Data sheet Electro-hydraulic actuators for valves

4

Data sheet Electro-hydraulic actuators for valves, SKC.., N4566

Siemens Building Technologies Frank Ernst

Electrohydraulic actuators SKC32.. for valves SKC82 ...

• Manual adjuster and position indicator • Optional functions with auxiliary switches, potentiometer and stem heater • SKC..U are UL-approved Use . For the operation of Siemens 2-port and 3-port valves, types VVF.. and VXF.. with a 40 mm stroke as control and safety shut-off valves in heating, ventilation and air conditioning systems ...

Data sheet Electro-hydraulic actuators for valves - Derossi ...

Manual adjuster and position indicator. • Optional functions with auxiliary switches, potentiometer and stem heater. • SKC..U are UL-approved.

Electrohydraulic actuators SKC32.. for valves SKC82.. SKC62 ...

In the manual operation mode the control signals Y and Z can further open the valve but cannot move to the «0%» stroke position of the valve. To retain the manually set position, switch off the power supply or disconnect the control signals Y and Z. The red indicator marked «MAN» is visible.

PDF preview unavailable. Download the PDF instead.

SKC62 Datasheet en
4566

Use
CM1N4566E 26.06.2012

Electrohydraulic actuators for valves
with a 40 mm stroke

SKC32.. SKC82.. SKC62.. SKC60

· SKC32.. Operating voltage AC 230 V, 3-position control signal · SKC82.. Operating voltage AC 24 V, 3-position control signal · SKC6.. Operating voltage AC 24 V, control signal DC 0...10 V, 4...20 mA or
0...1000  · SKC6.. Choice of flow characteristic, position feedback, stroke calibration,
LED status indication, override control · SKC62UA with functions choice of direction of operation, stroke limit control,
sequence control with adjustable start point and operating range, operation of frost protection monitors QAF21.. and QAF61.. · Positioning force 2800 N · Actuator versions with or without spring-return function · For direct mounting on valves; no adjustments required · Manual adjuster and position indicator · Optional functions with auxiliary switches, potentiometer and stem heater · SKC..U are UL-approved

For the operation of Siemens 2-port and 3-port valves, types VVF.. and VXF.. with a 40 mm stroke as control and safety shut-off valves in heating, ventilation and air conditioning systems.

Building Technologies

Types
Standard electronics Enhanced electronics TÜV tested as per DIN EN 14597
Accessories
Ordering Delivery Spare parts

Type
SKC32.60 SKC32.61 2) SKC82.60 SKC82.60U * SKC82.61 SKC82.61U * SKC62 2) SKC62U * SKC60 SKC62UA *

Operating voltage
AC 230 V
AC 24 V

Positioning signal
3-position
DC 0...10 V, 4...20 mA,
or 0...1000 

Spring-return Positioning time Enhanced Function Time Opening Closing functions

yes 18 s

120 s

yes 18 s 120 s

yes 20 s yes 20 s

20 s

yes 1)

1) Direction of operation, stroke limit control, sequence control, signal addition 2) Control devices MK..5.., MK..6.. and MK..5..G are TÜV tested per DIN EN 14597 and can therefore
be used as control devices with safety shut-off function for protection against excessive temperature and pressure. * UL-approved versions

Product No. Stock number Description

Data sheet

MK..5.. MK..6. MK..5..G

S55329-M1.. S55329-M1.. S55329-M1..

Control device PN 25 for safety function per DIN EN N4387 14597, for water Control device PN 40 for safety function per DIN EN N4388 14597, for water, steam, brine and heat transfer oil Control device PN 25 for safety function per DIN EN N4389 14597, for steam

Type ASC1.6 ASC9.3 ASZ7.3 ASZ7.31 ASZ7.32 ASZ6.5

Description Auxiliary switch Dual auxiliary switches Potentiometer 1000  Potentiometer 135  Potentiometer 200  Stem heater AC 24 V

For actuator SKC6..
SKC32.. SKC82..
SKC..

