MIRCOM® FA-101U

Fire Alarm Control Panel

INSTALLATION and OPERATION MANUAL

NOTICE ? All information, documentation, and specifications contained in this manual are subject to change without prior notice by the manufacturer. ©1998 by Mircom Technologies Limited Printed in CANADA, Dec 2005 LT-534 Rev. 4

TABLE OF CONTENTS

PAGE

1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2. MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 1

3. FUNCTION SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

4. WIRING:

    4.1 DETECTION ZONE . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    4.2 SIGNAL ZONE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    4.3 ALARM AND TROUBLE RELAYS . . . . . . . . . . . . . . . . . . 2

    4.4 REMOTE ANNUNCIATION . . . . . . . . . . . . . . . . . . . . . . . 2

    4.5 A.C. POWER AND BATTERIES . . . . . . . . . . . . . . . . . . . . 2

5. TROUBLE INDICATORS AND CONTROL:

    5.1 COMMON TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . 2

    5.2 COMMON TROUBLE BUZZER . . . . . . . . . . . . . . . . . . . . 2

    5.3 ZONE TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    5.4 TROUBLE SILENCE SWITCH . . . . . . . . . . . . . . . . . . . . . 2

    5.5 BATTERY FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . 3

    5.6 GROUND FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . 3

    5.7 SIGNAL TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . . 3

6. SEQUENCE OF OPERATION:

    6.1 NORMAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    6.2 ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    6.3 SIGNAL SILENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    6.4 RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

7. SYSTEM CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

8. POWER UP AND TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . 4

FIGURES:

    1. BACKBOX & FLUSH TRIM MOUNTING DETAILS . . . . . . . . . 5

    2. PRINTED CIRCUIT BOARD LAYOUT . . . . . . . . . . . . . . . . . 6

    3. DETECTION AND SIGNAL WIRING INSTRUCTION . . . . . . . . 7

    4. WIRING TABLE FOR DETECTION ZONE . . . . . . . . . . . . . . 8

    5. WIRING TABLE FOR BELLS AND HORNS . . . . . . . . . . . . . . 9

    6. ALARM AND TROUBLE RELAY CONTACTS, AND

        REMOTE ANNUNCIATION WIRING INSTRUCTION . . . . . . . . 10

APPENDIX "A" 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY . . . . . . . . . . . . . . 11

APPENDIX "B" BATTERY CALCULATIONS . . . . . . . . . . . . . . . . . . . 14

1. INTRODUCTION

The FA-101U is a supervised 1 zone 24VDC Fire Alarm Control Panel.

The panel provides the following features:

2. MECHANICAL INSTALLATION

The panel can be surface or flush mounted. Refer to Figure 1 for dimensions.

For surface mounting, mark the location of the four mounting holes. Install the top two screws into the wall and place the panel over the screws. Install the bottom screws, and tighten down all four screws.

For flush mounting, make the wall cut-out according to the panel dimensions. Remove the control panel door. Mount the flush mounting trim (MODEL FA-102TRU) to the back box using the screws and nuts provided with the flush mounting kit. Re-install the door on top of the flush trim. The cam lock may require a minor adjustment in order to compensate for the flush trim.

3. FUNCTION SELECTION

The following jumpers are available for function selection, refer to Figure 2 for location;

4. WIRING

4.1 DETECTION ZONES

The system has 1 detection zone. Refer to Figure 3 for wiring instruction and to Figure 4 for wire size.

4.2 SIGNAL ZONE

There is 1 signal zone available for bells and horns providing 1.25A of signal power. Refer to Figure 3 for wiring instruction and to Figure 5 for wire size.

4.3 ALARM AND TROUBLE RELAYS

Alarm and trouble relay contacts are provided. Refer to Figure 6 for contact location and designation.

4.4 REMOTE ANNUNCIATION

Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 for wiring instruction.

4.5 A.C. POWER AND BATTERIES

The A.C. power is connected to the terminal block above the transformer.

Use GEL CELL or SEALED LEAD-ACID type of batteries only. Connect the batteries after power up. Use 24V 4AH batteries for 24 hours standby and 5 or 30 minutes of alarm.

