Siemens Venturi Air Valve Installation Instructions
Document No. 546-00580 | May 22, 2012
Product Overview
The Siemens Venturi Air Valve is a pre-packaged, easy-to-install airflow measurement and control solution. It provides stable and precise airflow control for room supply, room general exhaust, or fume hood exhaust.
Options
- Sizes: 6 in, 8 in, 10 in, 12 in, 2 x 10 in, 2 x 12 in, 3 x 12 in
- Construction: Aluminum or Heresite coated
- Controller Integration: Laboratory Room Controller (LRC) in an enclosure with or without Fume hoods
- Control Types: Constant Air Volume Controller (CAV), Variable Air Volume Controller (VAV)
- Additional Features: Hot water reheat coils (one or two row)
Electronic Actuation
Control packages include fast-acting or basic electronic actuation (optional) and a differential pressure transmitter (optional). These components are factory-mounted in an enclosure on the outside of the valve.
Expected Installation Time
30 minutes
Required Tools and Materials
- Small flat blade screwdriver
- 3/8-inch open end wrench
- Needle nose pliers
- Sealant
- 1/4-inch poly tubing
Prerequisites
- Valve ductwork free of debris
- Construction filters in place
- Supply/Exhaust ductwork installed
- Water lines installed (if reheat coils are used)
Installation Instructions
These installation instructions are provided for various actuator types of Venturi Air Valves and consist of the following sections:
- Section 1: Mounting the valve.
- Section 2: Adjusting AVC airflow.
- Section 3: Actuation and sensors.
Section 1: Mounting
- Move the valve to the installation area. Remove the valve from its shipping package. Do not carry the valve by the flow sensor, valve extension rod, or any controls. Refer to Table 1 for single-body and Table 3 for multi-body valve measurements.
- Verify the correct airflow direction and orientation of the valve in the ductwork (e.g., Horizontal).
- Support the ductwork within 12 inches of the valve.
- Connect the ductwork to the valve's inlet collar using drawband, bolting, or other accepted trade practice.
A diagram illustrates a drawband connection for ductwork and valve.
- Connect the ductwork to the valve's outlet collar using drawband, bolting, or other accepted trade practice.
- Seal all ductwork and verify that the duct connections are airtight.
Venturi Air Valve Dimensions
Table 1: Single-body Venturi Air Valve Dimensions
Air Valve Size | Length (L) | Inlet/Outlet Outside Dia. (OD) | Overall Height (HO) | Overall Height with Enclosure (HE) | Overall Width with Enclosure (WE) | |||||
---|---|---|---|---|---|---|---|---|---|---|
106 | 21 3/4 | 552 | 5 15/16 | 151 | 13 15/16 | 354 | 13 7/8 | 352 | 9 1/4 | 235 |
108 | 24 3/4 | 629 | 7 7/8 | 200 | 15 7/8 | 403 | 14 7/8 | 378 | 9 1/4 | 235 |
110 | 26 1/2 | 673 | 9 7/8 | 251 | 17 7/8 | 454 | 15 7/8 | 403 | 10 | 254 |
112 | 29 1/2 | 749 | 11 7/8 | 302 | 19 7/8 | 505 | 17 7/8 | 454 | 12 | 305 |
Valve Configurations
Diagrams illustrate different valve configurations:
- AVC (Constant Volume): No actuator. Dimension HO = OD + 4".
- AVV (Variable Volume) with Actuator Bracket: Dimension HO = OD + 8".
- AVV (Variable Volume) with Enclosure: Dimension WE = Max [W1 or W2]. Requires 12" spacing around the enclosure for access.
Flanged ends are available for single-body Air Valves, without bolt holes. These have a Flange End width of 1.5 inches.
Table 2: Multi-Body Venturi Air Valve Dimensions
Slip Configuration (S & I)
Size | Matching Duct Minimum Inside | Matching Duct Outside Dimension | Face-to-face Lengtha) (L1) | Slip Tab Length | Overall Height with Enclosure | ||
---|---|---|---|---|---|---|---|
Height | Width | Height (H) | Width (W) | ||||
2x10 | 10 | 21 | 11 | 22 | 29 1/2 | 1.5 | 19 |
2x12 | 12 | 25 | 13 | 26 | 32 1/2 | 1.5 | 21 |
3x12 | 12 | 38 | 13 | 39 | 32 1/2 | 1.5 | 21 |
a) Slip end Air Valves need an extra 3 inches of clearance during installation.