Mounting location 1 x ASC 1.6 1 x ASC9.3 or 1 x ASZ7.3 or 1 x ASZ7.31 or 1 x ASZ7.32
1 x ASZ6.5

When ordering please specify the quantity, product name and type code. Example: 1 actuator, type SKC32.60 and
1 potentiometer, 135 , type ASZ7.31
The actuator, valve and accessories are supplied in separate packaging and not assembled prior to delivery.
See overview, section «Replacement parts», page 17.

2/18
Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

Equipment combinations

Rev. no.

Note

Valve type

DN

PN-class

kvs [m3/h]

Two-port valves VV... (control valves or safety shut-off valves)):

data sheet

VVF21... VVF31... VVF40... VVF41... VVF45... VVF43.. VVF53..

Flange Flange Flange Flange Flange Flansch Flansch

100

6

100...150

10

100...150

16

65...150

16

65...150

16

65...150

161)

65...150

25

124...160 124...315 124...315
49...300 49...300 50...400 63...400

4310 4320 4330 4340 4345 4404 4405

VVF61...

Flange

65...150

40

49...300

4382

Three-port valves VX... (control valves for «mixing» and« diverting»):

VXF21...

Flange

100

6

124...160

4410

VXF31...

Flange

100...150

10

124...315

4420

VXF40...

Flange

100...150

16

124...315

4430

VXF41...

Flange

65...150

16

49...300

4440

VXF43..

Flansch

65...150

161)

63...400

4404

VXF53..

Flansch

65...150

25

63...400

4405

VXF61...

Flange

65...150

40

49...300

4482

1) For DN  50 see VVF53.. or VXF53.. PN 25 (Data sheet N4405): Flange dimensions PN 25 same as for PN 16

For admissible differential pressures pmax and closing pressures ps, refer to the relevant valve data sheets.

Third-party valves with strokes between 12...40 mm can be motorized, provided they are «closed with the de-energized» fail-safe mechanism and provided that the necessary mechanical coupling is available. For SKC32.. and SKC82.. actuators the Y1 signal must be routed via an additional freely-adjustable end switch (ASC9.3) to limit the stroke. We recommend that you contact your local Siemens office for the necessary information.

Overview table, see page 17.

Technology Principle of electro-hydraulic actuators
Valve closed

4567Z0 1 4567Z02

Valve open

1

2

3

4

5 1 Manual adjuster

6

2 Pressure cylinder

7

8

3 Suction chamber

9 10

4 Return spring

11

5 Solenoid valve

12

6 Hydraulic pump

7 Piston

8 Pressure chamber

9 Position indicator (0 to 1)

10 Coupling

11 Valve stem

12 Plug

Siemens Building Technologies

Electrohydraulic actuators for valves

3/18
CM1N4566E 26.06.2012

Opening the valve
Closing the valve
Manual operation mode
Note: Controller in manual operation
Automatic mode
Minimal volumetric flow Spring-return facility
TÜV tested as per DIN EN 14597
SKC32../SKC82.. 3-position control signal
SKC62.., SKC60 Y control signal DC 0...10 V and/or DC 4...20 mA, 0...1000 
Frost protection monitor Frost protection thermostat
4/18 Siemens Building Technologies

The hydraulic pump (6) forces oil from the suction chamber (3) to the pressure chamber (8) and thereby moving the pressure cylinder (2) downwards. The valve stem (11) retracts and the valve opens. Simultaneously the return spring (4) is compressed.

Activating the solenoid valve (5) allows the oil in the pressure chamber to flow back into the suction chamber. The compressed return spring moves the pressure cylinder upwards. The valve stem extends and the valve closes

Turning the manual adjuster (1) clockwise moves the pressure cylinder downwards and opens the valve. Simultaneously the return spring is compressed. In the manual operation mode the control signals Y and Z can further open the valve but cannot move to the «0%» stroke position of the valve. To retain the manually set position, switch off the power supply or disconnect the control signals Y and Z. The red indicator marked «MAN» is visible. When setting the controller for a longer time period to manual operation, we recommend adjusting the actuator with the manual adjuster to the desired position. This guarantees that the actuator remains in this position for that time period. Attention: Do not forget to switch back to automatic operation after the controller is set back to automatic control.

