Goodman FTXNG-A Series Inverter Split Unit Air Conditioner Engineering Data

Brand: Goodman

Product Type: Air Conditioner

Introduction

This document provides engineering data for the Goodman FTXNG-A Series Inverter Split Unit Air Conditioner with Heatpump functionality. The series includes models FTXNG09A, FTXNG12A, and FTXNG18A, designed for wall-mounted installation and operating on a 208/230V, 60Hz power supply.

Model Name and Power Supply

Indoor Unit Outdoor Unit Power Supply
FTXNG09AXVJU RXNG09AXVJU 1 Phase, 208/230V, 60Hz
FTXNG12AXVJU RXNG12AXVJU
FTXNG18AXVJU RXNG18A

Nomenclature

The model numbers for the FTXNG-A series are structured to indicate specific features. Below is a breakdown of the nomenclature for both indoor and outdoor units:

Indoor Unit Nomenclature

Definition Description
Unit CategoryF: Air-Cooled Split Indoor Unit
Product TypeT: Wall Mounted
SystemX: Inverter, Heatpump
GradeN: R410A, Internet Model
BrandG: Goodman Brand
Capacity Indication*09: 9,000 Btu/h
Major Design CategoryA: A Series
Factory OriginX: Malaysia
Power SupplyVJ: 208/230V / 1Phase / 60Hz
CountryU: United States

*Capacity value under Nomenclature is an indication. Please refer to Specifications Data for exact capacity value.

Outdoor Unit Nomenclature

Definition Description
Unit CategoryR: Air-Cooled Split Outdoor Unit
SystemX: Inverter, Heatpump
GradeN: R410A, Internet Model
BrandG: Goodman Brand
Capacity Indication*09: 9,000 Btu/h
Major Design CategoryA: A Series
Factory OriginX: Malaysia
Power SupplyVJ: 208/230V / 1Phase / 60Hz
CountryU: United States

Functions

The FTXNG-A series offers a range of functions for comfortable and efficient operation:

Category Functions FTXNG09/12A
RXNG09/12A
FTXNG18A
RXNG18A
Basic FunctionInverter
Operation Limit for Cooling (°CDB)(O/D)10-4610-46
Operation Limit for Cooling (°FDB)(O/D)50-114.850-114.8
Operation Limit for Heating (°CWB)(O/D)-15-18-15-18
CompressorOperation Limit for Heating (°FWB)(O/D)5-64.45-64.4
Scroll Compressor
Swing Compressor
Comfortable AirflowRotary Compressor--
Power-airflow Flap
Power-airflow Dual Flaps
Power-airflow Diffuser--
Wide Angle Louvers
Vertical Auto-Swing (Up and Down)
Comfort ControlHorizontal Auto-Swing (Right and Left)
3D Airflow--
Breeze Airflow
OperationAuto Fan Speed
Indoor Unit Quiet Operation
Intelligent Eye Operation
Automatic Defrosting
Automatic Operation
Programme Dry Function
Lifestyle ConvenienceFan Only
Powerful Operation (Non Inverter)
Inverter Powerful Operation
Energy Saving Function
Sleep Mode
Lifestyle ConvenienceIndoor Unit ON/OFF Button
R/C with Backlight
Signal Receiving Sign (R/C)
Set Temperature Display (R/C)
Saranet Filter
Health & CleanAnti-virus Filter / Gin-ION Filter
Catechin Filter / Green Tea Filter--
Titanium Apatite Air-Purifying Filter
PM 2.5 Filter
Streamer
TimerPlasma
Wipe Clean Flat Panel
Weekly Timer Operation (Wired R/C)
Worry Free (Reliability & Durability)24-hour ON/OFF Timer (R/C)
Countdown ON/OFF Timer (R/C)
Auto Restart (after Power Failure)
FlexibilitySelf-diagnosis
Anti-corrosion Treatment of Outdoor Heat ExchangerBlue FinBlue Fin
Pre-charged Piping Length32-13/16 ft32-13/16 ft
Remote Control ControllerEither Side Drain (Right or Left)
WIFI Connectivity
BAG Connectivity
Remote ControllerDIII-NET Connectivity
WirelessBRC52B67BRC52B67
Wired

Note: •: Available, -: Not Available, •*: Optional

Specifications

The following tables detail the technical specifications for the Goodman FTXNG-A series air conditioners, covering cooling and heating performance, dimensions, electrical characteristics, and more. The specifications are provided for the FTXNG09A/RXNG09A, FTXNG12A/RXNG12A, and FTXNG18A/RXNG18A models.

