Eaton C30CN Lighting Contactor Series

Product Description

The Cutler Hammer C30CN Series is a magnetically operated lighting contactor, available in both open and enclosed forms. These contactors are field configurable for up to twelve poles, with a maximum of eight normally closed "NC" poles.

1 MAIN BASE

The base of the lighting contactor has provisions to accept power poles at positions "1" to "6". Provisions are also provided for up to 2 "NO" and 2 "NC" auxiliary contacts.

1.1 Description

The base of the lighting contactor has provisions to accept power poles at positions "1" to "6". Provisions are also provided for up to 2 "NO" and 2 "NC" auxiliary contacts.

1.2 Installation

  1. Remove all packing material from the base and all the kits.
  2. Contactor must be mounted in the vertical position on a sturdy support.
  3. Additional over-current protection may be required. Refer to the National Electrical Code or local electrical code as required.
  4. Refer to Section 5.3 and Table D on page 3 for the wire size and the required torque for the coil terminals.

Hazardous Voltage Warning: Disconnect all power before working on equipment. Electrical shock will cause severe injury or death.

Tension Dangereuse: Coupez l'alimentation avant travailler sur le produit. Electrocution peut causer de sévères blessures ou la mort.

Figure 1: Mechanically Held Contactor showing Main Base, NO Aux. Contact, and NC Aux. Contact.

2 POWER POLES: C320PRP1 & C320PRP2

2.1 Description

Power poles are available in both single pole (C320PRP1) and double pole (C320PRP2) versions. A maximum of twelve poles may be installed on the base. Positions "1" to "4" on the base can be configured as either normally open “NO” or “NC” while positions “5” and “6” can be configured as “NO” only.

2.2 Removal and Conversion of Power Poles

  1. If installed, ensure that all power is disconnected.
  2. For multiple possible configurations of the power poles, refer to Table A below.
  3. Remove block by using a screwdriver to pull the clip as shown (see Figure 2). Rotate block 180 degrees to convert from NO to NC or from NC to NO and install per 2.3 below.
Table A: Number of NC Contacts Desired vs. Number of NO Contacts Desired
# of NC Contacts Desired (3) # of NO Contacts Desired (4)
0 1 2 3 4 5 6 7 8 9 10 11 12
0 00 01 02 03 04 05 06 07 08
1 10 11 12 13 14 15 16 17 18
2 20 21 22 23 24 25 26 27 28
3 30 31 32 33 34 35 36 37 38
4 40 41 42 43 44 45 46 47 48
5 50 51 52 53 54 55 56 57 58
6 60 61 62 63 64 65 66
7 70 71 72 73 74 75
8 80 81 82 83 84
9 90 91 92 93
10 100 101 102
11 110 111
12 120

Standard Catalog #: C30CNE43A0

Figure 2: Installation of Power Poles, showing removal of block and conversion.

2.3 Installation of Power Poles

  1. Check moving carrier to assure free movement.
  2. Install the block by sliding foot into slot, using a screwdriver, pull the clip, and position block onto base. Release the clip.
  3. Check for the lettering on the base. "NO" should be visible if the power pole is assembled as normally open, and "NC" should be visible if it is assembled as normally closed (see Figure 3).

2.4 Wiring

Power poles can accept wires from #14 to #8 AWG (either solid or stranded) as single or combination of two wires (refer to Table B below for valid wire combination). Wire material must be copper with a temperature rating of 75 degrees C. Maximum tightening torque is 35 in-lbs.

Table B: Wire Gauge and Type Compatibility
Size Type
8 AWG Stranded 10 AWG Stranded 10 AWG Solid 12 AWG Stranded 12 AWG Solid 14 AWG Stranded 14 AWG Solid
8 AWG Stranded X X X X X X X
10 AWG Stranded X X X X X X X
10 AWG Solid X X X X X X X
12 AWG Stranded X X X X X X X
12 AWG Solid X X X X X X X
14 AWG Stranded X X X X X X X
14 AWG Solid X X X X X X X
Figure 3: Shows the assembled power pole with "NO" or "NC" visible.

3 AUXILIARY CONTACTS: C320AMH1 & C320AMH2

3.1 Description

The auxiliary contact blocks are available in both single pole (C320AMH1) and double pole (C320AMH2) versions. Auxiliary contacts can be added on either side of the base (see Figure 1). When added to the LEFT side of base, the auxiliary block functions as “NO”, and when added to the RIGHT side of base it functions as “NC”. Refer to section 4.3 for wiring.

4 CONTROL MODULE KITS

4.1 Description

Control module kits are available both for 2-wire and 3-wire control with a wide range of control voltage inputs. Figure 4 shows the components in 2-wire control module kit. A 3-wire kit includes an additional single-pole auxiliary contact block. Refer to the Ordering Detail section for more information on control module kits and control voltages available.

IMPORTANT: The control module kits are for use with the coils up to 277 VAC maximum. Use a control power transformer for higher voltages.

Conversion from an electrically held to a mechanically held type is possible by adding a “control module kit" to the base.

Figure 4: Components of a 2-wire control module kit.

4.2 Installation

  1. Disconnect all power and mount the control module on the contactor as shown in Figure 1 (3-wire control type).
  2. Mount the latch as shown in Figure 5.
  3. Be sure the latch is firmly in place with the wire facing out and the slot positioned with tab inserted.
  4. Mount the latch cover as shown in Figure 5.
  5. For 2-wire control, the auxiliary contact block is assembled to the right side of the base for "NC".
  6. Operate contactor manually, using manual operation tabs (See Figure 5) on side, prior to installing cover to insure correct installation.

