Schneider Electric TeSys K Contactor LC1K0601E7
Product Data Sheet
Specifications
Product Type: Contactor
Device Short Name: LC1K
Device Application: Control
Contactor Application: Motor control
Complementary
Utilisation Category: AC-3, AC-3e, AC-4
Poles Description: 3P
Power Pole Contact Composition: 3 NO
[Ue] Rated Operational Voltage: Power circuit <= 690 V AC; Signalling circuit <= 690 V AC
[Ie] Rated Operational Current: 6 A (at <= 440 V AC) for AC-3 and AC-3e
Control Circuit Type: AC 50/60 Hz
[Uc] Control Circuit Voltage: 48 V AC 50/60 Hz
Motor Power kW: 1.5 kW at 220...230 V AC (AC-3); 2.2 kW at 380...415 V AC (AC-3); 3 kW at 440/690 V AC (AC-3)
Auxiliary Contact Composition: 1 NC
[Uimp] Rated Impulse Withstand Voltage: 8 kV
Overvoltage Category: III
[Ith] Conventional Free Air Thermal Current: 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms Rated Making Capacity: 110 A AC for power circuit conforming to IEC 60947
Rated Breaking Capacity: 110 A at 220...230 V; 110 A at 380...400 V; 110 A at 415 V; 110 A at 440 V; 80 A at 500 V; 70 A at 660...690 V (all conforming to IEC 60947)
[Icw] Rated Short-Time Withstand Current: 90 A at 122 °F (50 °C) - 1 s for power circuit; 85 A at 122 °F (50 °C) - 5 s for power circuit; 80 A at 122 °F (50 °C) - 10 s for power circuit; 60 A at 122 °F (50 °C) - 30 s for power circuit; 45 A at 122 °F (50 °C) - 1 min for power circuit; 40 A at 122 °F (50 °C) - 3 min for power circuit; 20 A at 122 °F (50 °C) - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit
Associated Fuse Rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit; 10 A gG for signalling circuit conforming to IEC 60947; 10 A gG for signalling circuit conforming to VDE 0660
Average Impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] Rated Insulation Voltage: Power circuit 600 V UL 508, 690 V IEC 60947-4-1; Signalling circuit 690 V IEC 60947-4-1, 690 V IEC 60947-5-1, 600 V UL 508; Power circuit 600 V CSA C22.2 No 14; Signalling circuit 600 V CSA C22.2 No 14
Insulation Resistance: > 10 MOhm for signalling circuit
Inrush Power in VA: 30 VA (at 68 °F (20 °C))
Hold-in Power Consumption in VA: 4.5 VA (at 68 °F (20 °C))
Heat Dissipation: 1.3 W
Control Circuit Voltage Limits: Operational: 0.8...1.15 Uc; Drop-out: >= 0.20 Uc
Connections - Terminals: Screw clamp terminals (solid, flexible with/without cable end)
Maximum Operating Rate: 3600 cyc/h
Auxiliary Contacts Type: Instantaneous 1 NC
Signalling Circuit Frequency: <= 400 Hz
Minimum Switching Current: 5 mA for signalling circuit
Minimum Switching Voltage: 17 V for signalling circuit
Mounting Support: Plate, Rail
Tightening Torque: 7.08...11.5 lbf.in (0.8...1.3 N.m) for screw clamp terminals
Operating Time: 10...20 ms (coil de-energisation and NO opening), 10...20 ms (coil energisation and NO closing)
Safety Reliability Level: B10d = 1369863 cycles (contactor with nominal load); B10d = 20000000 cycles (contactor with mechanical load)
Non Overlap Distance: 0.02 in (0.5 mm)
Mechanical Durability: 10 Mcycles
Electrical Durability: 1.3 Mcycles at 6 A AC-3 <= 440 V; 1.3 Mcycles at 6 A AC-3e <= 440 V; 0.05 Mcycles at 36 A AC-4 <= 440 V
Mechanical Robustness: Shocks: 10-15 Gn (closed), 6-10 Gn (opened); Vibrations: 4 Gn (closed), 2 Gn (opened)
Height: 2.3 in (58 mm)
Width: 1.8 in (45 mm)
Depth: 2.2 in (57 mm)
Product Weight: 0.40 lb(US) (0.18 kg)
Environment
Standards: EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, IEC 60335-1, IEC 60335-2-40, UL 60335-2-40
