SC-UN – Universal Source Controllers - Cooper Lighting

SC-UN – Universal Source Controllers www.eaton.com/lightingsystems. Wiring Diagram. iCANnet. iCANnet. SWITCH INPUT 2. SWITCH INPUT 1.

PDF preview unavailable. Download the PDF instead.

sc un spec sheet fwb
Technical Data

iILNSu#min

SC-UN ­ Universal Source Controllers

Catalog# Project Comments

Prepared by Date Type

Overview
The Universal Source Controller line of lighting control panels set a new standard in architectural lighting control. Each Source Controller contains individual control cards that are the industry's only "true universal" by controlling most load types without interface or multiple cards. In addition, each panel has onboard Ethernet, A/V interface, Contact Closure, DMX input, voltage sensing, real-time individual circuit power metering, and Phase SenseTM technology designed to ensure control even during individual phase failure.
Features
6, 12, and 24 circuit variants
Forward Phase triac slow rise-time dimmer engine. Capable of withstanding repetitive inrush current of 50 times operating current without impacting lifetime of dimmer or relay.
Positive air-gap off per circuit
Single or three phase versions
Continuous duty, thermal magnetic SWD rated breakers for each circuit
Bypass per circuit for manual override and providing construction site lighting
Voltage and frequency compensation to maintain light level during supply fluctuations
Real-time power metering for each circuit, phase, and the total panel
Live feed per circuit, via breaker, for emergency lighting connection


July 2015

SC-UN ­ Universal Source Controllers  

Specifications

Mechanical Programming Interfacing
Standards

No regular maintenance requirements due to natural convection cooling, i.e. no fans or filters
Single circuit dimmer card
Wall mounted design
An LCD graphical user interface and keypad for ease of programming and configuration. The interface can be used for programming single area systems there is no need to use a PC. The GUI also allows programming of the astronomical timeclock.
All SC-UN Source Controllers have RS485 and Ethernet over UDP connections to allow for control by third party systems (Building Management System, Audio/Visual, etc.) through the use of open protocol ASCII message commands
Two contact closure inputs for integration with auxiliary equipment and emergency lighting input
DMX512 input for control by entertainment systems
Power metering information is available via Ethernet over UDP through the use of open protocol ASCII message commands

37.2 in. (945 mm)

Dimensions
(Inches/mm)
6 Circuit 20.3 in. (517 mm)
6 Channel
12 Circuit 20.3 in. (517 mm)

7.6 in. (193 mm)
7.6 in. (193 mm)

24 Circuit
27.8 in. (707 mm)

37.2 in. (945 mm) 56.7 in. (1440 mm) 56.7 in. (1440 mm)

Load Types

6 Circuit
20.3 in. (517 mm)

Incandescent

Magnetic and Forward Phase electronic low voltage - Factory Approved Transformer only.

Neon / cold cathode

Non-dim (switched)

Analog fluorescent ballast control

-- 2-wire fluorescent loads

-- 3-wire fluorescent loads (Lutron ECO-10 and Hi-Lume)

-- 4-wire fluorescent loads, 0-10 VDC Isolated (40 µA max per

circuit leakage to line)

6 Channel

Each 0-10V output supports up to 50 ballasts/driver1s2tChairtcudirtaw the

standard 2mA each

20.3 in.

(517 mm)

7.6 in. (193 mm)
7.6 in. (193 mm)

12 Channel
24 Circuit 27.8 in. (707 mm)

7.6 in. (193 mm)

18 & 24 Channe

56.7 in. (1440 mm) 56.7 in. (1440 mm)

2

www.eaton.com/lightingsystems

12 Channel

18 & 24 Channel

SC-UN ­ Universal Source Controllers  
Wiring Diagram

POWER FEED 120V and 277V options, Single
or 3 Phase options

LOAD WIRING

DIMMING NON-DIM / SWITCHED 2-WIRE FLUORESCENT 3-WIRE FLUORESCENT

Feed Wiring
Applicaiton
24 Channel 3-phase Panel
Phase Neutral Earth
12 Channel 3-phase Panel
Phase Neutral Earth
12 Channel 1-phase Panel
Phase Neutral Earth

Wire Range (AWG)
4/0-6 350 MCM - 6 2-14
2/0-12 2/0-12 2-14
350 MCM - 6 350 MCM - 6 2-14

ETHERNET LINK RS485 DMX IN
SWITCH INPUT 1 SWITCH INPUT 2

0-10V for 4-WIRE for Dimmable Fluorescent, LED's, HID

iCANnet iCANnet
iCANnet cable type ­ Cooper LCCNP (Non Plenum) Cable or LCCP (Plenum) or Belden 1502R (Non Plenum) or 1502P (Plenum).
Each Source Controller can power up to 10 wallstations/devices. For more than 10 wallstations/devices per Source Controller add a 15 VDC External Power Supply. Wallstations/devices must be within 1,000 ft. of the Source Controller.
For wallstations/devices further from a Source Controller add a 15 VDC External Power Supply. 100 Devices per physical segment on iCANnet, maximum segment distance of 1000m/3200ft. A BN-2-NA can be added to combine more than 100 devices together (up to 65,000 total) and to extend network cable distance.