Turn the manual adjuster counterclockwise to the end stop. The pressure cylinder moves upward to the «0%» stroke position of the valve. The red indicator marked «MAN» is no longer visible.

The actuator can manually be adjusted to a stroke position > 0 % allowing its use in applications requiring constantly a minimal volumetric flow. The SKC32.61, SKC82.61.. and SKC62.. actuators, which feature a spring-return function, incorporate an additional solenoid valve which opens if the control signal or power fails. The return spring causes the actuator to move to the «0 %» stroke position and closes the valve.

Control devices TÜV tested per DIN EN 14597 can be used as control devices with safety shut-off function for protection against excessive temperature and pressure:
 Water: MK..5.., PN 25, see data sheet N4387  Steam: MK..5..G, PN 25, see data sheet N4389  Water, steam, brine, heat transfer oil: MK..6.., PN 40, see data sheet N4388

The valve is controlled by a 3-position signal either via terminals Y1 or Y2 and generates the desired stroke by means of above described principle of operation.

· Voltage on Y1 · Voltage on Y2 · No voltage on Y1 and Y2

piston extends

valve opens

piston retracts

valve closes

piston / valve stem remain in the respective position

The valve is either controlled via terminal Y or override control Z. The positioning signal Y generates the desired stroke by means of above described principle of operation.

· Signal Y increasing: · Signal Y decreasing: · Signal Y constant: · Override control Z

piston extends

valve opens

piston retracts

valve closes

piston / valve stem remain in the respective position

see description of override control input, page 8

A frost protection thermostat can be connected to the SKC6.. actuator. The added signals from the QAF21.. and QAF61.. require the use of SKC62UA actuators. Notes on special programming of the electronics are described under «Enhanced electronics» on page 5. «Connection diagrams» for operation with frost protection thermostat or frost protection monitor refer to page 15.

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

4567Z03

Standard electronics SKC62.., SKC60

Z
0...10V 4...20mA
Calib. Status

Calib.

Status
green

ok calib.

error

red

valve

jam

1 Connection terminals 2 Mode DIL switches 3 LED status indication 4 Slot for calibration

DIL switches SKC62.., SKC60

Positioning signal Y Position feedback U

ON

ON

DC 4...20 mA

12

4567Z05

ON
OFF *)
12

DC 0...10 V

4567Z06

*) Factory setting: All switches OFF

Enhanced electronics SKC62UA

Flow characteristic

4567Z07

ON
lin = linear
12
ON
log = equal percentage
12

4567Z08

Relationship

V100

between control

signal Y and

volumetric flow

V0

0

4

log

lin 10 V 20 mA

Z
0...10V 4...20mA
Calib. Status

Calib.

Status
green

ok calib.

error

red

valve

jam

1 Connection terminals 2 DIL switches 3 LED status indication 4 Stroke calibration 5 Rotary switch Up
(factory setting 0) 6 Rotary switch Lo

Siemens Building Technologies

Electrohydraulic actuators for valves

5/18
CM1N4566E 26.06.2012

DIL switches SKC62UA
Selection of direction of operation SKC62UA
Note

Direction of operation Sequence control or stroke limit control

Control signal Y

Flow characteristic

Position feedback U

Sequence control

ON

reverse-acting

Signal addition

DC 4...20 mA

lin = linear

QAF21../QAF61..

OFF *

direct-acting

* Factory settings: all switches OFF

Stroke limit control

DC 0...10 V

log = equal percentage

Relationship

V100

between control

signal Y and

volumetric flow V0 0 4

log

lin 10 V 20 mA

· With normally-closed valves, «direct-acting» means that with a signal input of 0 V, the valve closes (applies to all Siemens valves listed under «equipment combinations» on page 3)
· With normally-open valves, «direct-acting» means that with a signal input of 0 V, the valve is open.