Flange Configuration (F & J)
Size | Matching Duct Minimum Inside | Matching Duct Outside Dimension | Face-to-face Lengtha) (L1-3) | Overall Height with Enclosure | ||
---|---|---|---|---|---|---|
Height | Width | Height (H) | Width (W) | |||
2x10 | 10 | 21 | 12 | 23 | 26 1/2 | 19 |
2x12 | 12 | 25 | 14 | 27 | 29 1/2 | 21 |
3x12 | 12 | 38 | 14 | 40 | 29 1/2 | 21 |
Diagrams of a Dual Air Valve -- Slip End and a Triple Air Valve -- Flange End are provided.
Section 2: Adjusting AVC Valve Airflow
The control arm is held by a threaded rod with two nuts on opposite sides of the flange on the indicator gauge. To change the flow setting:
- Locate the nut on the upstream side of the indicator gauge flange (towards the valve inlet where the flow sensor is located). This is the calibration locking nut. Loosen this nut and back it off to provide sufficient distance to adjust the flow.
- Locate the nut on the downstream side to move the control arm. This is the flow adjustment nut. Turning this nut clockwise reduces airflow. Turn it counter-clockwise to increase airflow rate.
- Once the required airflow is achieved, tighten the calibration locking nut.
Diagrams for Style 1 AVC and Style 2 AVC are provided, showing the flow adjustment nut and calibration locking nut.
Section 3: Controls, Sensors and Actuation
Differential Pressure Transmitter
Connect a two-conductor 20 AWG cable to the controller's 4 to 20 mA input. Connect the wire to the differential pressure transmitter or through the wiring bushing/knockout to the transmitter inside the enclosure. Connect the cable to the differential pressure transmitter.
A diagram illustrates differential pressure transmitter wiring connections, showing high-pressure port, low-pressure port, span adjustment, zero adjustment, and transducer terminals.
GMA 121 Actuation
2-position control, 24 Vac/dc.
Table 4: 2-position Control 24 Vac
Standard Symbol | Function | Terminal Designation | Color | Color Symbol |
---|---|---|---|---|
1 | Supply (SP) | G | Red | RD |
2 | System Neutral | G0 | Black | BK |
A diagram shows the wiring for 2-position GMA 121 Actuators.
GDE/GLB 131 Actuation
Wiring
- All wiring must conform to NEC and local codes and regulations.
- Use earth ground isolating step-down Class 2 transformers. Do not use auto transformers.
- Determine the supply transformer rating by summing the total VA of all actuators used.
Three-position control (24 Vac), 24 Vac power supply.
Table 5: 3-position Control 24 Vac
Standard Symbol | Function | Terminal Designation | Color Standard | Plenum Color |
---|---|---|---|---|
1 | Supply (SP) | G | Red | Red |
6 | Control signal clockwise | Y1 | Violet | Violet |
7 | Control signal counter-clockwise | Y2 | Orange | Orange |
GLB/GDE/GMA 161 Actuation
Modulating control (0-10V), 24 Vac/dc.
Table 6: Modulating Control 24 Vac
Standard Symbol | Function | Terminal Designation | Color | Color Symbol |
---|---|---|---|---|
1 | Supply (SP) | G | Red | RD |
2 | System Neutral | G0 | Black | BK |
8 | Input Signal: 0-10 Vdc (GMA161) or 2-10 Vdc (GMA15x) | Y | Gray | GY |
9 | Position Output: 0-10 Vdc (GMA161) or 2-10 Vdc (GMA15x) | U | Pink | PK |
A diagram shows actuator wiring for VAV/CV TECs.
GNP191 Actuation - Modulating Control (0 to 10 Vdc)
- Connect the Fast Acting Lab Electronic Actuator to a source of 24 Vac power.
- Connect the wire from the Fast Acting Lab Electronic Actuator to the controller.
Diagrams show switch settings for the Fast Acting Lab Electronic Actuator for both supply and exhaust configurations.
GNP191 Actuation - Pulsed Control
- Connect the Fast Acting Lab Electronic Actuator to a source of 24 Vac power.
- Connect the wire from the Fast Acting Lab Electronic Actuator to the controller.
Diagrams show switch settings for the Fast Acting Lab Electronic Actuator for both supply and exhaust configurations.