Schneider Electric TeSys Deca GV2ME103 Manual Motor Starter and Protector

Product Data Sheet

Specifications

Main

Range TeSys Deca
Product name TeSys GV2
Product or Component Type Motor circuit breaker
Device short name GV2ME
Device Application Motor protection
Trip unit technology Thermal-magnetic

Complementary

Poles description 3P
Network type AC
Utilisation category Category A IEC 60947-2
AC-3 IEC 60947-4-1
AC-3e IEC 60947-4-1
Network frequency 50/60 Hz IEC 60947-2
Motor power kW 2.2 kW 400/415 V AC 50/60 Hz
3 kW 500 V AC 50/60 Hz
Breaking capacity 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
50 kA Icu 440 V AC 50/60 Hz IEC 60947-2
50 kA Icu 500 V AC 50/60 Hz IEC 60947-2
3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity 100% 230/240 V AC 50/60 Hz IEC 60947-2
100% 400/415 V AC 50/60 Hz IEC 60947-2
100% 440 V AC 50/60 Hz IEC 60947-2
100% 500 V AC 50/60 Hz IEC 60947-2
75% 690 V AC 50/60 Hz IEC 60947-2
Control Type Push-button
Line Rated Current 6.3 A
Thermal protection adjustment range 4...6.3 A IEC 60947-2
Magnetic tripping current 6.3 A IEC 60947-2
[Ith] conventional free air thermal current 91 A
[Ue] rated operational voltage 690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Phase failure sensitivity Yes IEC 60947-4-1
Suitability for isolation Yes IEC 60947-1
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles AC-3 415 V In
100000 cycles AC-3e 415 V In
Rated duty Uninterrupted IEC 60947-4-1
Connections - terminals Power circuit spring terminals 2 0.002...0.009 in² (1...6 mm²)solid
Power circuit spring terminals 2 0.002...0.006 in² (1.5...4 mm²)flexible without cable end
Power circuit spring terminals 2 0.002...0.006 in² (1...4 mm²)flexible with cable end
Fixing mode 35 mm symmetrical DIN rail clipped
(Panel screwed with adaptor plate)
Mounting position Horizontal
Vertical
Width 1.8 in (45 mm)
Height 4.0 in (101 mm)
Depth 3.09 in (78.5 mm)
Net Weight 0.62 lb(US) (0.28 kg)
color Dark grey

Environment

Standards EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC/EN 60335-2-40:Annex JJ
IEC/EN 60335-1:Clause 30.2
Product Certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
IK degree of protection IK04
IP degree of protection IP20 IEC 60529
Climatic withstand IACS E10
Ambient Air Temperature for Storage -40...176 °F (-40...80 °C)
Fire resistance 1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation -4...140 °F (-20...60 °C)
Mechanical robustness Shocks 30 Gn for 11 ms
Vibrations 5 Gn, 5...150 Hz
Operating altitude <= 6561.68 ft (2000 m)

Ordering and shipping details

Category US1011122367
Discount Schedule 0111
GTIN 3389110346442

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 2.17 in (5.5 cm)
Package 1 Width 4.33 in (11 cm)
Package 1 Length 3.35 in (8.5 cm)
Package 1 Weight 10.7 oz (304 g)
Unit Type of Package 2 S02
Number of Units in Package 2 20
Package 2 Height 5.91 in (15 cm)
Package 2 Width 11.81 in (30 cm)
Package 2 Length 15.75 in (40 cm)
Package 2 Weight 14.15 lb(US) (6.42 kg)

Contractual warranty

Warranty 18 months

Performance Curves

Thermal-Magnetic Tripping Curves for GV2ME and GV2P

Average Operating Times at 20 °C Related to Multiples of the Setting Current

A graph shows time in seconds on the y-axis (logarithmic scale) versus multiples of the setting current (Ir) on the x-axis (logarithmic scale). Three curves are plotted, representing different conditions: 3 poles from cold state, 2 poles from cold state, and 3 poles from hot state.

Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))

Dynamic Stress: I peak = f (prospective Isc) at 1.05 Ue = 435 V

A graph shows limited peak current (kA) on the y-axis (logarithmic scale) versus prospective Isc (kA) on the x-axis (logarithmic scale). Multiple curves are shown, each corresponding to a range of maximum peak current values (e.g., 24-32 A, 20-25 A, etc.).

Thermal Limit on Short-Circuit for GV2ME

Thermal Limit in kA²s in the Magnetic Operating Zone: Sum of I²dt = f (prospective Isc) at 1.05 Ue = 435 V

A graph shows Sum of Fdt (kA²s) on the y-axis (logarithmic scale) versus prospective Isc (kA) on the x-axis (logarithmic scale). Multiple curves are shown, each corresponding to a range of current values (e.g., 24-32 A, 20-25 A, etc.).

Dimensions Drawings

Dimension GV2ME

Diagrams showing the dimensions of the GV2ME device. Key dimensions include:

  • Width: 45 mm
  • Height: 101 mm
  • Depth: 78.5 mm
  • X1 Electrical clearance = 40 mm for Ue ≤ 690 V

Diagrams also show the device's overall dimensions and internal component layout.