Direct acting

Reverse-acting

0 %

(10 V) 100 %

Stroke
100 %

Reverse-acting

Input

Y

100 % (10 V)

DC 0...10 V DC 4...20 mA
0...1000 

Input

Y
0 %
DC 10...0 V DC 20...4 mA 1000...0 

Direct
0 % 0 V 4 mA
0 

10 V Y 20 mA 1000 

The mechanical spring-return function is not affected by the direction of operation selected.

Stroke limit control and sequence control SKC62UA

Setting the stroke limit control
The rotary switches LO and UP can be used to apply an upper and lower limit to the stroke in increments of 3%, up to a maximum of 45%

Setting the sequence control
The rotary switches LO and UP can be used to determine the starting point or the operating range of a sequence.

6/18
Siemens Building Technologies

Position of LO
0 1 2 3 4 5 6 7 8 9 A B C

Lower stroke limit
0 % 3 % 6 % 9 % 12 % 15 % 18 % 21 % 24 % 27 % 30 % 33 % 36 %

Position of UP
0 1 2 3 4 5 6 7 8 9 A B C

Upper stroke limit
100 % 97 % 94 % 91 % 88 % 85 % 82 % 79 % 76 % 73 % 70 % 67 % 64 %

Electrohydraulic actuators for valves

Position Starting point for Position of LO sequence control of UP

0

0 V

0

1

1 V

1

2

2 V

2

3

3 V

3

4

4 V

4

5

5 V

5

6

6 V

6

7

7 V

7

8

8 V

8

9

9 V

9

A

10 V

A

B

11 V

B

C

12 V

C

Operating range of sequence control
10 V 10 V * 10 V **
3 V *** 4 V 5 V 6 V 7 V 8 V 9 V 10 V 11 V 12 V

CM1N4566E 26.06.2012

Stroke control with QAF21.. / QAF61.. signal addition SKC62UA only Calibration SKC62.., SKC60
Indication of operating state SKC62.., SKC60

D

39 %

D

61 %

E

42 %

E

58 %

F

45 %

F

55 %

D

13 V

E

14 V

F

15 V

D

13 V

E

14 V

F

15 V

* Operating range of QAF21.. (see below) ** Operating range of QAF61.. (see below) *** The smallest adjustment is 3 V; control with 0...30 V is only possible via Y.

Calib.
Lo Up

Setting the signal addition

The operating range of the frost protection monitor (QAF21.. or QAF61..) can be defined with rotary switches LO and UP.

Position Sequence control Position QAF21../ QAF61..

of LO

start point

of UP

operating range

0

1

QAF21..

0

2

QAF61..

In order to determine the stroke positions 0 % and 100 % in the valve, calibration is required on initial commissioning:

Prerequisites

· Mechanical coupling of the actuator SKC6.. with a Siemens valve

· Actuator must be in «Automatic operation» enabling stroke calibration to capture the effective 0 % and 100 % values
· AC 24 V power supply · Housing cover removed

Calibration

1. Short-circuit contacts in calibration slot (e.g. with a screwdriver)
2. Actuator moves to «0 %» stroke position (1) (valve closed)

01124
green LED flashes; position feedback U inactive

3. Actuator moves to «100 %» stroke position (2) (valve open)
4. Measured values are stored

0%

1

2

3

Stroke 4567Z09

Normal operation 5. Actuator moves to the position (3) as
indicated by signals Y or Z

100%

t

green LED is lit permanently; position feedback U active, the values correspond to the actual positions

A lit red LED indicates a calibration error. The calibration can be repeated any number of times. The LED status indication indicates operational status with dual-colored LED and is visible with removed cover.

LED Indication Green Lit

Function Normal operation

Remarks, troubleshooting Automatic operation; everything o.k.

Flashing Red Lit
Flashing

Calibration in progress Faulty stroke calibration
Internal error Inner valve jammed

Wait until calibration is finished (LED stops flashing, green or red LED will be lit)
Check mounting Restart stroke calibration (by short-circuiting calibration slot)
Replace electronics
Check valve

Both Dark

No power supply Electronics faulty

Check mains network, check wiring Replace electronics

As a general rule, the LED can assume only the states shown above (continuously red or green, flashing red or green, or off).

