Instruction Manual for SIEMENS models including: SKD62UA Electronic Valve Actuator, SKD62UA, Electronic Valve Actuator, Valve Actuator, Actuator

SKD...U Electronic Valve Actuator

Installation Instructions

CPS;, 129-217;, 2018-02-28

Mary Alice Helms; Sue McGlade

Installation Instructions

Siemens SKD62UA Valve Actuator - Adaptive HVAC Supplies

Siemens SKD62U Valve Actuator - Adaptive HVAC Supplies

SKD...U Electronic Valve Actuator


File Info : application/pdf, 6 Pages, 593.37KB

PDF preview unavailable. Download the PDF instead.

44838 SKD..U-Electronic-Valve-Installation-Instructions en
Installation Instructions Document No. 129-217 September 24, 2018

SKD...U Electronic Valve Actuator

Product Description

The SKD...U actuator requires a 24 Vac supply signal to control a FlowriteTM 599 Series valve with a 3/4-inch (20 mm) stroke.

Product Numbers

Non-Spring Return SKD60U SKD82.50U

Spring Return SKD62U SKD82.51U

Warning/Caution Notations

WARNING: CAUTION:
Required Tools

Personal injury or loss of life may occur if you do not follow a procedure as specified.
Equipment damage or loss of data may occur if you do not follow a procedure as specified.

· 5 mm Allen wrench · Small and medium flat-blade screwdrivers

Expected Installation Time
20 minutes for factory-installed actuator 45 minutes for field replacement of actuator

Prerequisites
WARNING:
If mounting the actuator to a valve already in line, either close the shut-off valves in the piping (upstream first, then downstream) or switch off the pump to allow the differential and static pressure in the valve to drop.

Mounting Positions
Figure 1. Acceptable Mounting Positions.
Using the Weather Shield
The SKD must be in the vertical position. Complete instructions for the mounting of the Weather Shield are included with that product. NOTE: Use the top knockout position when installing
the Weather Shield. See Figure 17.
Figure 2. Weather Shield Installation Position.
Installation
If you are mounting an actuator on a new valve, begin with the instructions in Figure 3.

Item Number: 129-217-04, Rev. DA

Page 1 of 6

Document No. 129-217 Installation Instructions September 24, 2018
Removing the Actuator from the Valve
1. Remove the actuator cover. 2. Disconnect the wires and conduit, if installed. 3. Loosen the valve stem retainer using a 5 mm Allen
wrench and lower the valve stem into the valve. 4. Loosen the yoke nuts using a 5 mm Allen wrench
in the actuator yoke. 5. Remove the actuator from the valve, being careful
not to damage the valve stem. Continue with Mounting an Actuator to a Valve.

5
Figure 6. NOTE: Hold the stem retainer in place as you tighten
it around the valve stem. See Figure 6.

Figure 3. Preparing a new Valve.
Mounting an Actuator to a Valve.
NOTE: Install the stem heating element, (P/N ASZ6.6), if used, before proceeding.
1
2
Figure 4. NOTE: Ensure the yoke nuts are loose enough to
allow the actuator to slip over the bonnet. See Figure 5.
4 3
Figure 5.

6
Figure 7. NOTE: Position the actuator to accommodate the
wiring. Hold the actuator in place while tightening the yoke nuts. See Figure 7.
7
Figure 8.

Page 2 of 6

Siemens Industry, Inc.

Wiring
CAUTION: Use care when removing the knockout. Do not damage the circuit board.

Do not use autotransformers. Use earth ground isolating step-down Class 2 transformers.
Determine supply transformer rating by summing total VA of all actuators used. The maximum rating for a Class 2 power supply circuit is 100 VA.

Actuator

Power

Actuators Per

Consumption Class 2 Supply Circuit*

(80% of Transformer VA)

SKD6...U

17 VA

4

SKD82.50U

13 VA

8

SKD82.51U

18 VA

5

* Operating more actuators requires additional

transformers or separate 100 VA power supplies.