ELECTRICAL RATING: 120V, 60Hz, 1A / 240V, 50 Hz, 0.5A

5. TROUBLE INDICATORS AND CONTROL

Refer to Figure 2 for the location of indicators and control.

5.1 COMMON TROUBLE LED

The yellow common trouble LED will flash for any trouble in the panel.

5.2 COMMON TROUBLE BUZZER

The common trouble buzzer will sound intermittently for any trouble.

5.3 ZONE TROUBLE LED

The yellow zone trouble LED will illuminate steadily for open loop in the zone wiring.

5.4 TROUBLE SILENCE SWITCH

Operating this switch will silence the common trouble buzzer. If there is no trouble condition and the switch is in the silence position, the buzzer will sound continuously.

5.5 BATTERY FAULT LED

Battery removal, low voltage and open battery leads will turn on the yellow battery fault LED and the common trouble LED.

5.6 GROUND FAULT LED

Any ground fault of 10K ohms or less will turn on the yellow ground fault LED steadily, flashing the common trouble LED and sounding the common trouble buzzer intermittently.

5.7 SIGNAL TROUBLE LED

The yellow signal trouble LED will illuminate steadily for any open or short. (The LED is located behind the display plate.)

6. SEQUENCE OF OPERATION

Refer to Figure 2 for the location of indicators and controls.

6.1 NORMAL

All indicators are normally OFF except for the green A.C. On LED.

6.2 ALARM

A red zone alarm LED will illuminate steadily for incoming alarm.

6.3 SIGNAL SILENCE

If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation. Once the 60 seconds have expired, pushing the signal silence switch to the right will silence all the bells and horns. Once the signal has been silenced, the signal silenced LED will illuminate. If the switch is in the off normal position to the right while there is no alarm condition, the panel will indicate trouble.

6.4 RESET

Operating the reset switch will restore all latched functions in the panel. The smoke detectors will reset if all products of combustion are cleared from their chambers.

7. SYSTEM CHECKOUT

BEFORE TURNING POWER ON:

  1. Check all external wiring for opens, shorts or grounds.
  2. Check that transformer cables are securely connected.
  3. Check the A.C. power wiring for proper connection. DO NOT connect batteries in order to prevent sparking.
  4. Check that all switches are in the normal position to the left.

8. POWER UP AND TROUBLESHOOTING

  1. After completing all of the system checkout procedures, power up the panel. The A.C. On LED should illuminate.
  2. The trouble buzzer should sound intermittently, the common trouble LED flash, indicating battery fault.
  3. Connect the batteries carefully, observing the correct polarity.
  4. The common trouble LED should extinguish. If the common trouble LED stays on, check the front panel for the illumination of the following LEDs;
    • a) BATTERY LED - battery voltage may be too low, below 20.4V.
    • b) GROUND FAULT LED - indicates a ground on one or more of the extended wires.
    • c) ZONE TROUBLE LED - indicates an open loop or a signal silence switch is in the off normal position to the right.
    • d) SIGNAL TROUBLE LED - indicates an open loop or short in the signal zone.