Siemens Building Technologies

Electrohydraulic actuators for valves

7/18
CM1N4566E 26.06.2012

Override control input Z SKC62.., SKC60

Override control input can be operated in following different modes of operation

no function

fully open

Z-mode
closed

override with 0...1000 

Signal addition SKC62UA only

Connections

Transfer

Accessories SKC..

linear or equalpercentage
· Z-contact not connected
· Valve stroke follows Y-input

linear or equalpercentage

linear or equalpercentage

· Z-contact connected · Z-contact connected · Z-contact connected · Z-contact is

directly to G

directly to G0

to M via resistor R

connected to R of

· Y-input has no effect · Y-input has no effect · Starting position at 50  / end position at 900 

the frost protection monitor QAF21.. or QAF61..

· Y-input has no effect

· Valve stroke follows signals Y and R(Z)

Note

Shown operation modes are based on the factory setting «direct acting» Y-input has no effect in Z-mode.

ASZ6.5 stem heater

01825

SKC32.., SKC82..

· for media below 0 °C

· mount between valve and actuator

ASC9.3

ASZ7.3..

double auxiliary switch

potentiometer

4561Z05

adjustable switching points

ASZ7.3: ASZ7.31: ASZ7.32:

0...1000  0...135  0...200 

8/18
Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

4567Z11

SKC62.., SKC60

ASC1.6 auxiliary switch

Engineering notes Caution Caution
Mounting instructions Orientation

switching point 0...5 % stroke
See section «Technical data» on page 12 for more information.

Conduct the electrical connections in accordance with local regulations on electrical installations as well as the internal or connection diagrams.
Safety regulations and restrictions designed to ensure the safety of people and property must be observed at all times!
For media below 0 °C the ASZ6.5 stem heater is required to keep the valve from freezing. For safety reasons the stem heater is designed for an operating voltage of AC 24 V / 30 W. For this case, do not insulate the actuator bracket and the valve stem, as air circulation must be ensured. Do not touch the hot parts without prior protective measures to avoid burns. Non-observance of the above may result in accidents and fires! Recommendation: Above 140 °C insulating the
valves is strictly recommended. Observe admissible temperatures, refer to «Use» on page 1 and «Technical data» on page 12
If an auxiliary switch is required, its switching point should be indicated on the plant schematic.
Every actuator must be driven by a dedicated controller (refer to «Connection diagrams», page 15).

Mounting Instruction 74 319 0324 0 for fitting the actuator to the valve are by packed in the actuator packaging. The instructions for accessories are enclosed with the accessories themselves.

Accessories ASC1.6 ASC9.3 SKC.. SKC..

Installation instructions

G4563.3

4 319 5544 0

G4561.3

4 319 5545 0

M3240

74 319 0324 0

74 319 0326 0

Accessory ASZ6.5 ASZ7.3.. ACT control unit QAF21..

Mounting instructions

M4563.7

4 319 5564 0

74 319 0247 0

M4568

74 319 0554 0

74 319 0399 0

90°

90°

Siemens Building Technologies

Electrohydraulic actuators for valves

9/18
CM1N4566E 26.06.2012

4 566 Z1 2 45 66Z13

Commissioning notes

When commissioning the system, check the wiring and functions, and set any auxiliary switches and potentiometers as necessary, or check the existing settings.

Cylinder with valve

Cylinder with valve

stem connector fully

stem connector fully

retracted

0 extended

0

 stroke = 0%

1  stroke = 100 %

1

Automatic operation

The manual adjuster must be rotated counterclockwise to the end stop. This causes the Siemens valves, types VVF.. and VXF.. to close (stroke = 0 %).
For automatic operation, the crank (2) on the manual adjustment knob (1) must be engaged. If not engaged, turn the crank counter-clockwise until the display window (3) neither shows the scale (4) nor the crank engagement bar.
1 2

4564Z1 4 4564Z16

Manual operation

Engaged crank (2) on the

Display window with invisible scale dial and crank

manual adjustment knob (1) engagement bar

For manual operation, swing out the crank (2) so that the display window (3) becomes visible. By rotating the crank or the manual adjustment knob (1), the display window shows the engagement bar and/or the scale dial with stroke indication.
3
4

