R. STAHL Circuit Breaker 8530/1-MCB-STA103-C10-000-3
Article No. 272176
Product Description
The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA). This results in reduced load on electrical lines and high selectivity with respect to upstream fuses. The modules feature a modular design, available in 1 to 4 pole versions, and nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key Features:
- Disconnector function according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations thanks to the modular design of the protective switch.
- Easy mounting by clipping onto a DIN mounting rail in Ex e enclosures.
- Fixed thermal and magnetic trip adjustment.
- Ergonomic operating lever ensures safe connection and disconnection.
- Protection against re-closing during maintenance using padlocks (Accessories).
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEX FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230/400 V |
Rated operating current | 10 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | none |
Voltage 1st auxiliary function AC | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | none |
Max. voltage 2nd aux. function DC | - |
Trip characteristic | C |
Number of poles | 3-pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on current certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 cross-section min. | 1.5 mm² |
Connection terminal 2 cross-section max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (a difference in cross-section between the upper and lower chamber can only be connected). Permitted connection cross-section combinations are listed in the user instructions. |
Width | 83 mm (3.27 in) |
Length | 165 mm (6.5 in) |
Installation depth | 138.3 mm (5.44 in) |
Weight | 1.4 kg (3.087 lb) |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2-3 N·m (17.7 ... 26.6 lbf-in) |
Tightening torque auxiliary contact | 0.4–0.6 Nm (3.5 ... 5.3 lbf in) |
Technical Diagrams
Trip Time Characteristic Curve: The document includes a graph illustrating the trip time characteristic curve for the circuit breaker, showing the relationship between the multiple of the rated current (I/In) and the trip time in seconds and minutes. It specifies the characteristic as 'C' for both AC and DC applications.
Dimensional Drawings: Detailed dimensional drawings are provided for the circuit breaker (8530/1, 3 division units), showing measurements in millimeters and inches. These include width, height, depth, and mounting dimensions.
Accessories
Cylinder Lock
Description: For locking (shackle Ø 3)
Article No.: 107115
Quadruple Immobilization Device
Description: Locking pliers / labeling for individual component locking using up to 4 cylinder locks.
Article No.: 227232
Fixing Kit
Description: A fixing set for mounting the component on the mounting plate without a top-hat rail.
Article No.: 276618
General Information
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com
Note: R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.