General Specifications

Model Rated Capacity (Min. ~ Max.) Moisture Removal (gal/h) Rated Running Current (A) Rated Power Consumption (W) EER2 SEER2 COP HSPF2 Power Factor (Rated)
Cooling (kW) Heating (kW)
FTXNG09A / RXNG09A 2.57 (1.30 - 3.00) 2.75 (1.30 - 3.80) 0.09 3.82 800 11.0 18.0 3.56 9.0 N/A
FTXNG12A / RXNG12A 3.22 (1.30 - 3.90) 3.31 (1.30 - 4.81) 0.18 4.55 1004 8.5 18.0 3.30 9.0 N/A
FTXNG18A / RXNG18A 5.27 (1.96 - 5.86) 5.24 (1.70 - 6.60) 0.41 7.53 1714 10.5 18.0 3.30 8.5 N/A

Indoor Unit Specifications (Example: FTXNG09A)

Parameter Value
Front Panel ColourWHITE
Airflow Rate (Turbo/High/Medium/Low/Quiet)466/431/322/249/142 CFM
Sound Pressure Level (H/M/L/Q)43/36/29/19 dBA
Fan TypeCROSS FLOW
Fan DriveDIRECT CURRENT
Fan Speed3 STEPS, QUIET, AUTO, TURBO
Fan Motor Output29 W
Dimensions (H x W x D)11-1/3 x 30-5/16 x 9-3/16 inches (288 x 770 x 234 mm)
Weight20.3 lbs (9.2 kg)

Outdoor Unit Specifications (Example: RXNG09A)

Parameter Value
Casing ColourIVORY WHITE
Airflow Rate (High)1083 CFM
Sound Pressure Level46 dBA
Fan TypePROPELLER
Fan DriveDIRECT CURRENT
Index of protection (IP)24
Insulation GradeE
Fan Motor Output32 W
Compressor TypeHERMETIC SWING
Dimensions (H x W x D)21-11/16 x 26-1/2 x 11-3/16 inches (550 x 675 x 284 mm)
Weight55 lbs (25 kg)

Note: Capacities are based on specific test conditions (e.g., Indoor 80°FDB/67°FWB for cooling, 70°FDB for heating; Outdoor 95°FDB for cooling, 47°FDB/43°FWB for heating).

Dimensions

Detailed dimensional drawings are provided for both indoor and outdoor units to aid in installation planning.

Indoor Unit Dimensions

Diagrams show the front, rear, left, right, and bottom views of the indoor units FTXNG09/12A and FTXNG18A, with key dimensions indicated in inches and millimeters. These diagrams are for illustrative purposes only.

Diagram illustrating dimensions for FTXNG09/12A Indoor Unit. Diagram illustrating dimensions for FTXNG18A Indoor Unit.

Outdoor Unit Dimensions

Diagrams show the front, rear, left, right, and bottom views of the outdoor units RXNG09/12A and RXNG18A, including details on mounting holes, service valves, and clearance requirements for installation. Key dimensions are provided in inches and millimeters. These diagrams are for illustrative purposes only.

Diagram illustrating dimensions and installation clearances for RXNG09/12A Outdoor Unit. Diagram illustrating dimensions and installation clearances for RXNG18A Outdoor Unit.

Wiring Diagrams

Electrical wiring diagrams are provided for the indoor and outdoor units, illustrating the connections for power supply, motors, sensors, and control boards.

Indoor Unit Wiring Diagram (Model: FTXNG-A)

This diagram shows the internal wiring of the indoor unit, including connections for the fan motor (MF), air swing motor (MS), thermistors (TH1, TH2), display board, and optional Wi-Fi adapter or wired accessories.

Diagram showing the internal wiring of the FTXNG-A indoor unit.

Outdoor Unit Wiring Diagrams

Separate diagrams are provided for the outdoor units RXNG09/12A and RXNG18A. These illustrate the connections for the compressor motor (MC), fan motor (MF), electronic expansion valve (EXV), four-way valve (4WV), fuses, terminal blocks, and sensors (outdoor air, heat exchanger, discharge). Field wiring connections are also indicated.

Diagram showing the wiring of the RXNG09/12A outdoor unit. Diagram showing the wiring of the RXNG18A outdoor unit.