4564Z15 4564Z17

Swung-out crank, display window (3)

Display window with scale dial (4) and stroke indication

10/18
Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

Maintenance notes Repair
Disposal Warranty

The SKC.. actuators are maintenance-free.
When servicing the actuator: · Switch off pump of the hydronic loop · Interrupt the power supply to the actuator · Close the main shutoff valves in the system · Release pressure in the pipes and allow them to cool down completely · If necessary, disconnect electrical connections from the terminals · The actuator must be correctly fitted to the valve before recommissioning.
Recommendation SKC6..: trigger stroke calibration. «Replacement parts», see page 17.
A damaged housing or cover represents an injury risk
· NEVER uninstall an actuator from the valve · Uninstall the valve-actuator combination (actuating device) as a complete
device · Use only properly trained technicians to uninstall the unit · Send the actuating device together with an error report to your local Siemens
representative for analysis and disposal · Properly mount the new actuating device (valve and actuator)
Parts could fly ultimately resulting in injuries from uninstalling an actuator with a damaged valve housing due to the tensioned return spring.
The device contains electrical and electronic components and must not be disposed of together with domestic waste. This applies in particular to the PCB. Legislation may demand special handling of certain components, or it may be sensible from an ecological point of view. Current local legislation must be observed.
The technical data relating to specific applications are valid only in conjunction with the valves listed in this Data Sheet under «Equipment combinations», page 3. The use of the actuators in conjunction with third-party valves invalidates all claims under Siemens Switzerland Ltd warranty.

Siemens Building Technologies

Electrohydraulic actuators for valves

11/18
CM1N4566E 26.06.2012

Technical data

Power supply
Signal inputs
Position feedback Operating data
Electrical connections Norms and standards

Operating voltage Voltage tolerance
Frequency

SKC32.. AC 230 V
± 15 %

SKC82..

SKC6..

AC 24 V

AC 24 V

± 20 %

­20 % / +30 %

SELV / PELV

50 or 60 Hz

Max. Power consumption at 50 Hz

SKC32.60: 19 VA / 16 W
SKC32.61: 24 VA / 21 W

SKC82.60, ..60U 19 VA / 16 W
SKC82.61, ..61U 24 VA / 21 W

SKC62.. 28 VA / 20 W
SKC60 24 VA / 18 W

External supply cable fuse

min. 0.5 A, slow max. 6 A, slow

min. 1.6 A, slow max. 10 A, slow

Control signal Terminal Y

DC 0...10 V,

3-position

DC 4...20 mA,

0...1000 

Voltage DC 0...10 V

Input impedance 100 k

Current DC 4...20 mA

Input impedance 240 

Signal resolution < 1%

Hysteresis 1 %

Terminal Z Override control

Resistor 0...1000 

Z not connected No function, priority

terminal Y

Z connected directly to G max. stroke 100 %

Z connected directly to G0 min. stroke 0 %

Z connected to M via 0...1000 

stroke proportional to R

Terminal U

voltage DC 0...9,8 V ±2 % load impedance > 10 k
current DC 4...19,6 mA ±2 % load impedance < 500 

Positioning time at 50 Hz opening SKC32.6.. 120 s SKC82.6.. 120 s

120 s

Closing SKC32.6.. 120 s SKC82.6.. 120 s

20 s

Spring-return time (closing) SKC32.61 18 s SKC82.61 18 s SKC60

­

SKC32.60

­ SKC82.60

­ SKC62..

20 s

Positioning force

2800 N

Nominal stroke

40 mm

Max. permissible medium temperature

-25...220 (350) °C < 0 °C: requires stem heater ASZ6.5

Cable entry

4 x M20 ( 20,5 mm) ..U with knockouts for standard ½" conduit connectors (Ø 21.5 mm)

CE-conformity EMC-directive

2004/108/EC

Immunity EN 61000-6-2 Industrial

Emission EN 61000-6-3 Residential

Low voltage directive

2006/95/EC

Electrical safety EN 60730-1

Product standards for

EN 60730-2-14

automatic electric controls

Protection standard

I

III

EN 60730

Housing protection standard

Upright to horizontal

IP54 to EN 60529

Conform with UL standards

SKC82..U UL 873

12/18

Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

Dimensions / Weight
Materials

SKC32..

