Mircom Addendum for LT-657 FX-2000 Installation and Instruction Manual
Following are some new features incorporated into the FX-2000 Fire Alarm Control Panel:
New Features
-
UUKL Feature: A new UUKL feature is available on the FX-2000 Configurator, used exclusively with the FDG-008 and FDX-008 Fan Damper Controller modules. Refer to manual LT-966 for comprehensive details. This feature allows for an "Any of" operation setting for each UUKL relay/equipment set. If selected, the panel will still enter alarm if any detector is tripped. The distinction lies in relays configured for "any of" operation in smoke control, which will only activate after a specified number of detectors are active. This is intended for atriums where multiple detector activations are needed to initiate smoke control, while building signaling is based on the first detector activation.
-
Output Circuit Delay Operation: A new feature allows for delayed relay functions associated with alarm initiating circuits. An Output Delay timer is linked to this feature, as detailed in the table below. Programming is done via the FX-2000 Configuration software. The Output Delay timer is specifically intended for elevator recall purposes.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product features field-programmable software. To ensure compliance with Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be restricted to specific values or not used as indicated below.
Program feature or option | Permitted in UL 864? (Y/N) | Possible settings | Settings permitted in UL 864 |
---|---|---|---|
Delay Output Timer | YES | 4 seconds maximum (due to worst case loop delay of 6 seconds) | 10 seconds |