Caution: Once latch cover has been installed, it may not be removed. Ensure latch is properly installed prior to installing the latch cover.

IMPORTANT: Latch and electronic module must be used together to ensure proper operation. Failure to do so will void warranty.

4.3 Wiring

Control module's and auxiliary contact block's terminals can accept a single wire from #22 to #12 AWG (either solid or stranded). Maximum tightening torque required for the control module's terminals is 5 in-lbs. Auxiliary contact block terminals can accept parallel conductor size combinations utilizing torques identified in Table C.

Table C: Wire Combination and Torque for Auxiliary Contacts
Wire Combination Torque
#12 with #14 12 in-lbs
#14 with #16 12 in-lbs
#16 with #18 12 in-lbs
#16 with #20 12 in-lbs
#16 with #22 12 in-lbs
#18 with #22 10-12 in-lbs
#18 with #20 10-12 in-lbs
#20 with #22 7-12 in-lbs
Figure 5: Illustrates latch installation and manual operation tabs.

5 COIL KITS

5.1 Description

A wide range of coils is available for both electrically held and mechanically held lighting contactors. Refer to the Ordering Detail section for more information about the coil kit catalog numbers and voltages available.

Note: For mechanically held lighting contactors, only use coils rated up to 277 VAC maximum. Use a control power transformer for higher voltages.

5.2 Installation

  1. Disconnect all power. Replace and mount the coil on the contactor as shown in Figure 7.
  2. For mechanically held contactors, remove all wires from the control module and remove the coil cover along with control module.
Figure 7: Shows coil replacement.

5.3 Wiring

Coil terminal can accept wires from #18 AWG to #14 AWG (either solid or stranded) as single or combination of two wires (Refer to Table D below for valid wire combination). Wire material must be copper with a temperature rating of 60 or 75 degrees C. Maximum tightening torque is 15 in-lbs.

Table D: Coil Wiring Compatibility
Size Type
#14 AWG Solid #14 AWG Stranded #16 AWG Solid #16 AWG Stranded #18 AWG Solid #18 AWG Stranded
#14 AWG Solid X X X X X X
#14 AWG Stranded X X X X X X
#16 AWG Solid X X X X X X
#16 AWG Stranded X X X X X X
#18 AWG Solid X X X X X X
#18 AWG Stranded X X X X X X

Follow the schematic (Figure 6) to wire the 2 and 3-wire control modules.

Note: For 2-wire control, ensure the two wires coming from the control module are connected across a NC auxiliary contact.

Figure 6: Wiring schematics for 2-wire and 3-wire control modules.

Ordering Details

Coil Kits:

Control Module Kits:

Power Pole Kits:

Auxiliary Contact Kits:

Note: These instructions do not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently or the Purchase's purpose, the matter should be referred to Eaton e-Com Technical Support. Toll free telephone (800) 356-1243.

Wiring Diagrams

Diagrams illustrating the wiring for C30CN Electrically Held Contactor and C30CN Mechanically Held Contactor, including optional pilot devices and control module connections for 2-wire and 3-wire control.

Wiring Diagrams for Electrically Held and Mechanically Held Contactors.

PDF preview unavailable. Download the PDF instead.

c30cn-lighting-contactors-installation-instructions-PUB50765 Acrobat Distiller 5.0 (Windows)

Related Documents

Preview Eaton 239403 DILM Contactor Specifications
Detailed specifications for the Eaton Moeller series DILM Contactor, 3 pole, 380 V - 440 V, 37 kW, AC operation, with screw terminals. Includes technical data, certifications, and operating parameters.
Preview Eaton DC Contactor Installation and Safety Instructions
Comprehensive instruction leaflet for Eaton DC contactors, including DILDC and XTCE series, covering safety warnings, installation procedures, wiring diagrams, and technical specifications.
Preview Eaton DILM & XTCEX Wiring Kits: Installation Instructions and Safety Guide
Comprehensive installation leaflet for Eaton DILM and XTCEX series contactors and wiring kits, including essential safety warnings, wiring diagrams, and technical specifications for motor control applications.
Preview Eaton XT UL Short-Circuit Current Ratings Technical Data
Comprehensive technical data detailing Eaton's XT series components, including fuse-contactors, breaker-contactors, and motor controllers, with UL short-circuit current ratings (SCCR) for various applications and voltages.
Preview Eaton ZE, XTOM, XTMC Motor Protective Relays Instruction Leaflet
Instruction leaflet for Eaton ZE, XTOM, and XTMC series motor protective relays, covering installation, safety, and technical specifications. Includes wiring diagrams, current ratings, and reset functions.
Preview Eaton SC-UN Universal Source Controllers: Technical Data and Specifications
Comprehensive technical data, features, specifications, and ordering information for Eaton's SC-UN Universal Source Controllers, designed for advanced architectural lighting control.
Preview Eaton PXR Trip Units and Power Defense Frames Wiring Diagrams
Technical wiring diagrams and instructions for Eaton PXR Trip Units and Power Defense Frames (Models 2, 3, 4, 5, & 6), covering control power, sensing, interlock, maintenance, Modbus, and communication interfaces.
Preview Eaton Aerospace Master Technical Publications Index List
A comprehensive index of technical publications for Eaton Aerospace products, detailing part numbers, model numbers, document types, issue dates, aircraft platforms, and manufacturing sites. This list serves as a crucial resource for maintaining and servicing aerospace components.