SKC82..

SKC6..

SKC62U,

UL873

SKC62UA

C-tick

N474

N474

Environmental compatibility ISO 14001 (Environment)

ISO 9001 (Quality)

SN 36350 (Environmentally compatible products)

RL 2002/95/EG (RoHS)

Dimensions

refer to «Dimensions», page 16

Weight

SKC32.60 9.80 kg SKC82.60 9.90 kg SKC60/62 9.95 kg

SKC32.61 10.00 kg SKC82.60U 10.15 kg SKC62U/UA 10.20 kg

SKC82.61 10.00 kg

SKC82.61U 10.25 kg

Actuator housing, bracket Housing box and manual adjuster

Die-cast aluminum Plastic

Accessories ASC1.6 Auxiliary switch

Switching capacity

ASC9.3 double auxiliary switch ASZ7.3 Potentiometer
ASZ6.5 stem heater

Switching capacity per auxiliary switch
Change in overall resistance of potentiometer at nominal stroke min. current in sliding contact
expected lifetime max. current in sliding contact
expected lifetime Operating voltage
Power consumption

SKC32.., SKC82..
AC 250 V, 6 A resistive, 2.5 A inductive
ASZ7.3 0...1000  ASZ7.31 0...135  ASZ7.32 0...200 
0,05 mA 250'000 full lifts
2,5 mA 100'000 full lifts
AC 24 V ± 20 %
30 VA

SKC6..
AC 24 V, 10 mA...4 A resistive,
2 A inductive

SKC62UA enhanced functions

Direction of operation

Direct-acting, reverse-acting

Stroke limit control Sequence control
Signal addition

Range of lower limit Range of upper limit Terminal Y Starting point of sequence Operating range of sequence Z connected to R of Frost protection monitor QAF21.. Frost protection monitor QAF61..

DC 0...10 V / DC 10...0 V DC 4...20 mA / DC 20...4 mA 0...1000  / 1000...0  0...45 % adjustable 100...55 % adjustable
0...15 V adjustable 3...15 V adjustable
0...1000 , added to Y signal DC 1.6 V, added to Y signal

General ambient conditions

Environmental conditions Temperature Humidity

Operation EN 60721-3-3
Class 3K5 -15...55 °C 5...95 % r.h.

Transport EN 60721-3-2
Class 2K3 -30...65 °C < 95 % r.h.

Storage EN 60721-3-1
Class 1K3 -15...55 °C 5...95 % r.h.

Siemens Building Technologies

Electrohydraulic actuators for valves

13/18
CM1N4566E 26.06.2012

Internal diagrams SKC32.61 AC 230 V, 3-Position
SKC32.60 AC 230 V, 3-Position
SKC82.61 AC 24 V, 3-Position
SKC82.60 AC 24 V, 3-Position

Cm1 end switch

n

solenoid valve for spring-

return

c1, c2 ASC9.3 double auxiliary switch

a, b, c ASZ7.. potentiometer

Y1 Positioning signal «open»

Y2 Positioning signal «close»

21 spring-return function

N

neutral conductor

Cm1 end switch

n

solenoid valve for spring-

return

c1, c2 ASC9.3 double auxiliary switch

a, b, c ASZ7.. potentiometer

Y1 Positioning signal «open»

Y2 Positioning signal «close»

21 spring-return function

G

System potential

SKC60, SKC62 SKC60U, SKC62U SKC62UA AC 24 V, DC 0...10 V, 4...20 mA, 0...1000 
Connection terminals SKC6..
Auxiliary switch ASC1.6

DC 0 ...10 V

U

oder 4 ... 20 mA

Ausgang

voll offen 0 ...100 %

Eingang Zwangsteuerung (Signalpriorität)

