TOSHIBA Carrier MMD-UP0121VHG-UL VRF Indoor Unit Submittal Data
Model: MMD-UP0121VHG-UL
Brand: TOSHIBA Carrier
Product Type: VRF Indoor Unit / Vertical Air Handler
Submittal Data
Job Name: ________________________________
Location: ________________________________
Tag: ________________________
Standard Features
- Dual Drainage Spouts
- Three Fan Speeds - High, Medium and Low
- Unit Can Be Installed Standing Vertical or Laid Horizontally
- Electronically Commutated Fan Motor (ECM)
- Built-In Pulse Modulating Valve For Installation Ease
- Removable Front Panel Provides Easy Access
- Filter MERV 3
Performance Specifications
Parameter | Unit | Value |
---|---|---|
Cooling Rated Capacity | Btu/h | 12,000 |
Heating Rated Capacity | Btu/h | 13,500 |
Airflow (H/M/L) | CFM | 480/440/340 |
Sound Data (H, M, L) † | dBA | 41.4/38.2/36.8 |
External Static Pressure (ESP) | in. WG | 0.3 (Factory Default) / 0.5 (Max) |
Physical Data
Parameter | Unit | Value |
---|---|---|
Pipe Connection Size - Liquid | inches | 1/4 (brazed) |
Pipe Connection Size - Suction | inches | 3/8 (brazed) |
Refrigerant | R410A | |
Dimensions (H) | in | 46-7/8 |
Dimensions (W) | in | 17-3/4 |
Dimensions (D) | in | 22-1/4 |
Net Weight | lbs | 130 |
Electrical Specifications
Parameter | Unit | Value |
---|---|---|
Power Supply | V/Ph/Hz | 208-230/1/60 |
MCA* | A | 1.9 |
MOCP* | A | 15 |
Full Load Amps (FLA)* | A | 1.5 |
Accessories (Optional)
- Simple Wired Remote Control - RBC-ASCU11-UL
- Wired Remote Controller (Local Controller) - RBC-AWSU52-UL
- Touch Screen Central Controller - BMS-CT2560U-UL
- Stand Alone Receiver with Wireless Remote TCB-AX32UL
- Remote Sensor TCB-TC41U-UL
- Wired Remote Controller - RBC-AMT32UL
- Filter Box / 1" MERV3 (TCB-FB2F241VDGUL)
- Plenum TCB-PL2S241VDGUL
- Electrical Heater (240V/208V) with models: 1.0kW/0.8kW (TCB-HT101VDGUL), 3.0kW/2.3kW (TCB-HT301VDGUL), 5.0kW/3.8kW (TCB-HT501VDGUL)
Notes:
- * Does not include electric heater.
- † Average / weighted sound values.
Dimensional Drawing Description
The dimensional drawing illustrates the vertical air handler unit. Key dimensions are provided in inches:
- Overall Height: 46-7/8 inches
- Overall Width: 17-3/4 inches
- Overall Depth: 22-1/4 inches
- The unit features connection points for liquid (1/4" brazed) and suction (3/8" brazed) pipes.
- It includes provisions for electrical power entry and communication (COM) entry, with options available on both sides.
- An optional EH (Electric Heater) disconnect cover is indicated.
- Airflow is indicated as entering from the bottom and exiting from the top.
- Condensate and auxiliary drain connections (3/4" FPT) are located at the bottom.
- Various smaller dimensions detail panel access, internal component spacing, and connection port locations.