ASSA ABLOY ACCENTRA™ KRM200 & KRM200F and Corbin Russwin CR972BKM / CR972KM / CR910BKM Mullions
Installation
Attention Installer
Any retrofit or other field modification to a fire-rated opening can potentially impact the fire rating of the opening. ASSA ABLOY makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire-rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings.
Tools Required
Measuring Tape, Pencil, Drill & Tap Sizes (#7 drill and 1/4"-20 tap), Concrete Drill (3/8" diameter), Center Punch, Hammer, #3 Phillips Screwdrivers, 5/32" Allen Wrench, 1/8" Allen Wrench
Installation Steps
- Close and block doors against frame stops. Check gap between door leaves and door to frame and correct if necessary.
- Locate the center of the opening on the floor. Using the bottom retainer, mark the positions for the two drop-in fasteners.
- The bottom of the door should come to rest against the surface of the mullion.
- Modify threshold as required.
- Drill holes with a 3/8" diameter cement bit to a minimum depth of 2-1/2" (63.5 mm).
- Fasten bottom retainer to floor.
- Locate the center of the opening on the top of the frame. Using the top retainer, mark the positions for the four fasteners.
- The door should evenly rest against both the frame stop and the mullion.
- If a top retainer mounting kit is used, modify weather stripping as required.
- Drill and tap each location for 1/4"-20 fasteners.
- Mount top retainer on frame with provided fasteners.
- Measure "Dim X" as shown in the diagram. Remove material from the bottom of the mullion per the formula: length of mullion = "Dim X" minus 3/4" (19 mm).
- Note: This leaves approximately 1/8" (3.2 mm) clearance between the mullion and the top retainer when mounted.
Installation of Cylinder
- Depress latchbolt and hold fully retracted.
- Carefully thread cylinder with cylinder ring into lock assembly until it bottoms out.
- Unscrew the cylinder, orienting the keyway at the bottom.
- Release latch bolt. Note: If latch bolt is not fully projected, loosen cylinder an additional 1-2 full turns.
- Tighten set screw with a 5/64" Allen Wrench through the access hole in the side of the mullion.
Mullion and Exit Device Installation
- Place mullion onto bottom bracket and pivot into opening to latch.
- Tighten bottom bracket set screw to prevent mullion rattle.
- Install exit devices according to the manufacturer's instructions.
- Fire-rated Rim and SquareBolt® / SecureBolt® Exit Devices: After exit devices and strikes have been assembled, install interlock brackets with #10-24 x 3/4" screws as shown in the illustration.
Interlock Installation
Interlock Bracket Required for Fire Rated SquareBolt® and Rim Exit Device with Mullion.
- Position strike interlock bracket in place, as shown. Locate bracket holes.
- Prepare interlock bracket mounting holes and mount with (4) 10-24 x 3/4" screws (and SNBs when applicable).
The interlock bracket's center tab engages under the strike roller. The distance between the mullion and the strike surface should be 5/16" (7.9 mm).
WARNING
This product can expose you to lead, which is known to the state of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov.
ASSA ABLOY Opening Solutions
225 Episcopal Road
Berlin, CT 06037
For support, contact ASSA ABLOY at 1-800-543-3658 or visit www.assaabloy.com.
Copyright © 2020, 2022, 2024 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
Document Number: MEMN11 04/24