Piping Diagrams

Refrigerant piping diagrams illustrate the flow of refrigerant for cooling and heating modes for both indoor and outdoor units.

Indoor Unit Piping Diagrams

Diagrams for FTXNG09A, FTXNG12A, and FTXNG18A show the indoor heat exchanger, distributor, fan motor, and thermistor connections, along with field piping connections (1/4" and 3/8" copper tubing).

Diagram showing the refrigerant piping for the FTXNG09A indoor unit. Diagram showing the refrigerant piping for the FTXNG12A indoor unit. Diagram showing the refrigerant piping for the FTXNG18A indoor unit.

Outdoor Unit Piping Diagrams

Diagrams for RXNG09A, RXNG12A, and RXNG18A illustrate the outdoor heat exchanger, propeller fan, compressor, four-way valve, electronic expansion valve, accumulator, strainers, mufflers, and thermistors. Field piping connections are also indicated.

Diagram showing the refrigerant piping for the RXNG09A outdoor unit. Diagram showing the refrigerant piping for the RXNG12A outdoor unit. Diagram showing the refrigerant piping for the RXNG18A outdoor unit.

Capacity Tables

Extensive tables provide detailed cooling and heating capacity data for the FTXNG-A series models under various operating conditions. These tables list Total Capacity (TC), Sensible Heat Capacity (SHC), and Power Input (PI) in kW (or kBtu/h) for different combinations of indoor and outdoor temperatures (both Celsius and Fahrenheit). Interpolation is required to determine values for conditions not explicitly listed.

Key Information Presented in Capacity Tables:

Due to the extensive nature of these tables, specific values are not reproduced here but are available in the original document.

Capacity Correction Factor by Refrigerant Piping Length

Graphs illustrate the capacity correction factor based on the length of the refrigerant piping. These factors are applied to the nominal capacities to account for variations in piping length and refrigerant charge. The graphs show separate curves for cooling and heating, indicating how the correction factor decreases as piping length increases.

Graph showing capacity correction factor vs. piping length for FTXNG09A/RXNG09A and FTXNG12A/RXNG12A models. Graph showing capacity correction factor vs. piping length for FTXNG18A/RXNG18A models.

Notes:

Operation Limit

The operation limit graphs define the permissible operating temperature ranges for the units in cooling and heating modes. These graphs plot outdoor temperature against indoor temperature to show the continuous operation zone and pull-down period.

Graph showing the cooling operation limits for the RXNG-A outdoor unit, plotting outdoor temperature (°FDB) against indoor temperature (°FWB). Graph showing the heating operation limits for the RXNG-A outdoor unit, plotting outdoor temperature (°FWB) against indoor temperature (°FDB).

Sound Level

Sound level data is provided for the indoor units, measured in an anechoic chamber. This includes sound pressure levels across various octave bands and overall noise criteria.

Sound Pressure Level (Cooling)

FTXNG09A (Cooling)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG09AHigh54434139393526154338
FTXNG09AMed45353633322617123631
FTXNG09ALow37283027251912102923
FTXNG09AQuiet25192016131089190
FTXNG12A (Cooling)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG12AHigh44364240433729194542
FTXNG12AMed34293533342819123733
FTXNG12ALow26243029272114113125
FTXNG12AQuiet171918161311109190
FTXNG18A (Cooling)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG18AHigh51414543444235254843
FTXNG18AMed41354139393729184338
FTXNG18ALow34303734333021133732
FTXNG18AQuiet30283431282313103326

Sound Pressure Level (Heating)

FTXNG09A (Heating)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG09AHigh49373937403426154239
FTXNG09AMed36293733312413113530
FTXNG09ALow30233226241612102922
FTXNG09AQuiet2321292319111192517
FTXNG12A (Heating)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG12AHigh47364038413423124340
FTXNG12AMed39293733322414113631
FTXNG12ALow29253228261712113024
FTXNG12AQuiet28242925201210102619
FTXNG18A (Heating)
Model Speed 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) Overall (dBA) Noise Criteria
63Hz125Hz250Hz500Hz1kHz2kHz4kHz8kHz
FTXNG18AHigh52404342423930164641
FTXNG18AMed45353938373424124136
FTXNG18ALow38313834322514113631
FTXNG18AQuiet37293531292312103328

NC Curve: A graph is provided showing Noise Criteria (NC) curves for different sound levels (Silent, Low, Medium, High, Turbo) across various octave band frequencies. This helps in assessing the perceived loudness of the unit in different environments.

