MIRCOM® FA-101U
Fire Alarm Control Panel
INSTALLATION and OPERATION MANUAL
TABLE OF CONTENTS
PAGE
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. FUNCTION SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4. WIRING:
4.1 DETECTION ZONE . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.2 SIGNAL ZONE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.3 ALARM AND TROUBLE RELAYS . . . . . . . . . . . . . . . . . . 2
4.4 REMOTE ANNUNCIATION . . . . . . . . . . . . . . . . . . . . . . . 2
4.5 A.C. POWER AND BATTERIES . . . . . . . . . . . . . . . . . . . . 2
5. TROUBLE INDICATORS AND CONTROL:
5.1 COMMON TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . 2
5.2 COMMON TROUBLE BUZZER . . . . . . . . . . . . . . . . . . . . 2
5.3 ZONE TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.4 TROUBLE SILENCE SWITCH . . . . . . . . . . . . . . . . . . . . . 2
5.5 BATTERY FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.6 GROUND FAULT LED . . . . . . . . . . . . . . . . . . . . . . . . . 3
5.7 SIGNAL TROUBLE LED . . . . . . . . . . . . . . . . . . . . . . . . 3
6. SEQUENCE OF OPERATION:
6.1 NORMAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.2 ALARM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.3 SIGNAL SILENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.4 RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7. SYSTEM CHECKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
8. POWER UP AND TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . 4
FIGURES:
1. BACKBOX & FLUSH TRIM MOUNTING DETAILS . . . . . . . . . 5
2. PRINTED CIRCUIT BOARD LAYOUT . . . . . . . . . . . . . . . . . 6
3. DETECTION AND SIGNAL WIRING INSTRUCTION . . . . . . . . 7
4. WIRING TABLE FOR DETECTION ZONE . . . . . . . . . . . . . . 8
5. WIRING TABLE FOR BELLS AND HORNS . . . . . . . . . . . . . . 9
6. ALARM AND TROUBLE RELAY CONTACTS, AND
REMOTE ANNUNCIATION WIRING INSTRUCTION . . . . . . . . 10
APPENDIX "A" 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY . . . . . . . . . . . . . . 11
APPENDIX "B" BATTERY CALCULATIONS . . . . . . . . . . . . . . . . . . . 14
1. INTRODUCTION
The FA-101U is a supervised 1 zone 24VDC Fire Alarm Control Panel.
The panel provides the following features:
- 1 class B detection zone
- 1 class B signal zone, 1.25A
- Alarm and trouble relay contacts
- Remote trouble and A.C. ON indication
- Zone silence/disconnect switch
- Trouble silence switch
- LED indicators for zone Alarm and Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced
2. MECHANICAL INSTALLATION
The panel can be surface or flush mounted. Refer to Figure 1 for dimensions.
For surface mounting, mark the location of the four mounting holes. Install the top two screws into the wall and place the panel over the screws. Install the bottom screws, and tighten down all four screws.
For flush mounting, make the wall cut-out according to the panel dimensions. Remove the control panel door. Mount the flush mounting trim (MODEL FA-102TRU) to the back box using the screws and nuts provided with the flush mounting kit. Re-install the door on top of the flush trim. The cam lock may require a minor adjustment in order to compensate for the flush trim.
3. FUNCTION SELECTION
The following jumpers are available for function selection, refer to Figure 2 for location;
- JW1: Cut for normally open trouble contacts.
- JW2: Cut for normally closed trouble contacts.
- JW3: Cut to enable common alarm relay to de-energize if signal silence switch is activated.
- JW6: Cut if 60 second signal silence inhibit is not required (Signals can be manually silenced any time if cut).
4. WIRING
4.1 DETECTION ZONES
The system has 1 detection zone. Refer to Figure 3 for wiring instruction and to Figure 4 for wire size.
4.2 SIGNAL ZONE
There is 1 signal zone available for bells and horns providing 1.25A of signal power. Refer to Figure 3 for wiring instruction and to Figure 5 for wire size.
4.3 ALARM AND TROUBLE RELAYS
Alarm and trouble relay contacts are provided. Refer to Figure 6 for contact location and designation.
4.4 REMOTE ANNUNCIATION
Annunciation outputs are provided for remote trouble indicator and buzzer. Refer to Figure 6 for wiring instruction.
4.5 A.C. POWER AND BATTERIES
The A.C. power is connected to the terminal block above the transformer.
Use GEL CELL or SEALED LEAD-ACID type of batteries only. Connect the batteries after power up. Use 24V 4AH batteries for 24 hours standby and 5 or 30 minutes of alarm.
