SCCR ratings for contactors in combination
xt-ul-short-circuit-current-ratings-td03407003e Technical Data TD03407003E
Effective August 2016 Supersedes January 2010
XT UL short-circuit
current ratings
Changes to UL 508A and the NEC in recent years have brought a focus to control panel safety with regard to short-circuit current ratings (SCCR). Eaton's XT line of IEC power control has a wide variety of SCCR solutions for a variety of applications and SCCR needs. The SCCR data provided in this document reflects the latest information as of July 2016.
Contents
Description
Page
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Fusecontactor high fault . . . . . . . . . . . . . . . . . . . 2 Breakercontactor high fault . . . . . . . . . . . . . . . . . 3 Fusecontactorthermal overload relay high fault. . . . . . . . . . . . . . . . . . . . . 4 Breakercontactorthermal overload relay high fault. . . . . . . . . . . . . . . . . . . . . 5 Breaker--electronic overload . . . . . . . . . . . . . . . . 6 Fuseelectronic overload . . . . . . . . . . . . . . . . . . . . 6 Manual motor controllers . . . . . . . . . . . . . . . . . . . 7 Combination motor controllers . . . . . . . . . . . . . . . 8 Manual self-protected motor starters-- UL 508 Type E . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Motor protective circuit breaker . . . . . . . . . . . . . 10
Table 1. Summary
Components
Fusecontactor Breakercontactor Fusecontactorthermal overload relay Breakercontactorthermal overload relay Manual motor controller Combination motor controllers Motor protective circuit breakercontactor Fuse--electronic motor starter
240 V SCCR
Up to 100 kA Up to 100 kA Up to 100 kA Up to 65 kA Up to 65 kA Up to 65 kA Up to 65 kA Up to 100 kA
For additional information, please visit our websites: Eaton.com/XT Eaton.com/SCCR
480 V SCCR
Up to 100 kA Up to 100 kA Up to 100 kA Up to 65 kA Up to 65 kA Up to 65 kA Up to 65 kA Up to 100 kA
600 V SCCR
Up to 100 kA Up to 85 kA Up to 100 kA -- Up to 50 kA Up to 50 kA -- Up to 100 kA
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Table 2. Fusecontactor high fault
XT part number
kA (600 Vac)
XTCE007B
100
XTCE009B
100
XTCE012B
100
XTCE015B
100
XTCE018C
100
XTCE025C
100
XTCE032C
100
XTCE040D
100
XTCE050D
100
XTCE065D
100
XTCE080F
100
XTCE095F
100
XTCE115G
100
XTCE150G
100
XTCE170G
100
XTCE(S)185H
100
XTCE(S)225H
100
XTCE(S)250L
18
XTCE(S)300L
18
XTCE(S)400M
100
XTCE(S)500M
100
XTCE580N
85
XTCE650N
85
XTCE750N
85
XTCE820N
85
XTCEC10N
85
XTCEC16
85
Fuse class
J J J J J J J J J J J J J J J J J L L J J
Max. upstream fuse ampere rating
20 20 45 60 70 100 125 150 150 150 300 300 300 600 600 600 600 700 800 600 600 2000 2000 2000 2000 2000 2000
2
EATON www.eaton.com
XT UL short-circuit current ratings
Technical Data TD03407003E
Effective August 2016
Table 3. Breakercontactor high fault
XT part number
XTCE007B XTCE009B XTCE018C XTCE025C XTCE032C XTCE040D XTCE050D XTCE065D XTCE080F XTCE095F XTCE115G XTCE150G XTCE170G XTCE(S)185H XTCE(S)225H XTCE(S)250L XTCE(S)300L XTCE(S)400M XTCE(S)500M XTCE580N XTCE650N XTCE750N XTCE820N XTCEC10N
kA (480 Vac)
65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 100 100 85 85 85 85 85
Max. upstream breaker ampere rating
16 16 32 32 32 100 100 100 250 250 250 250 250 350 350 250 250 600 600 1200 1200 1200 1200 1200
kA (600 Vac)
10/22 10/22 10/22 30 30 30 30 30 30 30 30 18/50 18/50 18 18 30 30 85 85 85 85 85
High-fault rating combination can be utilized with any series breaker as long as the maximum ampacity coincides with the table and the breaker carries an equivalent kA rating, such as 65 kA.
