Stäubli MA707 MC4-Evo 2 In-line Fuse PV-K/1500ILF3

Installation and Operation Manual

Safety Instructions

Importance of the Assembly Instructions

Non-compliance with assembly and safety instructions can lead to life-threatening injuries due to electric shock, electric arcs, fire, or system failure.

  • Follow all assembly instructions.
  • Use and install the product only according to these instructions and technical data.
  • Safely store instructions and pass them to end-users.

Requirements for Personnel

Assembly, installation, and commissioning must be performed by an electrician or an electrically instructed person.

  • An electrician has professional training, knowledge, and experience to identify and avoid electrical dangers and use appropriate personal protective equipment.
  • An electrically instructed person is trained or supervised by an electrician and can identify and avoid electrical dangers.

Intended Use

In-line fuses interrupt DC circuits during over-current events.

Prerequisites for Installation and Assembly

  • NEVER use a damaged connector or in-line fuse.
  • ONLY use tools and procedures approved by Stäubli.

Safe Assembly and Mounting

Live parts can remain energized after isolation or disconnection. ALWAYS de-energize the photovoltaic array or string before installing the product.

Mating and Disconnecting

  • ALWAYS de-energize the photovoltaic system before mating and disconnecting connectors.
  • NEVER disconnect connectors under load.
  • NEVER connect Stäubli connector parts with connectors from other manufacturers.
  • NEVER reconnect a string without an in-line fuse if it was previously disconnected.

Do NOT Modify NOR Repair Component

  • Do NOT modify the component.
  • Replace defective components.

Technical Data

DesignationProduct DesignationValue
Voltage ratingDC 1500 V
Test voltage8 kV
Safety classII
Overvoltage categoryCATIII/3
Pollution degree3
Upper Limiting Temperature (ULT)115° C
Ambient temperature range-40 °C...+50 °C
Degree of Protection (IP)IP65/IP68 (1 m, 1 h)
Insulation materialPolyamide/EVA/XLPE
Mating connectorsOnly genuine Stäubli connectors shall be used! PV-KST4/... or PV-KBT4/... ("MC4")¹), PV-KBT4-EVO 2... or PV-KST4-EVO 2... ("MC4-Evo 2")
Rated current (gPV)Rated current (gPV) in A4 A, 5 A, 6 A, 15 A, 20 A
Transportation/storage temperature range-40 °C to +50 °C
Certification TÜV Rheinlandacc. to 2PfG 2380/10.21R 60163375
Fuse link gPV certifiedacc. to IEC60269-6:2010+Amd1J 50524015

¹ Attention: When connecting the connectors, ensure that the rated data (current carrying capacity and rated voltage) of the products are compatible with the mating connectors used. Observe the information in the assembly instructions for the connectors used.

Tools and Installation Procedure

Tools/Assembly Materials Required

For integration into a PV cable harness system:

For MC4-Evo 2 connectors: Assembly and unlocking tool, PV-MS-PLS, order No. 32.6058.

Note: Refer to Operating instructions MA270, www.staubli.com/electrical.

Installation Procedure

Important Electric Shock Hazard: Do not disconnect the In-line Fuse under load nor connect it in an electrical circuit that is under load.

Image shows the Stäubli MC4-Evo 2 In-line Fuse (PV-K/1500ILF3) connected to cables. Separate images show PV-BVK4 and PV-SVK4 sealing caps.

Step 1: Preparation

Using the appropriate disconnect tool, separate the mated connector pair where the In-line Fuse will be located.

Image sequence shows the process of disconnecting a connector pair using a specialized tool.

Notes on Installation

General Notes on Installation

  • Unmated connectors must be protected from environmental impact (moisture, dirt, dust, etc.) with sealing caps (socket order no. 32.0716; plug order no. 32.0717).
  • Do not mate contaminated connectors.
  • Connectors must not come into contact with any chemicals.

Cable Routing

Cable management must allow a minimum of 20 mm of cable that exits directly from the cable seal without bending or stress. Refer to cable manufacturers' specifications for minimum bending radius. When installing in bundles (n > 1), consider product temperature ratings and relevant standards/regulations.