ELECTRICAL RATING: 120V, 60Hz, 1A / 240V, 50 Hz, 0.5A
5. TROUBLE INDICATORS AND CONTROL
Refer to Figure 2 for the location of indicators and control.
5.1 COMMON TROUBLE LED
The yellow common trouble LED will flash for any trouble in the panel.
5.2 COMMON TROUBLE BUZZER
The common trouble buzzer will sound intermittently for any trouble.
5.3 ZONE TROUBLE LED
The yellow zone trouble LED will illuminate steadily for open loop in the zone wiring.
5.4 TROUBLE SILENCE SWITCH
Operating this switch will silence the common trouble buzzer. If there is no trouble condition and the switch is in the silence position, the buzzer will sound continuously.
5.5 BATTERY FAULT LED
Battery removal, low voltage and open battery leads will turn on the yellow battery fault LED and the common trouble LED.
5.6 GROUND FAULT LED
Any ground fault of 10K ohms or less will turn on the yellow ground fault LED steadily, flashing the common trouble LED and sounding the common trouble buzzer intermittently.
5.7 SIGNAL TROUBLE LED
The yellow signal trouble LED will illuminate steadily for any open or short. (The LED is located behind the display plate.)
6. SEQUENCE OF OPERATION
Refer to Figure 2 for the location of indicators and controls.
6.1 NORMAL
All indicators are normally OFF except for the green A.C. On LED.
6.2 ALARM
A red zone alarm LED will illuminate steadily for incoming alarm.
6.3 SIGNAL SILENCE
If the 60 second signal silence inhibit is selected, the signal cannot be silenced for 60 seconds after an alarm initiation. Once the 60 seconds have expired, pushing the signal silence switch to the right will silence all the bells and horns. Once the signal has been silenced, the signal silenced LED will illuminate. If the switch is in the off normal position to the right while there is no alarm condition, the panel will indicate trouble.
6.4 RESET
Operating the reset switch will restore all latched functions in the panel. The smoke detectors will reset if all products of combustion are cleared from their chambers.
7. SYSTEM CHECKOUT
BEFORE TURNING POWER ON:
- Check all external wiring for opens, shorts or grounds.
- Check that transformer cables are securely connected.
- Check the A.C. power wiring for proper connection. DO NOT connect batteries in order to prevent sparking.
- Check that all switches are in the normal position to the left.
8. POWER UP AND TROUBLESHOOTING
- After completing all of the system checkout procedures, power up the panel. The A.C. On LED should illuminate.
- The trouble buzzer should sound intermittently, the common trouble LED flash, indicating battery fault.
- Connect the batteries carefully, observing the correct polarity.
- The common trouble LED should extinguish. If the common trouble LED stays on, check the front panel for the illumination of the following LEDs;
- a) BATTERY LED - battery voltage may be too low, below 20.4V.
- b) GROUND FAULT LED - indicates a ground on one or more of the extended wires.
- c) ZONE TROUBLE LED - indicates an open loop or a signal silence switch is in the off normal position to the right.
- d) SIGNAL TROUBLE LED - indicates an open loop or short in the signal zone.
FIGURES
WIRE GAUGE (AWG) | MAXIMUM WIRING DISTANCE TO THE LAST DEVICE | |
---|---|---|
FEET | METRES | |
22 | 2990 | 910 |
20 | 4760 | 1450 |
18 | 7560 | 2300 |
16 | 12000 | 3600 |
14 | 19000 | 5800 |
12 | 30400 | 9200 |
TOTAL SIGNAL LOAD Amperes | MAXIMUM ONE WAY DISTANCE / WIRE SIZE | MAX. LOOP RESISTANCE Ohms | |||||||
---|---|---|---|---|---|---|---|---|---|
18AWG | 16AWG | 14AWG | 12AWG | ||||||
ft | m | ft | m | ft | m | ft | m | ||
0.06 | 2350 | 716 | 3750 | 1143 | 6000 | 1829 | 8500 | 2591 | 30 |
0.12 | 1180 | 360 | 1850 | 567 | 3000 | 915 | 4250 | 1296 | 15 |
0.30 | 470 | 143 | 750 | 229 | 1200 | 366 | 1900 | 579 | 6 |
0.60 | 235 | 71 | 375 | 114 | 600 | 183 | 850 | 259 | 3 |
0.90 | 156 | 47 | 250 | 76 | 400 | 122 | 570 | 174 | 2 |
1.25 | 118 | 36 | 185 | 56 | 300 | 91 | 425 | 129 | 1.5 |
APPENDIX "A" - COMPATIBLE DEVICES
This appendix lists compatible 2-WIRE SMOKE DETECTOR CONTROL PANELs and their compatible devices by manufacturer.
