additional number of cycles for a pattern 0~199 refers to the pattern will be executed for 1 ~ 200 times.
1060H~1067H No. of the link pattern for the current pattern 0~8, 8 refers to end of the program. 0~ 7 refers to the next pattern No. following the current pattern.
1068H Run/Stop setting 0: Stop, 1: Run, 2: Program end, 3: Program hold
1069H Control selection of Output 1 0: Heating, 1: Cooling, 2: Alarm, 3: Proportional output
106AH Control selection of Output 2 0: Heating, 1: Cooling, 2: Alarm (1000/2000 model)
106BH Unlock Level 1 password protection. Read/write allowed Shall be the same as Level 1 password (106E)
106CH Unlock Level 2 password protection. Use Level 3. Shall be the same as Level 2 password (106F)
106DH Unlock Level 3 password protection. Use Level 2 Shall be the same as Level 3 password (1070)
106EH Unlock Level 1 password protection/Set up password Unlock password before setting it up.
106FH Unlock Level 2 password protection/Set up password Unlock password before setting it up.
1070H Unlock Level 3 password protection/Set up password Unlock password before setting it up.
1071H Read/write communication address 1~247
1072H Read/write communication format 1: RTU, 0: ASCII
1073H Read/write communication speed 0~4: 2,400 ~ 38,400
1074H Read/write communication data length 0: 8 bits, 1: 7 bits
1075H Read/write parity bit 0: None, 1: Even, 2: Odd
1076H Read/write stop bit 0: 2 stop bits, 1: 1 stop bit
2000H~203FH SV temperature for Pattern 0~7. SV for Pattern 0 is set in 2000H ~ 2007H Unit: 0.1°
2080H~20BFH Execution time for Pattern 0~7. Time for Pattern 0 is set in 2080H ~ 2087H 0~900 (1 scale = 1 minute)

5. Address and content of the bit register (read bits are stored starting from LSB, and written data is FF00H, set the bit as 1. 0000H sets the bits data to "0").

Unit Content Explanation
0811H Temperature unit display 0:°F, 1: °C (Default)
0813H Read/write auto-tuning status 0: End (Default), 1: Start
0814H Run/Stop setting 0: Stop, 1: Run (Default)
0815H Program hold flag 1: Program hold
0816H Program stop flag 1: Program stop

6. Communication format: Command 01: read bit, 05: write bit, 03: read word, 06: write word.

ASCII Mode

Read Command Read Response Message Write Command Write Response Message
Start word ':' Start word ':' Start word ':' Start word ':'
Machine address 1 '0' '0' Machine address 1 '0' '0' Machine address 1 '0' '0' Machine address 1 '0' '0'
Machine address 0 '1' '1' Machine address 0 '1' '1' Machine address 0 '1' '1' Machine address 0 '1' '1'
Command 1 '0' '0' Command 1 '0' '0' Command 1 '0' '0' Command 1 '0' '0'
Command 0 '3' '1' Command 0 '3' '1' Command 0 '6' '5' Command 0 '6' '5'
Read Command Read Response Message Write Command Write Response Message
Read staring address '0' '8' Length of response data (byte) '0' '0' '4' '2' Write data address '0' '8' '0' '8' Write data address '0' '8' '0' '8'
Read length of data/bit (word/bit) '0' '0' '0' '1' Data content in 1000H/081xH 'F' '0' 'F' '0' To write data content '3' 'F' '3' 'F' Write data content 'E' '0' 'E' '0'
LRC1 check 'E' 'D' Data content in 1001H '0' '8' '0' '8' LRC1 'F' 'E' LRC1 'F' 'E'
LRCO check 'A' 'D' LRCO check '0' 'D' '3' LRCO 'D' '3' LRCO 'D' '3'
End word 1 CR CR LRC1 check '0' 'E' End word 1 CR CR End word 1 CR CR
End word 0 LF LF End word 0 LF LF End word 0 LF LF End word 0 LF LF

LRC Check

LRC check sums up from "machine address" to "data content", e.g. 01H + 03H + 10H+ 00H + 00H + 02H = 16H. Obtain 2's complement EA.

RTU Mode

Read Command Read Response Message Write Command Write Response Message
Machine address 01H 01H Machine address 01H 01H Machine address 01H 01H Machine address 01H 01H
Command 03H 01H Command 03H 01H Command 06H 05H Command 06H 05H
Read start address 10H 08H Length of response data (byte) 04H 02H Write data address 10H 08H Write data address 00H 10H
Read length of data (bit/word) 00H 00H Data content 1 01H 17H Write data content 03H FFH Write data content 20H 00H
CRC low byte COH BBH CRC high byte CBH A9H CRC low byte DDH 8FH CRC high byte E2H 9FH

CRC Program Example

unsigned int reg_crc = 0xffff; i = 0;
while (length--)
{
i ++;
reg_crc ^= RTUData[i];
for (j = 0; j < 8; j++)
if (reg_crc & 0x01) reg_crc = (reg_crc >> 1) ^ 0xA001;
else reg_crc = reg_crc >> 1;
}
return(reg_crc);

Installation

How to connect maximum 8 DTC1000/2000 controllers by using DIN rail.

How to Set Up Current Input

For general input

For current input (4~20mA, 0~20mA)

PDF preview unavailable. Download the PDF instead.

Delta-DTC-User-Manual Acrobat Distiller 9.0.0 (Windows)

Related Documents

Preview Delta Temperature Controller User Manual
This user manual provides a comprehensive guide to the Delta DT series temperature controllers, detailing their default settings, various control modes (ON/OFF, MANUAL, PID, PID PROG), and operational procedures. It is designed for beginners to easily set up parameters and understand the functionality of these devices.
Preview DELTA DTK Series Temperature Controller Instruction Sheet
Instruction sheet for the DELTA DTK Series Temperature Controller, detailing its features, specifications, operation modes, and installation.
Preview DELTA A Series Temperature Controller Instruction Sheet
Instruction sheet for the DELTA A Series Temperature Controller, providing details on precautions, ordering information, specifications, parameters, operation, and communication protocols.
Preview DELTA DT3 Series Temperature Controller Operation Manual
Comprehensive operation manual for the DELTA DT3 Series Temperature Controllers, covering features, specifications, operation modes, wiring diagrams, and installation.
Preview Delta DVP-SX2 PLC: Instruction Sheet, Specifications, and Installation Guide
Comprehensive guide for the Delta DVP-SX2 Programmable Logic Controller (PLC). Covers product features, electrical specifications, A/D D/A specs, I/O configuration, installation, and safety for models DVP20SX211R, DVP20SX211T, DVP20SX211S.
Preview Delta DVP-SV2 Instruction Sheet
This document provides detailed instructions and specifications for the Delta DVP-SV2 PLC, covering installation, wiring, electrical specifications, and operational guidelines. It is designed for industrial automation applications.
Preview Delta DVP Series Programmable Logic Controllers (PLCs) - Product Catalog
Explore the Delta DVP Series Programmable Logic Controllers (PLCs), a comprehensive range of industrial automation solutions offering high performance, diverse models, and advanced motion control capabilities. This catalog details specifications, features, and ordering information for various DVP PLC series.
Preview Delta DVP-SE Series PLC Instruction Sheet
This document provides detailed instructions and specifications for the Delta DVP-SE series of Programmable Logic Controllers (PLCs), covering electrical specifications, installation, wiring, and communication settings.