Max. upstream breaker ampere rating
50/32 50/32 50/32 250 250 250 250 250 250 250 250 600/350 600/350 600 600 600 600 1200 1200 1200 1200 1200
EATON www.eaton.com
3
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Table 4. Fusecontactorthermal overload relay high fault
Contactor catalog number
Overload relay catalog number
High fault current kA (600 Vac)
XTCE007B
XTOBP40BC1
100
XTCE007B
XTOBP60BC1
100
XTCE007B
XTOB001BC1
100
XTCE007B
XTOB001BC1
100
XTCE007B
XTOB1P6BC1
100
XTCE007B
XTOB2P4BC1
100
XTCE007B
XTOB004BC1
100
XTCE007B
XTOB004BC1
100
XTCE007B
XTOB006BC1
100
XTCE009B
XTOB010BC1
100
XTCE015B
XTOB016BC1
100
XTCE018C
XTOB016CC1
100
XTCE025C
XTOB024CC1
100
XTCE032C
XTOB032CC1
100
XTCE040D
XTOB040DC1
100
XTCE050D
XTOB057DC1
100
XTCE050D
XTOB057DC1
100
XTCE065D
XTOB065DC1
100
XTCE080F
XTOB100GC1
100
XTCE095F
XTOB100GC1
100
XTCE150G
XTOB125GC1
100
XTCE150G
XTOB150GC1
100
Class J fuse size
1 1 1 1 3 3 3 6 10 15 30 35 45 60 60 90 110 125 150 200 250 300
Class CC fuse size
1 1 1 1 3 3 3 6 10 15 30
4
EATON www.eaton.com
XT UL short-circuit current ratings
Technical Data TD03407003E
Effective August 2016
Table 5. Breakercontactorthermal overload relay high fault
Contactor catalog number
Overload catalog number
UL 508 high fault rating (kA)
208 Vac
240 Vac
XTCE018C
XTOB1P6C
65
65
XTCE018C
XTOB2P4C
65
65
XTCE018C
XTOBP40C
65
65
XTCE018C
XTOBP60C
65
65
XTCE018C
XTOB001C
65
65
XTCE018C
XTOB004C
65
65
XTCE018C
XTOB006C
65
65
XTCE018C
XTOB010C
65
65
XTCE018C
XTOB016C
65
65
XTCE018C
XTOB024C
65
65
XTCE025C
XTOB024C
65
65
XTCE025C
XTOB032C
65
65
XTCE032C
XTOB032C
65
65
XTCE040D
XTOB010D
65
65
XTCE040D
XTOB016D
65
65
XTCE040D
XTOB024D
65
65
XTCE040D
XTOB040D
65
65
XTCE050D
XTOB057D
65
65
XTCE065D
XTOB065D
65
65
XTCE072D
XTOB075D
65
65
XTCE080F
XTOB035G
65
65
XTCE080F
XTOB050G
65
65
XTCE080F
XTOB070G
65
65
XTCE080F
XTOB100G
65
65
XTCE095F
XTOB100G
65
65
XTCE115G
XTOB125G
65
65
XTCE150G
XTOB150G
65
65
XTCE170G
XTOB175G
65
65
480 Vac
65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65
100 kA achievable at 208480 Vac and 50 kA at 600 Vac with use of current-limiting breaker, reference UL file E51580 V1 S29, confirm devices in protective suites.