Diagram illustrates proper cable routing, showing a cable exiting a seal with a minimum length of 20 mm indicated.

Contaminated/Damaged Connectors

  • Prevent connectors from contamination by the environment (e.g., soil, water, insects, dust).
  • Do not allow the connector surface to be contaminated (e.g., stickers, paint, heat shrink tubing).
  • Do not place the connector directly on the roofing surface.
  • Do not place the connector at the lowest point of cabling where water can collect.
  • Do not allow the connector to be in standing water.
  • Do not mount cable ties directly on the connector body.

Mechanical Stress

  • Ensure connectors are not subjected to permanent mechanical tensile load or vibration.
  • Connectors shall not be under strain from cable management.

Additional Notes and Contact Information

Refer to pages 6-8 for additional notes and global headquarters contact information.

Global Headquarters:

Stäubli Electrical Connectors AG
Stockbrunnenrain 8
4123 Allschwil/Switzerland

Tel: +41 61 306 55 55
Fax: +41 61 306 55 56
Email: ec.ch@staubli.com
Website: www.staubli.com/electrical

Models: MA707 MC4-Evo 2 In line Fuse, MA707 MC4-Evo, 2 In line Fuse, line Fuse, Fuse

File Info : application/pdf, 8 Pages, 940.09KB

PDF preview unavailable. Download the PDF instead.

PV MA707-fr

References

Adobe PDF Library 16.0.7

Related Documents

Preview Stäubli MC4-Evo 2 In-line Fuse MA707 Installation and Operation Manual
Detailed installation and operation manual for the Stäubli MC4-Evo 2 In-line Fuse, model MA707, designed for PV-K/1500ILF3 solar applications. Covers safety instructions, technical data, assembly procedures, and important notes.
Preview Stäubli MC4-Evo 2 Y-Splitter MA706 Installation and Operation Manual
Comprehensive installation and operation manual for the Stäubli MC4-Evo 2 Y-Splitter (MA706). Covers safety guidelines, technical specifications, required tools, installation procedures, and important notes for photovoltaic systems.
Preview Stäubli MC4-Evo Ready Connector MA293 Assembly Instructions
Comprehensive assembly instructions for the Stäubli MC4-Evo Ready MA293 connector. This guide covers essential safety precautions, required tools, detailed cable preparation steps, connector assembly, fastening, mating, and disconnecting procedures, along with technical specifications for photovoltaic applications.
Preview Stäubli MC4-Evo Stor MA702 Panel Receptacle Assembly Instructions and Technical Data
Comprehensive guide for the Stäubli MC4-Evo Stor MA702 panel receptacle, covering safety, tools, lead preparation, crimping, installation, mating, disconnecting, and technical specifications for photovoltaic applications.
Preview Stäubli MC4-Evo 2 Branch Connectors: Assembly and Technical Guide
Comprehensive assembly instructions and technical specifications for Stäubli MC4-Evo 2 branch connectors, including safety guidelines, installation procedures, and product data for photovoltaic and DC applications.
Preview Stäubli MC4 Connector MA231 Assembly Instructions and Technical Data
Comprehensive assembly instructions, safety guidelines, and technical specifications for the Stäubli MC4 connector MA231, designed for photovoltaic applications. Covers preparation, crimping, assembly checks, and technical data.
Preview Stäubli MC4-Evo 2 Connector Assembly Instructions (MA298)
Comprehensive assembly instructions for the Stäubli MC4-Evo 2 connector (MA298). This guide covers essential safety precautions, required tools, cable preparation, crimping procedures, mating and disconnecting steps, and detailed technical specifications for photovoltaic applications.
Preview Stäubli MC4-Evo 2 MA285 Panel Receptacle Assembly Instructions
Comprehensive assembly instructions for Stäubli MC4-Evo 2 MA285 panel receptacles. Covers safety guidelines, required tools, cable preparation, crimping, installation, plugging/unplugging, and technical data for photovoltaic and other low-voltage DC applications.