Siemens Differential Pressure Monitor
Technical Specification Sheet Rev. 4, July, 2005
Differential Pressure Monitor
The Differential Pressure Monitor (DPM) is an integral part of the APOGEE ® Automation System. The monitor measures and displays the differential pressure between a room and its adjoining space. It is used for monitoring in hospital pharmacies and isolation rooms, and also in labs, areas surrounding labs, holding rooms, and other areas where knowledge of the differential pressure is important.
The Differential Pressure Monitor can operate stand-alone or networked to the APOGEE Automation System. When used with the APOGEE Automation System, alarm, differential pressure values, and status point information can be communicated via a Local Area Network (LAN) to a central terminal for display and recording.
Features
- Through-the-wall differential pressure measurement
- Digital display of pressure (inches of water / Pascals)
- LED indicators for normal and alarm status
- Audible horn indicates alarm condition
- Return from power failure without operator intervention
- Optional 2-position keyed switch disables alarms, available in separate models enabling alarms for: > negative pressure (infectious isolation) > positive pressure (protective isolation)
- Control parameters assigned and changed using the Portable Operator's Terminal
- Proven system architecture
Description
The DPM consists of the following:
- A Liquid Crystal Display (LCD) which displays:
- State of pressure mode key switch (optional)
- Pressure monitoring mode
- High pressure alarm
- Low pressure alarm
- General failure
- Status of door switch
- Anteroom status
- Differential Pressure (In.w.c. or Pa)
- 2 LED status lights: green indicating normal operation; red indicating alarm condition
- Audible horn with Horn silence button
- Interfaces to:
- One or two Remote Pressure Transmitters
- APOGEE LAN communication
- Portable Operator's Terminal port
- Auxiliary alarm relay output
- 4-20 mA output of pressure
- Door switch contact
- Optional 2-position keyed switch disables alarms for space cleaning and maintenance.
- Separate keyed switch models for: > negative pressure (infectious isolation) > positive pressure (protective isolation)
Monitor Specifications
Specifications | Details |
Power Requirements | 18-28 Vac 50/60 Hz |
Operating Range | 2.2 VA @ 24 Vac |
Power Consumption | LAN trunk |
Local Communication | Portable Operator's Terminal |
Inputs | Digital: 2 Remote Pressure Transmitters, 1 dry contact |
Outputs | Analog: 1 4-20 mA (pressure) Digital: 1 resistive (mode switch), 2 dry contacts |
LEDs | 1 green, 1 red |
Alarm | 1 horn, 85 dbs @ 4" (10 cm) |
Ambient Conditions | Storage Temp: -40°F to 167°F (-40°C to 75°C) Operating Temp: 32°F to 120°F (0°C to 49°C) Humidity Range: 10% to 90% (non-condensing) |
Dimensions | 8.5" W x 4.5" H x 1.5" D (216 mm x 114 mm x 38 mm) |
Weight | 15 oz (410 g) |
Agency Listings | UL 916 PAZX, UL 864 UDTZ, CSA Certified, FCC Compliance Part 15, CI. A |
NOTE: Authorities having jurisdiction over healthcare facilities may not allow monitors with keyed switches. Please check with local codes before ordering.
Remote Pressure Transmitter
The Remote Pressure Transmitter (RPT) measures the differential pressure between a room and its adjoining space. The RPT uses thermal anemometer technology to measure the air pressure differential between two spaces. These values are then transmitted through a proprietary output signal to an input of the DPM, which converts the signal to a differential pressure measurement. The RPT is designed to be mounted in a through-the-wall installation. It is calibrated after installation. This calibration is made easy through the use of a proprietary NIST traceable calibration tool.
RPT Specifications
Specifications | Details |
Power Requirements | 18-28 Vac 50/60 Hz |
Operating Range | 1.4 VA @ 24 Vac |
Power Consumption | 500 ft. (150 m) |
Maximum Distance from Differential Pressure Monitor | -0.2" to +0.2" of water (-49.8 to + 49.8 Pascals) |
Measurement Range | ±0.001" of water (±0.3 Pascals) |
Accuracy | 0.0035 CFM (100 CCM) |
Airflow Across Sensor | Minimum: 0.0035 CFM (100 CCM) Maximum: 0.35 CFM (10,000 CCM) |
Ambient Conditions | Temperature Range: 65°F to 85°F (18°C to 30°C) Humidity Range: 10% to 90% (non-condensing) |
Product Ordering Information
Description | Product Part Number |
Differential Pressure Monitor (DPM) without Keyed Switch | 547-002 |
DPM with 2-position Keyed Switch, NEGATIVE / NEUTRAL | 547-005 |
DPM with 2-position Keyed Switch, POSITIVE / NEUTRAL | 547-006 |
Remote Pressure Transmitter | 547-003 |
Differential Pressure Monitor Calibration Tool | 547-004 |
Remote Pressure Transmitter | 149-903 |
NOTE: DPM with 3-position Keyed Switch, 547-001, is only offered as a service replacement part. Contact your local Siemens Building Technologies office for assistance.
Related Documents
- Healthcare Isolation Rooms Architectural and Mechanical Design Considerations Technology Report