Product Certifications: CB Scheme, CCC, UL, CSA, EAC, CE, UKCA
IP Degree of Protection: IP2X VDE 0106
Protective Treatment: TC IEC 60068, TC DIN 50016
Ambient Air Temperature for Storage: -58...176 °F (-50...80 °C)
Operating Altitude: 6561.68 ft (2000 m) without derating
Flame Retardance: V1 conforming to UL 94, Requirement 2 conforming to NF F 16-101, Requirement 2 conforming to NF F 16-102
Ordering and Shipping Details
Category: US1011222326
Discount Schedule: 0112
GTIN: 3389110374735
Returnability: No
Country of Origin: ID
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 2.60 in (6.600 cm)
Package 1 Width: 1.89 in (4.800 cm)
Package 1 Length: 2.44 in (6.200 cm)
Package 1 Weight: 6.279 oz (178.000 g)
Unit Type of Package 2: S02
Number of Units in Package 2: 50
Package 2 Height: 5.91 in (15.000 cm)
Package 2 Width: 11.81 in (30.000 cm)
Package 2 Length: 15.75 in (40.000 cm)
Package 2 Weight: 20.459 lb(US) (9.280 kg)
Contractual Warranty
Warranty: 18 months
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050. The "Use Better, Use Longer, Use Again" campaign promotes product longevity and recyclability.
Environmental Footprint: Carbon footprint (kg CO2 eq, Total Life cycle): 51
Materials and Substances: Packaging made with recycled cardboard: Yes; Packaging without single use plastic: Yes
EU RoHS Directive: Compliant
REACH Regulation: REACH Declaration
California Proposition 65: WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Repack and Remanufacture: Circularity Profile: No information available
Take-back: No
WEEE: The product must be disposed of in European Union markets following specific waste collection and never end up in rubbish bins.
Dimensions Drawings
Dimensions
Contactors LC1 K, LP1 K, LP4 K: Mounting on Panel
Diagram showing panel mounting dimensions with labels for L1 K, 35, 57, 45.
Contactors LC1 K, LP1 K, LP4 K: Mounting on Rail AM1 DP200 or AM1 DE200 (35 mm)
Diagram showing rail mounting dimensions with labels for 57, 58, 45.
Connections and Schema
Wiring
3-Pole Contactors: 3P + N/O
Wiring diagram for 3-pole contactors with Normally Open (N/O) auxiliary contacts.
3-Pole Contactors: 3P + N/C
Wiring diagram for 3-pole contactors with Normally Closed (N/C) auxiliary contacts.
Technical Illustration
Wiring Diagram
3P NC
Diagram illustrating the wiring for a 3-pole contactor with a Normally Closed (NC) auxiliary contact, showing terminals A1, A2, T1, T2, T3, and 22 NC.
Product Benefits / Features
TeSys K Technical Benefits
- Built-in in all 3 pole versions: 1NO or 1NC
- Up to 4 more by add-on blocks
- Up to 16 A for motor control (AC3/AC3E) and 20A for resistive load control (AC1)
- Available as single contactors, star-delta, and reversing combos, with a wealth of options and accessories
- Control Options: AC: 24 to 660/690 V; DC: 12 to 250V
- Thermal protection relays
- Features specific versions for railway (TeSys S207) and electrodomestic (TeSys S335) applications
TeSys K Contactors
- Flexibility: Designed with control voltages, low consumption, minimal noise levels, robust power connections, and a range of auxiliaries, and application-specific variants to meet diverse needs.
- Safety: Provides ultimate protection with IP20 finger-safe terminals, built-in NO/NC auxiliary contacts, and IEC-certified mirror and mechanically linked contacts for safety applications.
- Compact size: Up to 50% less volume compared to other contactors in the market.
Assembly's Dimensions
Diagram showing assembly dimensions with various measurements indicated in mm.