NC Curve graph illustrating sound pressure levels across octave bands for different operating speeds.

Electric Characteristic

This table details the electrical characteristics of the unit combinations, including Maximum Circuit Amps (MCA), Maximum Overcurrent Protection (MOP), Compressor Input Current (A), Rated Operating Frequency (RHz), Outdoor Fan Motor (OFM) and Indoor Fan Motor (IFM) power, and Maximum Operating Current (MOC).

Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MOP COMP OFM IFM
A kW A kW A kW
FTXNG09A RXNG09A 60Hz-208V / 60Hz-230V MAX. 60Hz 253V MIN. 60Hz 187V 12.35 15 88 4.34 0.026 0.60 0.022 0.35
FTXNG12A RXNG12A 60Hz-208V / 60Hz-230V MAX. 60Hz 253V MIN. 60Hz 187V 12.40 15 96 5.57 0.026 0.61 0.022 0.40
FTXNG18A RXNG18A 60Hz-208V / 60Hz-230V MAX. 60Hz 253V MIN. 60Hz 187V 16.55 20 90 8.17 0.055 1.30 0.039 0.55

Notes:

Models: R410A FTXNG-A Series Inverter Split Unit Air Conditioner Wall Mounted, R410A, FTXNG-A Series Inverter Split Unit Air Conditioner Wall Mounted, Air Conditioner Wall Mounted, Wall Mounted

File Info : application/pdf, 31 Pages, 5.52MB

PDF preview unavailable. Download the PDF instead.

ed5wm16r-na23v2 - ftxng a - engineering manual - revised (1) 1680770783558 Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)

Related Documents

Preview Goodman FTXNG-A Series Engineering Data: Inverter Split Unit Air Conditioner
Comprehensive engineering data for the Goodman FTXNG-A Series Inverter Split Unit Air Conditioner, featuring wall-mounted heat pump models. This document includes detailed specifications, dimensions, wiring and piping diagrams, capacity tables, operation limits, sound pressure levels, and electrical characteristics for models FTXNG09A, FTXNG12A, and FTXNG18A with corresponding outdoor units RXNG09A, RXNG12A, and RXNG18A.
Preview Goodman GLXS5B High-Efficiency R-32 Split System Air Conditioner
Detailed specifications, features, and performance data for the Goodman GLXS5B High-Efficiency R-32 Split System Air Conditioner, offering up to 16.5 SEER2 and capacities from 1.5 to 5 tons.
Preview Goodman GLXS3B R-32 Split System Air Conditioners & AMST Series Air Handlers: Specifications, Data, and Diagrams
Comprehensive technical specifications, performance data, nomenclature, dimensions, wiring diagrams, and accessories for Goodman GLXS3B R-32 split system air conditioners and AMST series air handlers. Includes details on SEER2 ratings, cooling capacities, and installation information.
Preview Goodman GMEC96 Two-Stage ECM Gas Furnace Specifications and Features
Detailed specifications, features, dimensions, and airflow data for the Goodman GMEC96 Two-Stage, Multi-Speed ECM Gas Furnace. Includes product nomenclature, electrical data, and available accessories.
Preview Goodman ASPT Series ECM Air Handlers: Features, Specifications, and Data
Comprehensive overview of Goodman's ASPT Series multi-position, multi-speed ECM-based air handlers, detailing product features, technical specifications, dimensions, airflow data, heat kit compatibility, and wiring diagrams for various models.
Preview Goodman GSX13 Split System Air Conditioner Specifications
Comprehensive specifications, features, nomenclature, cooling data, AHRI ratings, dimensions, and accessories for the Goodman GSX13 Split System Air Conditioner series, designed for efficient and reliable cooling.
Preview Goodman SSZ 14 SEER Split System Heat Pumps Technical Manual
Technical manual for Goodman SSZ 14 SEER Split System Heat Pumps, covering product identification, design, specifications, performance data, and wiring diagrams for HVAC technicians.
Preview Goodman GMES96/GCES96 Gas Furnace: Specifications, Features, and Airflow Data
Detailed technical specifications, features, dimensions, and airflow performance data for the Goodman GMES96 and GCES96 single-stage, multi-speed gas furnaces, offering up to 96% AFUE.