Mounting GV2ME

The GV2ME can be mounted in several ways:

  • On a 35 mm rail.
  • On a panel with adapter plate GV2AF02.
  • On pre-slotted plate AM1 PA AF1 EA4.
  • On rails DZ5 MB201.

Diagrams illustrate each mounting method.

GV2AF01 Combination GV2ME + TeSys k contactor

Diagram showing the combined dimensions and layout of GV2ME with a TeSys k contactor.

GV2ME + LC1D09...D18 LC1D25 and D32
b 176.4 186.8
c1 94.1 100.4
c 99.6 105.9

GV2AF3 Combination GV2ME + TeSys d contactor

Diagram showing the combined dimensions and layout of GV2ME with a TeSys d contactor.

GV2ME + LC1D09...D18 LC1D25 and D32
b 176.4 186.8
c1 103.1 136.4
c 135.6 141.9
d1 107 107
d 112.5 112.5

GV2ME + GV1L3 (Current Limiter)

Diagram showing the combined dimensions and layout of GV2ME with a GV1L3 current limiter. Includes dimensions and notes on electrical clearance.

Connections and Schema

GV2ME. and GV2RT

Diagrams illustrating the electrical connections and schematics for GV2ME and GV2RT devices.

Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only

A schematic diagram shows the wiring for an undervoltage trip connection on the GV2ME, indicating terminals and components.

Offer Marketing Illustration

Product benefits / Features

TeSys Deca Motor Circuit Breakers

Range Accessories

Images and labels for various accessories are displayed:

Technical Benefits

TeSys Deca Motor Circuit Breakers

Product benefits / Features

TeSys Deca Motor Circuit Breakers

Environmental Data

Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.

Environmental footprint

Materials and Substances

Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
EU RoHS Directive Compliant with Exemptions
SCIP Number 04104e70-ba29-493c-b2cc-b5837d1f879b
REACH Regulation REACH Declaration
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Use Again

Repack and remanufacture

Circularity Profile End of Life Information
Take-back No
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

PDF preview unavailable. Download the PDF instead.

Generatepdf.aspx?salesorgid=78&dist=849&lang=42&form=no&documenttype=plain&productid=GV2ME103 cairo 1.15.12 (http://cairographics.org)

Related Documents

Preview Schneider Electric TeSys Deca Contactor LC1D25AP7 Product Data Sheet
Detailed product data sheet for the Schneider Electric TeSys Deca Contactor, model LC1D25AP7. This document outlines specifications, technical data, environmental information, and packaging details for this 3-pole contactor.
Preview Schneider Electric TeSys Deca GV2ME14A Motor Circuit Breaker Data Sheet
Detailed specifications for the Schneider Electric TeSys Deca GV2ME14A motor circuit breaker, including its thermal-magnetic protection, snap-in terminals, push button operation, and environmental data.
Preview Schneider Electric GV2L16 TeSys Deca Manual Starter and Protector Data Sheet
Detailed technical specifications, performance curves, dimensions, and environmental data for the Schneider Electric GV2L16 TeSys Deca Manual Starter and Protector.
Preview Schneider Electric TeSys Hybrid LZ7H Ultra-Compact Starter Data Sheet
Technical specifications for the Schneider Electric TeSys Hybrid LZ7H ultra-compact starter, including its electrical and mechanical data, environmental information, and packaging details. Suitable for 3-phase applications up to 500VAC, 3kW at 400V, with a 24VDC control circuit.
Preview Schneider Electric TeSys Ultra Reverser Block LU6MB0BL - 38A/690V, 24VDC Coil
Technical data sheet for Schneider Electric TeSys Ultra reverser block, model LU6MB0BL. Features include 38A/690V rating, 24VDC coil, separate mounting, motor control application, and compliance with various international standards.
Preview Schneider Electric TeSys Deca LC1D09M7 IEC Contactor - 9A, 3-Phase, 220VAC Coil
Detailed technical data sheet for the Schneider Electric TeSys Deca LC1D09M7 IEC contactor. Features include 9A rated operational current (AC3), 3 poles (3NO), 1 NO + 1 NC auxiliary contacts, and a 220VAC 50/60Hz coil. Specifications cover electrical ratings, complementary components, environmental data, dimensions, and ordering information.
Preview Schneider Electric TeSys Catalog 2024: Motor Control Solutions
Explore the Schneider Electric TeSys Catalog 2024, featuring innovative and connected solutions for motor starters, control, protection, and power management. Discover a century of expertise in motor control technology.
Preview Schneider Electric TeSys K Contactor LC1K0601E7 - 6A, 48VAC Coil
Technical data sheet for the Schneider Electric TeSys K Contactor LC1K0601E7. Features include 3 poles, 1 NC auxiliary contact, AC-3 utilization category up to 440V, and 48VAC coil. Details on specifications, dimensions, environment, ordering, and packing units.