Toshiba Carrier VRF Outdoor Unit MMY-MUP1201FT9P-UL - Heat Recovery
This document provides submittal data for the Toshiba Carrier VRF Outdoor Unit, Model MMY-MUP1201FT9P-UL, featuring heat recovery capabilities.
Submittal Data
Job Name: ______________________________
Location: ______________________________
Tag: _______________________
Heat Recovery Features
- Modules and pairings available from 6 to 30 tons.
- Modules feature inverter-driven scroll compressors.
- Direct-drive, inverter-driven outdoor motor.
- Supports up to 3937 ft actual total system piping (liquid line).
- Supports 656 ft (200 m) actual piping length from the outdoor unit to the furthest fan coil.
- Operating temperature range: Cooling (db): -10° to 125°F (-15° to 52°C); Heating (wb): -22° to 60°F (-25° to 18°C).
- Protection features include: high pressure sensor and switch, low pressure sensor and switch, process controller board fuse, and inverter overload protection.
- Includes a 7-year compressor limited warranty.
- Includes a 5-year parts limited warranty.
Performance Specifications
Header Unit Model | MMY-MUP1201FT9P-UL | ||
---|---|---|---|
PERFORMANCE | Unit | ||
Nominal Cooling Capacity | Btu/h | 120,000 | |
Nominal Heating Capacity | Btu/h | 135,000 | |
Maximum Number of Indoor Units | 21 | ||
SIMULTANEOUS COOLING AND HEATING EFFICIENCY+ | |||
SCHE, Ducted FCUs | 31.0 | ||
SCHE, Ductless FCUs | 35.0 | ||
COOLING EFFICIENCY+ | |||
EER/IEER, Ducted FCUs | Btu/Wh | 11.6/22.0 | |
Power Consumption, Ducted FCUs | kW | 8.60 | |
EER/IEER, Ductless FCUS | Btu/Wh | 12.1/24.6 | |
Power Consumption, Ductless FCUs | kW | 9.26 | |
HEATING EFFICIENCY+ | |||
COP at 47°F, Ducted FCUS | 3.84 | ||
Power Consumption, Ducted FCUs | kW | 8.53 | |
COP at 47°F, Ductless FCUs | 4.20 | ||
Power Consumption, Ductless FCUs | kW | 8.76 | |
Fan Type (Qty) | Propeller (1) | ||
Airflow, Standard Range | CFM | 7416 | |
Sound Pressure | dBA | 60.0 | |
External Static Pressure* | in. wg | 0.321 |
LEGEND: db - Dry Bulb, COP - Coefficient of Performance, EER - Energy Efficiency Ratio, FCU - Fan Coil Unit, IEER - Integrated Energy Efficiency Ratio, wb - Wet Bulb, SCHE - Simultaneous Cooling and Heating Efficiency.
+Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard. Cooling: Indoor 80°F (27°C) db/67°F (20°C) wb; Outdoor 95°F (35°C) db. Heating: Indoor 70°F (21°C) db; Outdoor 47°F (8°C) db/43°F (6°C) wb.
*Requires setting by menu functions.
††Additional charge required.
NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour salt spray test.
Electrical Specifications
ELECTRICAL | |||
---|---|---|---|
Power Supply | V/Ph/Hz | 208-230/3/60 | |
Minimum Circuit Amps (MCA) | A | 36.8 | |
Maximum Overcurrent Protection (MOCP) | A | 45 |
Compressors and Fan
COMPRESSORS | |||
---|---|---|---|
Type (Number) | Hermetic Twin Rotary (1) | ||
FAN MOTOR | |||
Motor Output | kW | 0.33 x 2 |
Physical Data
PHYSICAL DATA | |||
---|---|---|---|
Pipe Connection Size - Liquid (High Pressure) | in. | 1/2 (Brazed) | |
Pipe Connection Size - Gas (Low Pressure) | in. | 1-1/8 (Brazed) | |
Discharge - Gas (High/Low Pressure) | 3/4 (Brazed) | ||
Refrigerant | R-410A | ||
Factory Charge†† | lb | 19.8 | |
Unit Width | in. | 51-1/2 | |
Unit Height | in. | 66-1/2 | |
Unit Depth | in. | 31-1/4 | |
Net Weight | lb | 675 |
Dimensional Drawing
The dimensional drawing shows the outdoor unit with various measurements and connection points. Key dimensions include width, height, and depth. It indicates the locations for power wiring, control wiring, and refrigerant piping connections (liquid and gas). The drawing also specifies required clearances for service and installation, including distances from obstacles and other piping.
Specific dimensions provided in the drawing include:
- Overall unit dimensions (Width, Depth, Height).
- Anchor bolt hole pitch and size.
- Knockout hole sizes for power and control wiring.
- Pipe connection port sizes and locations for liquid and gas lines.
- Space requirements for front, back, and side servicing.
© 2023 Carrier. All rights reserved.
Edition Date: 12/23
Printed in U.S.A.
Form No: MMY-MUP1201FT9P-UL_01
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.