Wiring Diagrams
SKD60U/SKD62U SKD82.50U/51U
SKD6...U

Figures 9 and 10 Figures 11 through 13

Document Number: 129-217 Installation Instructions September 24, 2018
Figure 10.
Connecting Terminals
24 Vac G System Potential (SP) G0 System Neutral (SN) Y Control Input: 0 to 10 Vdc or 4 to 20 mA
(DIP switch selectable) Z Override Control
(See Technical Instructions 155-180P25) M Measuring Neutral U Output for 0 to 10 Vdc or 4 to 20 mA
measuring voltage. It will match the input signal type. The position output signal U will switch from 0 to 10 Vdc to 4 to 20 mA when a 4 to 20 mA input signal is selected and used on the terminal.
Wiring for SKD82...U

1

2

Figure 9. SKD6...U.

DIP Switches

1 Selection of Control Signal

2 Selection of Flow
Characteristic

ON

4 to 20 mA

Modified*

OFF (Factory Setting)

0 to 10 Vdc

Default

*Changing the default setting will modify an equal

percentage valve to a linear flow characteristic. When

set to default, the flow characteristic is determined by

the valve body.

Figure 11. Location of Terminals.

Siemens Industry, Inc.

Page 3 of 6

Document No. 129-217 Installation Instructions September 24, 2018
Wiring for SKD82...U, Continued

Figure 12. Non-Spring Return SKD82.50U. Connecting Terminals

G Y1 Y2 Cm1 c1 c2 1000 

System Potential 24 Vac (+) Outward movement of coupling piece (0 to 1) Inward movement of coupling piece (1 to 0) Limit switch for 100% stroke ASC9.3DU double auxiliary switch ASC9.3DU double auxiliary switch ASZ7.3 potentiometer

The diagram shows all possible connections. How many and which are used depend on the application.

Figure 13. Spring Return SKD82.51U.

Connecting Terminals

G

System Potential 24 Vac (+)

21

System Neutral (SN)

Y1

Outward movement of coupling piece (0 to 1)

Y2

Inward movement of coupling piece (1 to 0)

Cm1 Limit switch for 100% stroke

c1

ASC9.3DU double auxiliary switch

c2

ASC9.3DU double auxiliary switch

1000  ASZ7.3 potentiometer

The diagram shows all possible connections. How many and which are used depend on the application.

Start-Up
Check the wiring for proper connections.
Consult Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Technical Instructions 155-180P25 for detailed commissioning information.
Normally Closed Valve
Actuator pressure cylinder moves: · Outward (0 to 1): Valve opens. · Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves: · Outward (0 to 1): Valve closes. · Inward (1 to 0): Valve opens.

Page 4 of 6

Siemens Industry, Inc.

Three-Way Valve
Actuator pressure cylinder moves: · Outward: Valve opens between port NC and C.
· Inward: Valve opens between ports NO and C.

NOTE: The valve body assembly determines the complete assembly action.

Reference

Technical Instruction

Document Number

Flowrite EA599 Series SKD Electronic Valve Actuator Proportional Control Flowrite EA599 Series SKD Electronic Valve Actuator 3-position (Floating) Control

155-180P25 155-181P25

Manual Operation

Dimensions

Document Number: 129-217 Installation Instructions September 24, 2018

Figure 14. Manual Override in Manual and Automatic Position.
Each complete revolution (360°) is equal to 3/32-inch (2.5 mm) stroke.

Figure 16. Dimensions of the 599-10071 Weather Shield in Inches (Millimeters).

Figure 15. Valve Stem Travel Indication. Siemens Industry, Inc.

Page 5 of 6

Document No. 129-217 Installation Instructions September 24, 2018
Dimensions, Continued
CAUTION: Be careful when removing the knockout. Do not damage the circuit board.
NOTE: Use the top knockout position when installing the Weather Shield.

SERVICE ENVELOPE MINIMUM ACCESS
SPACE RECOMMENDED 4 inches (100 mm)
8 inches (200 mm)

Figure 17. SKD...U Dimensions in Inches (Millimeters).

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Flowrite is a trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2018 Siemens Industry, Inc.

Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel. +1 847-215-1000

Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com

Document No. 129-217 Printed in the USA