FIGURES

FIGURE 1: BACKBOX & FLUSH TRIM MOUNTING DETAILS. This figure illustrates the dimensions and mounting hole locations for the fire alarm control panel backbox and the optional flush mounting trim (MODEL FA-102TRU).
FIGURE 2: CIRCUIT BOARD LAYOUT. This diagram shows the layout of the printed circuit board, including terminal blocks (TB2, TB3), jumpers (JW1, JW2, JW3, JW6), LEDs (AC ON, TRBL, ALARM, ZONE 1, SIG. SIL., BATT., GND, TRBL SIL.), relays (AUX ALARM RELAY, COMMON TROUBLE RELAY), and connections for SIGNAL, DETECTION ZONES, REMOTE ANNUNCIATION, RESET, BATTERY, and A.C. TRANSFORMER.
FIGURE 3: DETECTION AND SIGNAL WIRING INSTRUCTION. This schematic shows wiring for the Detection Zone (22VDC, 3mA standby, 50mA alarm) and Signal Zone (24VDC, 1.25A max). It depicts components like pull stations (F), smoke detectors (S), heat detectors (R), and bells (F), along with End-of-Line Resistors (ELR). It also notes the requirement for power-limited cable.
FIGURE 4: WIRING TABLE FOR DETECTION ZONE. This table lists Wire Gauge (AWG) and the corresponding Maximum Wiring Distance in FEET and METRES to the last device.
WIRE GAUGE (AWG) MAXIMUM WIRING DISTANCE TO THE LAST DEVICE
FEET METRES
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
FIGURE 5: WIRING TABLE FOR BELLS AND HORNS. This table details wiring specifications for signal zones, correlating Total Signal Load (Amperes) with Maximum One Way Distance (FEET/METRES) for various Wire Sizes (18AWG, 16AWG, 14AWG, 12AWG) and the corresponding Max. Loop Resistance (Ohms).
TOTAL SIGNAL LOAD Amperes MAXIMUM ONE WAY DISTANCE / WIRE SIZE MAX. LOOP RESISTANCE Ohms
18AWG 16AWG 14AWG 12AWG
ft m ft m ft m ft m
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.25 118 36 185 56 300 91 425 129 1.5
FIGURE 6: ALARM AND TROUBLE RELAY CONTACTS AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS. This diagram illustrates the wiring for terminal block TB3, detailing connections for Auxiliary Common Alarm Relay Contacts (28VDC, 3A, resistive), Common Trouble Relay Contacts (28VDC, 3A, resistive), and Remote Trouble LED (Amber), Remote Trouble Buzzer, and Remote "A.C. ON" LED (Green). It includes notes regarding jumper settings (JW1, JW2) and the requirement for a listed power-limited source of supply.

APPENDIX "A" - COMPATIBLE DEVICES

This appendix lists compatible 2-WIRE SMOKE DETECTOR CONTROL PANELs and their compatible devices by manufacturer.

CANADIAN 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY (ULC)

NOTES:

SMOKE DETECTOR
MAKE MODEL / BASE MAKE MODEL / BASE MAKE MODEL / BASE
MIRCOM
MIR-525
MIR-525T
CERBERUS PYROTRONICS
D1-2
D1-3 / DB-3S
FENWAL
PSD-7131 / 70-201000-001
PSD-7131 / 70-201000-002
PSD-7131 / 70-201000-003
PSD-7131 / 70-201000-005
SYSTEM SENSOR
1400-A
2400-A
1451-A / B401B
1451-A / B406B
2451-A / B401B
2451-A / B406B
1451DH / DH400A
2451-A / DH400A
MIRTONE
73471
73494
73575
73495 / 73486
73495 / 73487
73595 / 73486
73595 / 73497
PSD-7130 / 70-201000-001
PSD-7130 / 70-201000-002
PSD-7130 / 70-201000-003
PSD-7130 / 70-201000-005
PSD-7128 / 70-201000-001
PSD-7126 / 70-201000-002
PSD-7126 / 70-201000-003
PSD-7126 / 70-201000-005
EDWARDS
6249C
6250C
6264C
6266C
6269C
6270C
6269C-003
6270C-003
SIMPLEX
2098-9110
PSD-7129 / 70-211002-000
PSD-7125 / 70-201000-001
PSD-7126 / 70-201000-002
PSD-7125 / 70-201000-003
PSD-7125 / 70-201000-005
CPD-7021 / 70-201000-001
CPD-7021 / 70-201000-002
CPD-7021 / 70-201000-003
CPD-7021 / 70-201000-005

UNITED STATES 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY (ULI)

NOTES:

