Delta UNOnext: Protect Your Health, Starting from Indoor Air Quality
Connected. Smart. Healthy
Product Overview
The UNOnext Indoor Air Quality Monitor continuously monitors real-time data for seven types of harmful indoor air factors. The detection range includes Carbon Monoxide (CO), Carbon Dioxide (CO2), Fine Suspended Particulates (PM2.5), and Suspended Particulates (PM10), Formaldehyde (HCHO), Ozone (O3), Total Volatile Organic Compounds (TVOC), and Temperature, Humidity, and Illuminance.
UNOnext not only functions as a detection device but can also independently link ventilation equipment or integrate with central air conditioning. When indoor air quality deteriorates, UNOnext immediately triggers an alarm and introduces fresh air to eliminate poor indoor air. Its innovative design also contributes positively to LEED green building standards and WELL healthy building standards.
Key Features
- Accurately detects indoor air factors harmful to health, supported by third-party laboratory inspection certificates and annual calibration services.
- Plug-and-play functionality for quick browsing of real-time indoor environment information.
- Provides historical data trends and index analysis with cloud data storage.
- Smart-linked HVAC/fresh air systems enhance overall air quality.
System Diagram
The UNOnext system can be integrated with various components for comprehensive air quality management. This includes:
- UNOnext App: For monitoring via Bluetooth/WiFi.
- UNOweb & UNOcentral: IAQ management platforms accessible via WiFi and the internet.
- Connectivity: Supports Modbus RTU, TCP/IP, BACnet MS/TP, and BACnet IP for integration with Central HVAC systems.
- Ventilation Integration: Connects with HVAC control systems, Delta's positive/negative pressure ventilation, energy recovery ventilation, and third-party fresh air devices.
Monitor Specifications
Item | Measurement Range | Accuracy |
---|---|---|
Temperature | 0-50°C | ± 1°C |
Humidity | 0-100% rH | ± 5% |
CO2 | 400-10000 ppm | ± 30 ppm ± 3% |
PM2.5 | 0-1000 ug/m³ | 0-100 ug/m³ ± 10 ug/m³, 100-1000 ug/m³ ± 10% |
PM10 | 0-1000 ug/m³ | 0-100 ug/m³ ± 25 ug/m³, 100-1000 ug/m³ ± 25% |
Luminance | 0-10000 lux | For ambient light reference |
HCHO | 0-5000 ppb | ± 15% |
CO | 0-1000 ppm | ± 20ppm or ± 5% |
O3 | 0.5-10 ppm | 0.01 ppm |
TVOC | 0-30000 ppb | ± 15% in lab test (Ethanol) |
Ext. temp. | NTC10k Thermistor | ± 0.3°C |
System Specifications
Item | Specification |
---|---|
Operation range | 0°C to 50°C, 10-90% RH, IP20 |
Storage temp. | -20°C to 70°C |
Power requirements | Input 1: 9-24VDC+/-10%; Input 2: power adapter 12V/1A |
Power consumption | Max 500mA@12VDC |
Digital Control | RS485 or DO (low active) |
Dimensions | 14.2cm(L) x 6.8cm(W) x 4.2 cm(D) |
Weight | 208 g |
Display | 1.3" OLED |
Accessories | Wall Mount, Power Adapter, NTC thermistor (Optional) |
Language | Chinese, English, Japan |
Connectivity | RS485, Wi-Fi 2.4G 802.11 b/g/n, BLE5.1 |
Security | Open, WPA-PSK, WPA2-PSK |
Certification | CE, FCC/IC, NCC, JRF, WPC/ETA, SIRIM, IMDA, NBTC, VNTA |
Model Compatibility
Model | Temp./Humid. | PM2.5/PM10 | CO2 | Lux | TVOC | HCHO | CO | O3* | BLE | Wi-Fi | BACnet MS/TP | Modbus RTU | Ventilation equipment control |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
UNO-7TB | ● | ● | ● | ● | ● | ● | |||||||
UNO-6SW | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ||
UNO-7HW | ● | ● | ● | ● | ● | ● | ● | ||||||
UNO-9SW | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● |
UNO-10SW | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● | ● (Made to order) |