Y

DC 0 ...10 V oder
4 ... 20 mA

0 ...100 %

Eingang

Valve Seat Detection

M

Valve Jam Detection

G0
MMI G

U

position indication

Z

override control

Y

positioning signal

M

measuring neutral

G0 operating voltage AC 24 V:

Hub

system neutral (SN)

G

operating voltage AC 24 V:

system potential (SP)

Ventil

G0 operating voltage AC 24 V: system neutral (SN)

G

operating voltage AC 24 V: system potential (SP)

Y

Positioning signal DC 0...10 (30) V or DC 4...20 mA

M

Measuring neutral (= G0)

U

Position indication DC 0...10 V or DC 4...20 mA

Z

Override control (functionality see page 8)

3

01804

c1
45

14/18
Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

Connection diagrams
SKC32.. AC 230 V 3-Position

SKC32.61

SKC32.60

SKC82.. AC 24 V 3-Position

F1 N1, N2 Y1, Y2

temperature limiter controller actuators

SKC82.61, SKC82.61U

L Phase N neutral

Y1 Positioning signal «open» Y2 Positioning signal «close» 21 Spring-return function
SKC82.60, SKC82.60U

SKC6.. AC 24 V DC 0...10 V, 4...20 mA, 0...1000 

F1

temperature limiter

N1, N2 controller

Y1, Y2 actuators

SKC60

SP Systempotential AC 24 V Y1

SN System neutral

Y2

21

Positioning signal «open» Positioning signal «close» Spring-return function

Siemens Building Technologies

Electrohydraulic actuators for valves

15/18
CM1N4566E 26.06.2012

SKC62 SKC62U SKC62UA

Dimensions

Y1 N1 F1 F2
F3 F4 G (SP)

actuator controller temperature limiter frost protection thermostat
terminals: 1 ­ 2 frost hazard / sensor is interrupted (thermostat closes with frost) 1 ­ 3 normal operation
temperature detector Frost protection monitor with 0...1000  signal output, e.g. QAF21.. or QAF61.. (only SKB62UA) * System potential AC 24 V

G0 (SN) System neutral

* Only with sequence control and the appropriate selector switch settings (see page 5ff)

All dimensions in mm

** SKC..U: with knockouts for standard ½" conduit connectors (Ø 21.5 mm)
 = > 100 mm , minimum clearance from ceiling or wall for mounting,  = > 200 mm , connection, operation, maintenance etc.

16/18
Siemens Building Technologies

Electrohydraulic actuators for valves

CM1N4566E 26.06.2012

Replacement parts

Order numbers for replacement parts

Cover

Hand control 1)

Clamp

Stem connection Control unit

Actuator type SKC32.60 SKC32.61 SKC82.60 SKC82.60U SKC82.61 SKC82.61U SKC62 SKC62U SKC60 SKC62UA
Revision numbers
Type reference SKC32.60 SKC32.61 SKC82.60 SKC82.60U SKC82.61

410455828 410455828 410455828 410455828 410455828 410455828 410455828 410455828 410455828 410455828

426855108 426855108 426855108 426855108 426855108 426855108 426855108 426855108 426855108 426855108

410355768 410355768 410355768 410356058 410355768 410356058 410355768 410356058 410355768 410356058

1) hand control, blue with mechanical parts

417856498 417856498 417856498 417856498 417856498 417856498 417856498 417856498 417856498 417856498

466857488 466857488 466857598 466857518

Valid from rev. No.
..C ..C ..C ..C ..C

Type reference
SKC82.61U SKC62 SKC62U SKC60 SKC62UA

Valid from rev. No.
..C ..F ..F ..F ..F

Siemens Building Technologies

Electrohydraulic actuators for valves

17/18
CM1N4566E 26.06.2012

18/18
Siemens Building Technologies

 2002 ­ 2012 Siemens Switzerland Ltd Electrohydraulic actuators for valves

Subject to change
CM1N4566E 26.06.2012


Acrobat Distiller 9.5.1 (Windows) Frank Ernst