Applicaiton
6 Channel 3-phase Panel
Phase Neutral Earth
6 Channel 3-phase Panel
Phase Neutral Earth

Maximum BTU Dissipation

6 Circuit Unit 12 Circuit Unit 24 Circuit Unit

1050 BTU @ 100% 2100 BTU @ 100% 4200 BTU @ 100%

Wire Range (AWG)
2/0-12 2/0-12 2-14
2/0-14 2/0-14 2-14


July 2015
Amp Rating per Pole
128 192 N/A
64 96 N/A
192 288 N/A
Amp Rating per Pole
32 48 N/A
69 144 N/A

www.eaton.com/lightingsystems

3


July 2015

SC-UN ­ Universal Source Controllers  

Sample System Topology

DRY CONTACT CLOSURE

LOCAL PC

REMOTE PC SC277-12-UN-3P-ML-20

INTERNET

ROUTER

LAPTOP

SECURITY OCCUPANCY

AV

SYSTEM SENSOR COMPONENTS

WiFi

ETHERNET

CLS-4TSB-RL-W-IR
Scene 1 Scene 2 Scene 3 Scene 4

UIG-2-NA

RS232

SI-2-NA

Each Source Controller can power up to 10 wallstations/devices. These devices must be within 1000ft of the Source Controller.
For devices further from a Source Controller add a 15 VDC power supply. 100 devices/addresses per physical segment on iCANnet (BN-2-NA can be added
to combine more than 100 devices together, up to 65,000 total)

SC277-24-UN-3P-ML-20

TUNGSTEN DISCHARGE

DMX OUTPUT CONSOLE BY ZERO 88 OR OTHERS
DMX512

2, 3 & 4 WIRE FLUORESCENT
COLD CATHODE
COLOR CHANGING FIXTURES

DRY CONTACT CLOSURE

CONTACT CLOSURE INPUT

CLS-3TLB-W-IR
Scene 1 Scene 2 Scene 3
HH17IR

CLS-1TLB-W-IR
Scene 1

iCANnet
Cable type - Cooper LCCNP (NON PLENUM) OR Cooper LCCP (PLENUM) Cable or BeldenTM 1502R (NON PLENUM) or 1502P (PLENUM) Maximum segement distance of 1000m/3200ft per segment

SC120-12-UN-1P-ML-20

CRESTRON AMX

RS485
Contact closure input

TUNGSTEN
DISCHARGE
2, 3 & 4 WIRE FLUORESCENT COLD CATHODE
COLOR CHANGING FIXTURES

CLV-44-RL-W-IR

CLV-40-RL-W-IR CLV-44Z-RL-W-IR

HH17IR

Each Source Controller can power up to 10 wallstations/devices. These devices must be within 1000ft of the Source Controller.
For devices further from a Source Controller add a 15 VDC power supply. 100 devices/addresses per physical segment on iCANnet (BN-2-NA can be added
to combine more than 100 devices together, up to 65,000 total)

SC120-06-UN-1P-ML-20

TUNGSTEN
DISCHARGE
2, 3 & 4 WIRE FLUORESCENT
COLD CATHODE
COLOR CHANGING FIXTURES
TSC-30-SS-NA
9Vdc SUPPLY

NS3-C Combination
Sensor

iCANnet
Cable type - Cooper LCCNP (NON PLENUM) OR Cooper LCCP (PLENUM) Cable or BeldenTM 1502R (NON PLENUM) or 1502P (PLENUM) Maximum segement distance of 1000m/3200ft per segment

TUNGSTEN
DISCHARGE
2, 3 & 4 WIRE FLUORESCENT COLD CATHODE
COLOR CHANGING FIXTURES

Ordering
Catalog #
SC120-06-UN-1P-ML-20 SC120-12-UN-1P-ML-20 SC120-06-UN-3P-ML-20 SC120-12-UN-3P-ML-20 SC120-24-UN-3P-ML-20 SC277-06-UN-1P-ML-20 SC277-06-UN-3P-ML-20 SC277-12-UN-3P-ML-20 SC277-24-UN-3P-ML-20

Description
Universal 120V Cabinet with 6 Circuits for Most Loads, Single Phase, Main Lugs, 16A per Circuit
Universal 120V Cabinet with 12 Circuits for Most Loads, Single Phase, Main Lugs, 16A per Circuit
Universal 120V Cabinet with 6 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit
Universal 120V Cabinet with 12 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit
Universal 120V Cabinet with 24 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit
Universal 277V Cabinet with 6 Circuits for Most Loads, Single Phase, Main Lugs, 16A per Circuit
Universal 277V Cabinet with 6 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit
Universal 277V Cabinet with 12 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit
Universal 277V Cabinet with 24 Circuits for Most Loads, 3 Phase, Main Lugs, 16A per Circuit

SC - 120 - 12 - UN - 1P - ML - 20

Product SC Source Controller
Voltage 120V, 277V
Number of Circuits
Source Controller Type UN = All Loads

Branch Breaker Rating (Amps)
Panel Feed ML = Main Lugs
Phase 1P = Single Phase 3P = 3 Phase

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
Eaton Lighting systems 203 Cooper Circle Peachtree City, GA 30269 www.eaton.com/lightingsystems
© 2015 Eaton All Rights Reserved Printed in USA Publication No. TD503022EN July 10, 2015

Eaton is a registered trademark.
All other trademarks are property of their respective owners.


Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)