Raychem SBS-xx-SNR Control Cabinet for Sprinkler System Frost Protection

Description

[Image Description: A white, rectangular electrical control cabinet with a grey door. The Raychem logo is visible in the upper right corner. The door has several indicator lights, switches, and labels. It appears to be a robust industrial unit.]

The Raychem SBS-xx-SNR control cabinet is an integrated complete solution for controlling self-regulating Raychem heating cables for frost protection of pipelines in sprinkler systems. In accordance with the requirements of BS EN 12845:2008, it features a multi-regulator/multi-sensor thermostat control with automatic switching functionality to a redundant heating circuit.

Models in this series control 2-12 heating circuits of frost protection heating cables, utilizing up to 12 regulators and sensors (one per primary and redundant heating circuit). For safe operation, the control cabinet is equipped with circuit breakers (C-characteristic) and a residual current device (RCD). The cabinet is pre-wired and only requires connection to the mains power supply (400 V, three-phase alternating current).

Advantages

Technical Data

ParameterSpecification
Control2 x digital sensor controller Elreha Tarn 1170 per sprinkler line - primary heating circuit; redundant heating circuit (max. 12 regulators per control cabinet)
Operating Voltage400 V (three-phase)
Heating Circuit Voltage230 V AC, 50/60 Hz
Ambient Temperature+10 °C to +35 °C
SensorsAmbient temperature and sensor per sprinkler line
ApprovalsCE (IEC 61439)
Main SwitchDepending on selected model (32–63 A)
RCD (Residual Current Device)30 mA
Circuit Breaker16 A, C-characteristic, per heating circuit
Operation Mode SelectorAuto/ Manual, primary heating circuit switched on/ Manual, redundant heating circuit switched on
Alarm Function1 general potential-free alarm contact; alarm indicator light on the front panel

Cabinet Dimensions

ProductWeight (kg)Length (mm)Width (mm)Depth (mm)
SBS-02-SNR45600600210
SBS-04-SNR90800800210
SBS-06-SNR90800800210
SBS-08-SNR1151000800300
SBS-10-SNR14010001000300
SBS-12-SNR14010001000300

Related Products

The SBS-xx-SNR control cabinet is compatible with the following Raychem frost protection heating cables:

Reference Data

Product DesignationOrder NumberDescription
SBS-02-SNR185780-000Multi-circuit control cabinet for frost protection in sprinkler systems (1 pipeline)
SBS-04-SNR278362-000Multi-circuit control cabinet for frost protection in sprinkler systems (2 pipelines)
SBS-06-SNR300074-000Multi-circuit control cabinet for frost protection in sprinkler systems (3 pipelines)
SBS-08-SNR158834-000Multi-circuit control cabinet for frost protection in sprinkler systems (4 pipelines)
SBS-10-SNR012276-000Multi-circuit control cabinet for frost protection in sprinkler systems (5 pipelines)
SBS-12-SNR712998-000Multi-circuit control cabinet for frost protection in sprinkler systems (6 pipelines)

Installation Instructions

The product is supplied with complete connection diagrams and wiring schematics. All electrical work must be performed by a qualified electrician in compliance with applicable regulations and standards.

Contact Information

Germany
Tel: 0800 181 82 05
Email: SalesDE@chemelex.com

Austria
Tel: 0800 29 74 10
Email: SalesAT@chemelex.com

Switzerland
Tel: +41 (41) 766 30 80
Fax: +41 (41) 766 30 81
Email: infoCH@chemelex.com

PDF preview unavailable. Download the PDF instead.

Raychem-DS-CDE1636-SBSSNR-DE Adobe PDF Library 17.0 Adobe InDesign 20.5 (Macintosh)

Related Documents

Preview Raychem Self-Regulating Heating Cable: The Original and Reliable Solution
Explore Raychem's original self-regulating heating cable, detailing its performance characteristics based on ambient temperature (cold, warm, hot). Learn about its user-friendly and reliable features, historical significance, and industry certifications. Includes contact information for Chemelex, a leading manufacturer.
Preview Raychem QTVR Self-Regulating Heating Cables: Product Overview and Specifications
Detailed information on Raychem QTVR self-regulating heating cables for electrical process temperature maintenance in nonhazardous and hazardous locations. Includes specifications, approvals, performance data, and ordering details.
Preview Raychem GM-2X-KIT: Installation Guide for Gutter and Downpipe Frost Protection
Installation instructions and technical data for the Raychem GM-2X self-regulating heating cable kit, designed for frost protection of gutters and downpipes. Includes kit contents, installation steps, and specifications.
Preview Raychem XTV Self-Regulating Heating Cable: Product Overview and Specifications
Detailed product overview and technical specifications for the Raychem XTV self-regulating heating cable, including applications, performance data, approvals, and ordering information. Suitable for process temperature maintenance and frost protection in ordinary and hazardous areas.
Preview Raychem HTC-915 Universal Heat Tracing Control System - Technical Specifications
Detailed technical specifications, application, electrical properties, and configuration guide for the Raychem HTC-915 Universal Heat Tracing Control System. Includes product overview, installation notes, and maintenance information.
Preview Raychem MI Heating Cable System Installation and Operation Manual
Comprehensive guide for the installation, operation, and maintenance of Raychem MI heating cable systems for various applications including heat loss replacement, freezer frost heave prevention, comfort floor heating, and radiant space heating. Covers safety guidelines, electrical codes, component installation, power supply, commissioning, and troubleshooting.
Preview Raychem XPI-S Polymer Insulated Resistance Heating Cable Datasheet
Comprehensive datasheet for the Raychem XPI-S Polymer Insulated (PI) series resistance heating cable. Details product overview, technical specifications, hazardous area approvals, and ordering information for industrial heating applications.
Preview Raychem MI Series Heating Systems (IEC / ATEX) - Chemelex
Explore Raychem MI Series Mineral Insulated heating systems, designed for hazardous areas (ATEX/IECEx) with robust construction, advanced control and monitoring capabilities, and optimized system design using Raychem TraceCalc Pro software.