Overview
UNOlite is an indoor air quality monitor to measure the space temperature / humidity / CO2 / PM2.5 / PM10 / PM1 / TVOC and expose the measurements directly onto a BACnet MS/TP or Modbus RTU network. Moreover, the measurements are also accessible with UNO apps through BLE or UNO web through Wi-Fi (Wi-Fi model). Please refer to UNOlite official website for more information. This document is primarily concerned how to add UNOlite to Modbus/RTU network.
1

Hardware Interface

Key

Description

Hardware reset

Push this button will trigger a power cycle.

Factory reset

After booting, press this button three times within 2 seconds will trigger factory reset. The values below will be restored to default:
 Modbus baudrate  BACnet saved mac address  Wi-Fi MQTT broker setting (Wi-Fi model)

NOTE: It's recommended to use a paper clip to press the keys.

2

Terminal V+ VA+ BGND

Description
Power input. For more information, please refer to production specification.
Power input. For more information, please refer to production specification.
RS485(+) data pin. For Modbus/BACnet network.
RS485(-) data pin. For Modbus/BACnet network.
Ground terminal. Each RS485 driver in an installation is recommended to connect to the same ground to get a common reference.

DIPs

Description

ON OFF

1 - 6

Refer to the later sections for the definition of each pin



BACnet mode switch.

7

ON : BACnet mode



OFF : Modbus mode

8

RS485 terminator resistor (120 ohm)



NOTE: The dips should be adjusted to proper position in power off state. Adjust the dips, then power on device.

3

Modbus Mode

UNOlite follows Modbus over serial line specification and will run on Modbus/RTU mode if the 7th pin is set to OFF state.
The definition of the dips in Modbus mode as listed below:

DIP

Description

ON OFF

1

Modbus slave address (check address table)



2

Modbus slave address (check address table)



3

Modbus slave address (check address table)



4

Modbus slave address (check address table)



5

Modbus slave address (check address table)



NOTE: The definitions of dip are different from Modbus mode. Please make sure which mode is chosen.
NOTE: Pin6 is not defined in Modbus mode

Serial Configuration
UNOlite can directly connect to a controller with RS485 interface, up to 32 UNOlite devices can be joined to a Modbus serial bus.

NOTE: Suggestion to use 22AWG shielded twisted pair cable to connect devices in sequence
4

Default Serial Configuration:  Baud: 9600  Data-Bit: 8  Parity: None  Stop-Bit: 1 Note: perform factory reset to restore default value if configuration is missing
Modbus Slave Address
The DIP pins 1~5 represent for binary number 0~31, pin 1 is most significant bit (MSB) and pin 5 is least significant bit (LSB). Notice that Modbus slave address starts from 208, therefore, UNOlite can be configured address from 208 to 239:

DIP pin

Modbus Slave

DIP pin

Modbus Slave

1 2345

Addr

1 2345

Addr

     208 (0xD0)

     224 (0xE0)

     209 (0xD1)

     225 (0xE1)

     210 (0xD2)

     226 (0xE2)

     211 (0xD3)

     227 (0xE3)

     212 (0xD4)

     228 (0xE4)

     213 (0xD5)

     229 (0xE5)

     214 (0xD6)

     230 (0xE6)

     215 (0xD7)

     231 (0xE7)

     216 (0xD8)

     232 (0xE8)

     217 (0xD9)

     233 (0xE9)

     218 (0xDA)

     234 (0xEA)

     219 (0xDB)

     235 (0xEB)

     220 (0xDC)

     236 (0xEC)

     221 (0xDD)

     237 (0xED)

     222 (0xDE)

     238 (0xED)

     223 (0xDF)

     239 (0xEF)

5

Modbus Read Data

UNOlite supports function code both 0x03 and 0x04 to read following registers 0x03: read holding registers 0x04: read input registers Request

Slave Address

Function code

Register

Length [N]

CRC16

1 byte

1 byte

2 bytes

2 bytes

2 bytes

Response

Slave Address

Function code

Count [2*N]

Data

CRC16

1 byte

1 byte

1 byte

N * 2 bytes

2 bytes

Sensor Measurement

Register

Name

Description

30001 0x0000 IAQ index

Give an index according to current PM2.5, PM10, and CO2 concentration. The index also be referenced by IAQ LED:
GREEN: 0~80 YELLOW: 81~100 RED: 101~400 PURPLE: 401~

30002 0x0001 Concentration of PM2.5

Unit: g/m3

30003 0x0002 Concentration of PM10

Unit: g/m3

30004 30005 30006

0x0003 0x0004 0x0005

Concentration of carbon dioxide (formula CO2)

Unit: ppm

Concentration of total volatile organic compound (TVOC)

Unit: ppb

Concentration of total volatile organic compound (TVOC)

Unit: g/m3 (factor 1 ppb = 4.5 g/m3)