Max. breaker size ampere rating
15 15 15 15 15 15 15 20 25 35 35 50 50 15 25 50 60 75 100 100 90 125 175 250 250 200 250 250
EATON www.eaton.com
5
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Table 6. Breakerelectronic overload
Overload catalog number
High fault rating (kA) 480 V
XTOE005
100
XTOE020
100
XTOE045
100
XTOE100
50
XTOE140
100
XTOE175
100
600 V
35 35 35 50 65 65
Max. breaker size ampere rating
20 80 175 250 400 400
Table 7. Fuse--electronic overload
Overload catalog number
High fault rating (kA) 480 V
XTOE005
100
XTOE020
100
XTOE045
100
XTOE100
100
XTOE140
100
XTOE175
100
600 V
100 100 100 100 100 100
Max. fuse size ampere rating
30 100 100 200 400 500
6
EATON www.eaton.com
XT UL short-circuit current ratings
Technical Data TD03407003E
Effective August 2016
Table 8. Manual motor controllers (manual motor protector + contactor) for use in group motor applications
XTSC and XTSR manual motor controllers (MMC)/starter combinations Group installation, UL/CSA
Assembled controller Non-reversing Reversing
FLA adjustment range/overload r(aemlepaseere--sI)r
Short-circuit (raemlepaseere--sI)rm
XTSC and XTSR Frame B MMP + Frame B contactor
XTSCP16BB_ XTSRP16BB_ 0.10.16
2.2
XTSCP25BB_ XTSRP25BB_ 0.160.25
3.5
XTSCP40BB_ XTSRP40BB_ 0.250.4
5.6
XTSCP63BB_ XTSRP63BB_ 0.40.36
8.82
XTSC001BB_ XTSR001BB_ 0.361
14.0
XTSC1P6BB_ XTSR1P6BB_ 11.6
22.4
XTSC2P5BB_ XTSR2P5BB_ 1.62.5
35
XTSC004BB_ XTSR004BB_ 2.54
56
XTSC6P3BB_ XTSR6P3BB_ 46.3
88.2
XTSC010BB_ XTSR010BB_ 6.310
140
XTSC012BB_ XTSR012BB_ 812
168
XTSC and XTSR Frame B MMP + Frame C contactor
XTSC016BC_ XTSR016BC_ 1016
224
XTSC020BC_ XTSR020BC_ 1620
280
XTSC025BC_ XTSR025BC_ 2025
350
XTSC032BC_ XTSR032BC_ 2532
448
XTSC and XTSR Frame D MMP + Frame C contactor
XTSC016DC_ XTSR016DC_ 1016
224
XTSC025DC_ XTSR025DC_ 1625
350
XTSC032DC_ XTSR032DC_ 2532
448
XTSC and XTSR Frame D MMP + Frame D contactor
XTSC040DD_ XTSR040DD_ 3240
560
XTSC050DD_ XTSR050DD_ 4050
700
XTSC058DD_ XTSR058DD_ 5058
812
XTSC063DD_ XTSR063DD_ 5863
882
Underscore (_) indicates magnetic coil suffix required.
Max. rms symmetrical short-circuit ratings (kA)
240 V
480 V
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
42
42
18
18
18
18
18
18
65
65
65
65
65
65
65
65
65
65
65
65
65
65
600 V
50 50 50 50 50 50 50 50 50 22 22
50 18 18 18
22 22 22
22 22 22
Max. upstream protective device (A/A with current limiter)
Max. fuse 600 V
Max. circuit breaker 600 V
600 600 600 600 600 600 600 600 600 10/600 10/600
600 600 600 600 600 600 600 600 600 15/600 15/600
10/600 10/600 10/600 10/600
10/600 15/600 15/600 15/600
600
600
600
600
600
600
600
600
600
600
EATON www.eaton.com
7
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Table 9. Combination motor controllers (line side adapter + manual motor protector + contactor) UL 508 Type F self-protected
XTFC and XTFR combination motor controllers (CMC), UL 508 Type F
Assembled controller
Non-reversing
Reversing
(FaLmApaedrejuss) tment--Ir
XTFCP16BB_
XTFRP16BB_
0.10.16
XTFCP25BB_
XTFRP25BB_
0.160.25
XTFCP40BB_
XTFRP40BB_
0.250.4
XTFCP63BB_
XTFRP40BB_
0.40.63
XTFC001BB_
XTFRP63BB_
0.631
XTFC1P6BB_
XTFR1P6BB_
11.6
XTFC2P5BB_
XTFR2P5BB_
1.62.5
XTFC001BB_
XTFR004BB_
2.54.0
XTFC6P3BB_
XTFR6P3BB_
4.06.3
XTFC010BB_
XTFR010BB_
6.310
XTFC012BB_
XTFR012BB_
812
XTFC016BB_
--
1016
XTFC and XTFR Frame B MMP + Frame C contactor
XTFC016BC_
XTFR016BC_
1016
XTFC020BC_
XTFR020BC_
1620
XTFC025BC_
XTFR025BC_
2025
XTFC032BC_
XTFR032BC_
2532
XTFC and XTFR Frame D MMP + Frame C contactor
XTFC016DC_
XTFR016DC_
1016
XTFC025DC_
XTFR025DC_
1625
XTFC032DC_
XTFR032DC_
2532
XTFC and XTFR Frame D MMP + Frame D contactor
XTFC040DD_
XTFR040DD_
3240
XTFC050DD_
XTFR050DD_
4050
XTFC058DD_
XTFR058DD_
5058
XTFC063DD_
XTFR063DD_
5565
Short-circuit r(aemlepaesere--sI)rm
2.2 3.5 5.6 8.82 14 22.4 35 56 88.2 140 168 224
224 280 350 448
224 350 448
560 700 812 882
UL 508 Type F application
Max. rms symmetrical short-circuit ratings (kA)
240 V
480 V
600 V
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
65
65
18
18
18
--
18
18
--
18
18
--
18
18
--
18
18
--
65
65
30
65
65
30
65
65
50
65
65
50
65
65
65
65
65
65
Underscore (_) indicates magnetic Coil Suffix required. For UL 508 Type F applications, the combination motor controller assembly does not require a dedicated upstream protective device in the panel, thus a maximum rating is not required. For 65 kA UL rating, use Type E rating with contactor.