CANADIAN 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY (ULC)
NOTES:
- 1.* Reset time, hold for five seconds minimum.
- 2. Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 mA.
SMOKE DETECTOR | ||
---|---|---|
MAKE MODEL / BASE | MAKE MODEL / BASE | MAKE MODEL / BASE |
MIRCOM MIR-525 MIR-525T |
CERBERUS PYROTRONICS D1-2 D1-3 / DB-3S |
FENWAL PSD-7131 / 70-201000-001 PSD-7131 / 70-201000-002 PSD-7131 / 70-201000-003 PSD-7131 / 70-201000-005 |
SYSTEM SENSOR 1400-A 2400-A 1451-A / B401B 1451-A / B406B 2451-A / B401B 2451-A / B406B 1451DH / DH400A 2451-A / DH400A |
MIRTONE 73471 73494 73575 73495 / 73486 73495 / 73487 73595 / 73486 73595 / 73497 |
PSD-7130 / 70-201000-001 PSD-7130 / 70-201000-002 PSD-7130 / 70-201000-003 PSD-7130 / 70-201000-005 PSD-7128 / 70-201000-001 PSD-7126 / 70-201000-002 PSD-7126 / 70-201000-003 PSD-7126 / 70-201000-005 |
EDWARDS 6249C 6250C 6264C 6266C 6269C 6270C 6269C-003 6270C-003 |
SIMPLEX 2098-9110 |
PSD-7129 / 70-211002-000 PSD-7125 / 70-201000-001 PSD-7126 / 70-201000-002 PSD-7125 / 70-201000-003 PSD-7125 / 70-201000-005 CPD-7021 / 70-201000-001 CPD-7021 / 70-201000-002 CPD-7021 / 70-201000-003 CPD-7021 / 70-201000-005 |
UNITED STATES 2-WIRE SMOKE DETECTOR CONTROL PANEL COMPATIBILITY (ULI)
NOTES:
- 1. Reset time, hold for five seconds minimum.
- 2. Whether mixing different models of compatible smoke detectors, or using the same model on the same Circuit, total standby current of all detectors must not exceed 3 mA.
- 3. The below listed Smoke Detectors are compatible with Initiating Circuits having Compatability Identifier "A".
SMOKE DETECTOR | SMOKE DETECTOR | |||||||
---|---|---|---|---|---|---|---|---|
MAKE MODEL / BASE | COMPATIBILITY IDENTIFIER HEAD / BASE | RATED STANDBY CURRENT | MAKE MODEL / BASE | COMPATIBILITY IDENTIFIER HEAD / BASE | RATED STANDBY CURRENT | |||
SYSTEM SENSOR 1100 1151 / B110LP 1151 / B116LP 1400 1451 / B401 1451 / B401B 1451 / B406B 1451DH / DH400 2100 2100T 2151 / B110LP 2151 / B116LP 2400 2400TH 2400AT 2400AIT 2451 / B401B 2451 / B406B 2451 / DH400 2451TH / B401B 2451TH / B406B 2451 / B401 2451TH / B401 4451HT / B401B 4451HT / B406B 4451HT / B401 5451 / B401B 5451 / B401 5451 / B406B |
A - N/A A-A A-A A - N/A A-A A-A A-A A-A A - N/A A - N/A A-A A-A A - N/A A - N/A A - N/A A - N/A A-A A-A A - N/A A-A A-A A-A A-A A-A A-A A-A A-A A-A A-A |
0.12 mA 0.12 mA 0.12 mA 0.10 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA 0.12 mA |
SENTROL - ESL 429C 429CT 429CST 429CRT 711U / 701E, 701U, 702E, 702U 712U / 701E, 701U, 702E, 702U 713-5U / 701E, 701U, 702E, 702U 713-6U / 701E, 701U, 702E, 702U 721U / 702E, 702U 721UT / 702E, 702U 722U / 702E, 702U 731U / 702E, 702U, 702RE, 702RU 732U / 702E, 702U, 702RE, 702RU |
S10A - N/A S10A - N/A S11A - N/A S11A - N/A S10A - S00 S10A - S00 S10A - S00 S10A - S00 S10A - S00 S10A - S00 S10A - S00 S11A - S00 S11A - S00 |
0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA 0.10 mA |
DETECTION SYSTEMS INC. DS250 DS250TH DS282 DS282TH |
B - N/A B - N/A B - N/A B - N/A |
