Schneider Electric TeSys Deca GV2ME103 Manual Motor Starter and Protector
Product Data Sheet
Specifications
Main
Range | TeSys Deca |
Product name | TeSys GV2 |
Product or Component Type | Motor circuit breaker |
Device short name | GV2ME |
Device Application | Motor protection |
Trip unit technology | Thermal-magnetic |
Complementary
Poles description | 3P |
Network type | AC |
Utilisation category | Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1 |
Network frequency | 50/60 Hz IEC 60947-2 |
Motor power kW | 2.2 kW 400/415 V AC 50/60 Hz 3 kW 500 V AC 50/60 Hz |
Breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 100% 230/240 V AC 50/60 Hz IEC 60947-2 100% 400/415 V AC 50/60 Hz IEC 60947-2 100% 440 V AC 50/60 Hz IEC 60947-2 100% 500 V AC 50/60 Hz IEC 60947-2 75% 690 V AC 50/60 Hz IEC 60947-2 |
Control Type | Push-button |
Line Rated Current | 6.3 A |
Thermal protection adjustment range | 4...6.3 A IEC 60947-2 |
Magnetic tripping current | 6.3 A IEC 60947-2 |
[Ith] conventional free air thermal current | 91 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
Phase failure sensitivity | Yes IEC 60947-4-1 |
Suitability for isolation | Yes IEC 60947-1 |
Power dissipation per pole | 2.5 W |
Mechanical durability | 100000 cycles |
Electrical durability | 100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In |
Rated duty | Uninterrupted IEC 60947-4-1 |
Connections - terminals | Power circuit spring terminals 2 0.002...0.009 in² (1...6 mm²)solid Power circuit spring terminals 2 0.002...0.006 in² (1.5...4 mm²)flexible without cable end Power circuit spring terminals 2 0.002...0.006 in² (1...4 mm²)flexible with cable end |
Fixing mode | 35 mm symmetrical DIN rail clipped (Panel screwed with adaptor plate) |
Mounting position | Horizontal Vertical |
Width | 1.8 in (45 mm) |
Height | 4.0 in (101 mm) |
Depth | 3.09 in (78.5 mm) |
Net Weight | 0.62 lb(US) (0.28 kg) |
color | Dark grey |
Environment
Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2 |
Product Certifications | CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV RINA DNV-GL UKCA |
IK degree of protection | IK04 |
IP degree of protection | IP20 IEC 60529 |
Climatic withstand | IACS E10 |
Ambient Air Temperature for Storage | -40...176 °F (-40...80 °C) |
Fire resistance | 1760 °F (960 °C) IEC 60695-2-11 |
Ambient air temperature for operation | -4...140 °F (-20...60 °C) |
Mechanical robustness | Shocks 30 Gn for 11 ms Vibrations 5 Gn, 5...150 Hz |
Operating altitude | <= 6561.68 ft (2000 m) |
Ordering and shipping details
Category | US1011122367 |
Discount Schedule | 0111 |
GTIN | 3389110346442 |
Packing Units
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 2.17 in (5.5 cm) |
Package 1 Width | 4.33 in (11 cm) |
Package 1 Length | 3.35 in (8.5 cm) |
Package 1 Weight | 10.7 oz (304 g) |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 20 |
Package 2 Height | 5.91 in (15 cm) |
Package 2 Width | 11.81 in (30 cm) |
Package 2 Length | 15.75 in (40 cm) |
Package 2 Weight | 14.15 lb(US) (6.42 kg) |
Contractual warranty
Warranty | 18 months |
Performance Curves
Thermal-Magnetic Tripping Curves for GV2ME and GV2P
Average Operating Times at 20 °C Related to Multiples of the Setting Current
A graph shows time in seconds on the y-axis (logarithmic scale) versus multiples of the setting current (Ir) on the x-axis (logarithmic scale). Three curves are plotted, representing different conditions: 3 poles from cold state, 2 poles from cold state, and 3 poles from hot state.
Current Limitation on Short-Circuit for GV2ME and GV2P (3-Phase 400/415 V))
Dynamic Stress: I peak = f (prospective Isc) at 1.05 Ue = 435 V
A graph shows limited peak current (kA) on the y-axis (logarithmic scale) versus prospective Isc (kA) on the x-axis (logarithmic scale). Multiple curves are shown, each corresponding to a range of maximum peak current values (e.g., 24-32 A, 20-25 A, etc.).