SMOKE DETECTOR SMOKE DETECTOR
MAKE MODEL / BASE COMPATIBILITY IDENTIFIER HEAD / BASE RATED STANDBY CURRENT MAKE MODEL / BASE COMPATIBILITY IDENTIFIER HEAD / BASE RATED STANDBY CURRENT
SYSTEM SENSOR
1100
1151 / B110LP
1151 / B116LP
1400
1451 / B401
1451 / B401B
1451 / B406B
1451DH / DH400
2100
2100T
2151 / B110LP
2151 / B116LP
2400
2400TH
2400AT
2400AIT
2451 / B401B
2451 / B406B
2451 / DH400
2451TH / B401B
2451TH / B406B
2451 / B401
2451TH / B401
4451HT / B401B
4451HT / B406B
4451HT / B401
5451 / B401B
5451 / B401
5451 / B406B
A - N/A
A-A
A-A
A - N/A
A-A
A-A
A-A
A-A
A - N/A
A - N/A
A-A
A-A
A - N/A
A - N/A
A - N/A
A - N/A
A-A
A-A
A - N/A
A-A
A-A
A-A
A-A
A-A
A-A
A-A
A-A
A-A
A-A
0.12 mA
0.12 mA
0.12 mA
0.10 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
0.12 mA
SENTROL - ESL
429C
429CT
429CST
429CRT
711U / 701E, 701U, 702E, 702U
712U / 701E, 701U, 702E, 702U
713-5U / 701E, 701U, 702E, 702U
713-6U / 701E, 701U, 702E, 702U
721U / 702E, 702U
721UT / 702E, 702U
722U / 702E, 702U
731U / 702E, 702U, 702RE, 702RU
732U / 702E, 702U, 702RE, 702RU
S10A - N/A
S10A - N/A
S11A - N/A
S11A - N/A
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S10A - S00
S11A - S00
S11A - S00
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
0.10 mA
DETECTION SYSTEMS INC.
DS250
DS250TH
DS282
DS282TH
B - N/A
B - N/A
B - N/A
B - N/A
0.10 mA
0.10 mA
0.10 mA
0.10 mA
MIRCOM
MIR-525U
MIR-525TU
FDT-1
FDT-1
0.10 mA
0.10 mA

UNITED STATES SIGNALING DEVICE CONTROL PANEL COMPATIBILITY (ULI)

System Sensor SpecrAlert Wheelock Gentex
P2415 P2415W P241575 P241575W P2475 AS-2415W-24-FR AS-241575W-FR AS-2430W-FR AS-2475W-FR AS-24110W-FR AH-24-R AVP-4-15-1 AVP-4-15/75 AVP-4-30/75 AVP-4-110-1 GXS-4-15-1 GX90S-4-15-1
P2475W P24110 P241575 P24110W S2415 S2415W AS-2415C-FW AS-2430C-FW AS-2475C-FW AS-24100C-FW NS-24110W-FR NS-2475W-FR GXS-4-15/75-W GXS-4-30/75-W GXS-4-15/75-C GXS-4-110-1 SHG15/75-W SHG24-15-1
S241575 S241575W S2475 S2475W S24110 S24110W AH-24-WP-R NS-2415W-FR NS-241575W-FR NS-2430W-FR NS4-24110W-FR NS4-2475W-FR GX90S-4-15/75-W GX90S-4-30/75W GX90S-4-15/75-C GX90S-4-110-1 GOS24-15-1 GOT24
H12/24 H12/24W MDL MDLW NS-241575W-FR NS4-241575W-FR NS4-2430W-FR NS4-2475W-FR RSS-2415W-FR RSS-241575W-FR SHG24-30/75-W SHG24-15/75-C GOS24-15/75 GOS24-30/75 GOS24-110-1 GMS-24-15-1
RS-2415W-FR RSS-2430W-FR RSS-2415W-FR RSS-241575W-FR RSS-24110W-FR RSS-2430C-FW GOS24-15/75 GMS-24-15-1 GMS-24-15/75-W GMS-24-30/75-W GMS-24-15/75-C GMS-24-110-1
RSS-2475W-FR RSS-2475C-FW RSS-24100C-FW MT-12/24-ULC MT-24-LS-VFR-ULC MB-G6-24-R GMH-24 GMS-24-15-1 GMS-24-15/75-W GMS-24-30/75-W GMS-24-15/75-C WGMS-4/75
AMT-12/24-R-ULC AMT-24-LS-VFR-ULC MB-G10-24-R MT-24-WS-VFR-ULC SM-12/24-R GMS-24-110-1
DSM-12/24-R

APPENDIX "B" - BATTERY CALCULATIONS (SELECTION GUIDE)

Use the form below to determine the required batteries.

IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.

POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)

Model Number Description Qty STANDBY TOTAL STANDBY ALARM TOTAL ALARM
FA-101U Fire Alarm, 1 Det, 1 Sig X 0.066 = 0.125 =
FA-102U Fire Alarm, 2 Det, 1 Sig X 0.076 = 0.135 =
FA-1025U Fire Alarm, 5 Det, 2 Sig X 0.114 = 0.200 =
RTI-1 Remote Trouble Indicator X 0.035 = 0.035 =
2-Wire Smoke Detectors X 0.0001 = * 0.090 = 0.090
4-Wire Smoke Detectors X = = = =
Signal Load (bells, horns, strobes, and etc.) = = = =
Total currents (Add above currents) STANDBY (A) (B)

Total Current Requirement: ALARM (B)______ Amps.

Battery Capacity Requirement:
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [%Alarm in Hr.] _____) = (C) ______AH

Battery Selection: Multiply (C) by 1.20 to derate battery.

Batteries BA-104 (4.0AH) and BA-1065(6.5AH) fit into the backboxes ; all larger batteries such as BA-110(10AH) and the BA-117(17AH) require an external battery box.

* Assuming three Initiating Circuits in alarm.
% Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
' Using the MIR-425/U 2-wire smoke detector. See Appendix "A", for other available smoke detectors.

Contact Information

Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113

U.S.A.
60 Industrial Parkway PMB 278
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113

© Mircom 2006
Printed in Canada
Subject to change without prior notice
www.mircom.com

PDF preview unavailable. Download the PDF instead.

LT-534 FA-101U Installation and Operation Manual Acrobat Distiller 6.0.1 (Windows)

Related Documents

Preview Mircom FA-102U Fire Alarm Control Panel: Installation & Operation Manual
Comprehensive installation and operation manual for the Mircom FA-102U 2-zone, 24VDC Fire Alarm Control Panel, covering features, wiring, indicators, troubleshooting, compatibility, and warranty information.
Preview Mircom FA-300 Series LCD Fire Alarm Control Panel: Installation and Operation Manual
This comprehensive manual provides detailed installation and operation instructions for the Mircom FA-300 Series LCD Fire Alarm Control Panel. It covers system components, mechanical installation, wiring, configuration, troubleshooting, and supported devices, ensuring proper setup and use of this critical safety equipment.
Preview Mircom FA-101T Fire Alarm Control Panel Installation and Operation Manual
This manual provides detailed installation and operation instructions for the Mircom FA-101T Fire Alarm Control Panel, a supervised single-zone 24V DC system.
Preview Mircom FA-300 Series LED Fire Alarm Control Panel Installation and Operation Manual
Comprehensive installation and operation manual for the Mircom FA-300 Series LED Fire Alarm Control Panel. Covers features, components, wiring, configuration, and troubleshooting.
Preview UDACT-2200 Dual Line Dialer Installation Manual
This installation manual provides comprehensive instructions for the Mircom UDACT-2200 Dual Line Dialer, covering features, installation, wiring, operation, and programming for fire alarm systems.
Preview Mircom MGD-32 Master Graphic Driver Module - Fire Alarm Annunciator
Detailed product information for the Mircom MGD-32 Master Graphic Driver Module, a key component in fire alarm systems. Learn about its features, specifications, expandability, and compatibility with Mircom control panels and annunciator modules.
Preview Mircom FA-103 & FA-106 Conventional Fire Alarm Control Panels Product Introduction and FAQ
Mircom Group of Companies announces the introduction of the new FA-103 and FA-106 Conventional Fire Alarm Control Panels, replacing older models. This document provides product details, a comparison of features, and answers frequently asked questions regarding the new series.
Preview Mircom LT-657 FX-2000 Installation and Instruction Manual Addendum
This document provides an addendum to the Mircom LT-657 FX-2000 Fire Alarm Control Panel Installation and Instruction Manual, detailing new features such as UUKL functionality and Output Circuit Delay Operation, along with UL 864 compliance information.