30009 0x0008 Humidity

Unit: 0.01%

30011 0x000A Celsius temperature 30018 0x0011 Fahrenheit temperature

Real Temp = (Value - 4500) * 0.01 Unit: °C Real Temp = (Value - 4500) * 0.01 Unit: °F

6

30020 0x0013 Concentration of PM1

Unit: g/m3

Register

Name

30033 0x0020 PM2.5 sensor

Sensor State

Description

30034 0x0021 PM10 sensor 30035 0x0022 CO2 sensor 30036 0x0023 TVOC sensor 30037 0x0024 Humidity sensor 30038 0x0025 Temperature sensor

State of sensor hardware module 0x0000: Power off or does not exist 0x0001: Sensor Ready 0x0002: Warming up 0x0003: Busy 0x00FE: CSERROR 0x00FF: FAIL

30042 0x0029 PM1 sensor 30044 0x002B IAQ LED state

0x0000: LED off 0x0001: LED on

Device Information

Register

Name

30145

0x0090- Model and Product Serial 0x009F Number

30209 0x00D0 Main firmware version

30257 30260

0x01000x0102 0x01030x0105

BT MAC address WIFI MAC address

Description An ASCII string consists model name and serial number, separated by a comma. For example: "UNO-L,2250L01F9999" Number 1 to 65535 0x0000: device is initializing 6 groups of two hexadecimal digits, e.g. F2:11:8F:36:F6:93
6 groups of two hexadecimal digits

7

Modbus Write Command
UNOlite supports function code 0x06 and 0x10 to write request

0x06: write single register

Address 1 byte

Function code 1 byte

Address 1 byte

Function code 1 byte

Request Register 2 bytes Response Register 2 bytes

Data 2 bytes
Data 2 bytes

CRC16 2 bytes
CRC16 2 bytes

0x10: write multiple registers

Address 1 byte

Fn. Code 1 byte

Register 2 bytes

Address 1 byte

Function code 1 byte

Request Length[N]
2 bytes Response
Register 2 bytes

Count[2*N]

Data

1 byte

N * 2 bytes

CRC16 2 bytes

Length [N] 2 bytes

CRC16 2 bytes

Device Information

Register

Name

40012 0x000B Temperature calibration

40097

0x00600x0062

Serial configuration

Description

0~9998: directly set Celsius temperature from

0°C to 99.98°C

9999: reset to default

Data format:

1st word

2nd word

0x60

0x61

First 4 bytes are baud:

3rd word 0x62

1200 2400 4800 9600

19200 38400 57600 115200 (bps)

0x62 format:

3rd word

Hi byte

Lo byte

Bit7-4 Bit3-0 Bit7-4 Bit3-0

Databit Parity Stopbit Presets

Databit:

0x8 (RTU)

8

40215 0x00D6 UNOlite operation

Parity: 0x0 (Even) 0x1 (Odd) 0x04 (None)
Stopbit: 0x0(1 bit) 0x1(2 bits)
Preset: other parameters are ignored if preset bits is assigned.
0: Use baud/databit/parity/stopbit params. 1: 9600 8 N 1 (default) 2: 9600 8 N 2 3. 9600 8 E 1 4. 19200 8 N 1 5: 19200 8 N 2 6: 19200 8 E 1 Data Examples (hexadecimal): [00 00 25 80 84 10]: set to 9600 8 N 2 [00 00 00 00 00 02]: set to 9600 8 N 2 0x0010: perform factory reset (equivalent to press function key 3 times)

Modbus Examples

1. Read all sensor status from device 208 (0xD0)

Request

D0 03 00 20 00 0B 17 86

Response D0 03 16 00 01 00 01 00 01 00 01 00 01 00 01 00 FE 00 FE 00 FF 00

00 00 01 60 8F

2. Read firmware version from device 208 (0xD0)

Request

D0 03 00 D0 00 01 97 B2

Response D0 03 02 00 04 45 95

3. Set rs485 serial configuration, 115200-8-N-1

Request

D0 10 00 60 00 03 06 00 01 C2 00 84 00 BB 56

Response D0 10 00 60 00 03 92 57

9

Modbus Exception Response
If device receives a request message without a communication error, but cannot handle the query. It will reply with requested function code plus 0x80. Example, function code 0x3 becomes 0x83

Address 1 byte

Function code 1 byte

Code 1 bytes

CRC16 2 bytes

Code

Name

0x01

ILLEGAL FUNCTION

0x02

ILLEGAL DATA ADDRESS

0x03

ILLEGAL DATA VALUE

0x04

SERVER DEVICE FAILURE

0x05

ACKNOWLEDGE

0x06

SERVER DEVICE BUSY

0x08

MEMORY PARITY ERROR

0x0A

GATEWAY PATH UNAVAILABLE

0x0B

GATEWAY TARGET DEVICE FAILED TO RESPOND

Note: Please refer to "Modbus_Application_Protocol_V1_1b3" from www.modbus.org