Note: A Type F combination motor controller consists of a Type E manual self-protected motor controller and a magnetic motor controller.
8
EATON www.eaton.com
XT UL short-circuit current ratings
Technical Data TD03407003E
Effective August 2016
Table 10. Manual self-protected motor starters--UL 508 Type E
XTPR minimum
XTPR maximum
FLA adjustment--I
(amperes)
r
Frame B MMP + line side adapter XTPAXLSA
XTPRP16BC1_ XTPR004BC1_ 04 A
XTPR6P3BC1_ XTPR010BC1_ 6.310 A
XTPR012BC1_
12 A
XTPR016BC1_
16 A
XTPR020BC1_ XTPR032BC1_ 2032 A
Frame D MMP + line side adapter XTPAXLSAD
XTPR016DC1_ XTPR032DC1_ 1632 A
XTPR040DC1_
40 A
XTPR050DC1_
50 A
XTPR058DC1_
58 A
XTPR063DC1_
240 V
65 65 65 42 18
65 65 65 65 65
480 V
65 65 65 42 18
65 65 65 65 65
600 V
50 50 18 -- --
25 25 25 25 25
Contactor frame sizes With contactor
XTCE007B-015B XTCE007B-015B XTCE007B-015B XTCE018C-032C --
With contactor
XTCE018C-32C XTCE040D-65D XTCE050D-65D XTCE065D --
For UL 508 Type E applications, the assembly does not require a dedicated upstream protective device in the panel, thus a maximum rating is not required. Underscore (_) indicates magnetic coil suffix required.
240 V
65 65 65 65 --
65 65 65 65 --
Most of the XTPR manual motor protectors are UL listed as a manual Type E self-protected motor controller. The critical test for self-protected motor starters is to perform 6000 electrical operations and an additional 4000 mechanical operations after a short circuit.
A combination of a manual self-protected motor starter and contactor can be listed as a Type E self-protected combination motor controller if it passes this test. This means a weld-free performance to meet the additional life requirements. The Type E + contactor can be used as an alternative to the Type F rating.
480 V
65 65 65 65 --
65 65 65 65 --
600 V
-- -- -- -- --
-- -- -- -- --
EATON www.eaton.com
9
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Table 11. Motor protective circuit breakercontactor high fault ratings
Contactor
Motor protective circuit breaker
UL 508 high fault rating (kA)
240 Vac
480 Vac
XTCE...D...
FDMP
65
35
XTCE...D...
HFDMP
65
65
XTCE...F...
FDMP
65
35
XTCE...F...
HFDMP
65
65
XTCE...G...
FDMP
65
35
XTCE...G...
HFDMP
65
65
XTCS...L...
FDMP
65
35
XTCE...L...
FDMP
65
35
XTCS...L...
HFDMP
65
65
XTCE...L...
HFDMP
65
65
XTCS...L...
JGMPS
65
35
XTCE...L...
JGMPS
65
35
XTCS...L...
JGMPH
65
65
XTCE...L...
JGMPH
65
65
XTCS...M...
LGMPS
42
42
XTCE...M...
LGMPS
42
42
Max. breaker size ampere rating
100 100 205 205 205 205 205 205 205 205 250 250 250 250 600 600
10
EATON www.eaton.com
XT UL short-circuit current ratings
Technical Data TD03407003E
Effective August 2016
EATON www.eaton.com
11
Technical Data TD03407003E
Effective August 2016
XT UL short-circuit current ratings
Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
© 2016 Eaton All Rights Reserved Printed in USA Publication No. TD03407003E / Z18362 August 2016