0.10 mA 0.10 mA 0.10 mA 0.10 mA |
MIRCOM MIR-525U MIR-525TU |
FDT-1 FDT-1 |
0.10 mA 0.10 mA |
UNITED STATES SIGNALING DEVICE CONTROL PANEL COMPATIBILITY (ULI)
System Sensor SpecrAlert | Wheelock | Gentex | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P2415 | P2415W | P241575 | P241575W | P2475 | AS-2415W-24-FR | AS-241575W-FR | AS-2430W-FR | AS-2475W-FR | AS-24110W-FR | AH-24-R | AVP-4-15-1 | AVP-4-15/75 | AVP-4-30/75 | AVP-4-110-1 | GXS-4-15-1 | GX90S-4-15-1 | |
P2475W | P24110 | P241575 | P24110W | S2415 | S2415W | AS-2415C-FW | AS-2430C-FW | AS-2475C-FW | AS-24100C-FW | NS-24110W-FR | NS-2475W-FR | GXS-4-15/75-W | GXS-4-30/75-W | GXS-4-15/75-C | GXS-4-110-1 | SHG15/75-W | SHG24-15-1 |
S241575 | S241575W | S2475 | S2475W | S24110 | S24110W | AH-24-WP-R | NS-2415W-FR | NS-241575W-FR | NS-2430W-FR | NS4-24110W-FR | NS4-2475W-FR | GX90S-4-15/75-W | GX90S-4-30/75W | GX90S-4-15/75-C | GX90S-4-110-1 | GOS24-15-1 | GOT24 |
H12/24 | H12/24W | MDL | MDLW | NS-241575W-FR | NS4-241575W-FR | NS4-2430W-FR | NS4-2475W-FR | RSS-2415W-FR | RSS-241575W-FR | SHG24-30/75-W | SHG24-15/75-C | GOS24-15/75 | GOS24-30/75 | GOS24-110-1 | GMS-24-15-1 | ||
RS-2415W-FR | RSS-2430W-FR | RSS-2415W-FR | RSS-241575W-FR | RSS-24110W-FR | RSS-2430C-FW | GOS24-15/75 | GMS-24-15-1 | GMS-24-15/75-W | GMS-24-30/75-W | GMS-24-15/75-C | GMS-24-110-1 | ||||||
RSS-2475W-FR | RSS-2475C-FW | RSS-24100C-FW | MT-12/24-ULC | MT-24-LS-VFR-ULC | MB-G6-24-R | GMH-24 | GMS-24-15-1 | GMS-24-15/75-W | GMS-24-30/75-W | GMS-24-15/75-C | WGMS-4/75 | ||||||
AMT-12/24-R-ULC | AMT-24-LS-VFR-ULC | MB-G10-24-R | MT-24-WS-VFR-ULC | SM-12/24-R | GMS-24-110-1 | ||||||||||||
DSM-12/24-R |
APPENDIX "B" - BATTERY CALCULATIONS (SELECTION GUIDE)
Use the form below to determine the required batteries.
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number | Description | Qty | STANDBY | TOTAL STANDBY | ALARM | TOTAL ALARM |
---|---|---|---|---|---|---|
FA-101U | Fire Alarm, 1 Det, 1 Sig | X | 0.066 | = | 0.125 | = |
FA-102U | Fire Alarm, 2 Det, 1 Sig | X | 0.076 | = | 0.135 | = |
FA-1025U | Fire Alarm, 5 Det, 2 Sig | X | 0.114 | = | 0.200 | = |
RTI-1 | Remote Trouble Indicator | X | 0.035 | = | 0.035 | = |
2-Wire Smoke Detectors | X | 0.0001 | = | * 0.090 | = 0.090 | |
4-Wire Smoke Detectors | X | = | = | = | = | |
Signal Load (bells, horns, strobes, and etc.) | = | = | = | = | ||
Total currents (Add above currents) | STANDBY (A) | (B) |
Total Current Requirement: ALARM (B)______ Amps.
Battery Capacity Requirement:
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [%Alarm in Hr.] _____) = (C) ______AH
Battery Selection: Multiply (C) by 1.20 to derate battery.
Batteries BA-104 (4.0AH) and BA-1065(6.5AH) fit into the backboxes ; all larger batteries such as BA-110(10AH) and the BA-117(17AH) require an external battery box.
* Assuming three Initiating Circuits in alarm.
% Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
' Using the MIR-425/U 2-wire smoke detector. See Appendix "A", for other available smoke detectors.