Thermal Limit on Short-Circuit for GV2ME
Thermal Limit in kA²s in the Magnetic Operating Zone: Sum of I²dt = f (prospective Isc) at 1.05 Ue = 435 V
A graph shows Sum of Fdt (kA²s) on the y-axis (logarithmic scale) versus prospective Isc (kA) on the x-axis (logarithmic scale). Multiple curves are shown, each corresponding to a range of current values (e.g., 24-32 A, 20-25 A, etc.).
Dimensions Drawings
Dimension GV2ME
Diagrams showing the dimensions of the GV2ME device. Key dimensions include:
- Width: 45 mm
- Height: 101 mm
- Depth: 78.5 mm
- X1 Electrical clearance = 40 mm for Ue ≤ 690 V
Diagrams also show the device's overall dimensions and internal component layout.
Mounting GV2ME
The GV2ME can be mounted in several ways:
- On a 35 mm rail.
- On a panel with adapter plate GV2AF02.
- On pre-slotted plate AM1 PA AF1 EA4.
- On rails DZ5 MB201.
Diagrams illustrate each mounting method.
GV2AF01 Combination GV2ME + TeSys k contactor
Diagram showing the combined dimensions and layout of GV2ME with a TeSys k contactor.
GV2ME + LC1D09...D18 | LC1D25 and D32 | |
b | 176.4 | 186.8 |
c1 | 94.1 | 100.4 |
c | 99.6 | 105.9 |
GV2AF3 Combination GV2ME + TeSys d contactor
Diagram showing the combined dimensions and layout of GV2ME with a TeSys d contactor.
GV2ME + LC1D09...D18 LC1D25 and D32 | ||
b | 176.4 | 186.8 |
c1 | 103.1 | 136.4 |
c | 135.6 | 141.9 |
d1 | 107 | 107 |
d | 112.5 | 112.5 |
GV2ME + GV1L3 (Current Limiter)
Diagram showing the combined dimensions and layout of GV2ME with a GV1L3 current limiter. Includes dimensions and notes on electrical clearance.
Connections and Schema
GV2ME. and GV2RT
Diagrams illustrating the electrical connections and schematics for GV2ME and GV2RT devices.
Connection of Undervoltage Trip for Dangerous Machines (Conforming to INRS) on GV2ME Only
A schematic diagram shows the wiring for an undervoltage trip connection on the GV2ME, indicating terminals and components.
Offer Marketing Illustration
Product benefits / Features
TeSys Deca Motor Circuit Breakers
Range Accessories
Images and labels for various accessories are displayed:
- Energy Sensor
- Mounting and adapters
- Terminal block
- Combination block
- Motor starter adapter plate
- Current limiter
- Comb busbar
- Auxiliary contact blocks
Technical Benefits
TeSys Deca Motor Circuit Breakers
- High breaking capacity up to 100 kA.
- Screw clamp for the connection, with lug and spring terminals.
- Easily identify the tripped breaker.
- Padlockable in all versions.
- Sealable thermal overload settings without additional accessories.
- Short circuit indication for better diagnostics when a trip occurs.
- Maximum 15 current ratings to cover from 0.1 A to 32 A motor current with a IP20 level for finger safety.
Product benefits / Features
TeSys Deca Motor Circuit Breakers
- Universal Integration: Can be used for all types of applications across industry, infrastructure and buildings.
- Complete protection: Provides short circuit protection, overload protection, motor (ON/OFF) control, all in a single product.
- Standard Sync: Compliant to motor control and protection, in accordance with standards.
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity via its ongoing "Use Better, Use Longer, Use Again" campaign to extend product lifetimes and recyclability.
Environmental footprint
- Carbon footprint (kg CO2 eq, Total Life cycle): 43
Materials and Substances
Packaging made with recycled cardboard | Yes |
Packaging without single use plastic | Yes |
EU RoHS Directive | Compliant with Exemptions |
SCIP Number | 04104e70-ba29-493c-b2cc-b5837d1f879b |
REACH Regulation | REACH Declaration |
California proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Use Again
Repack and remanufacture
Circularity Profile | End of Life Information |
Take-back | No |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |