Goodman FTXNG-A Series Engineering Data

Inverter Split Unit Air Conditioner, Wall Mounted Heatpump [60Hz]

Introduction

Model Name and Power Supply

The Goodman FTXNG-A Series Inverter Split Unit Air Conditioners are available in the following indoor and outdoor unit combinations, operating on a 1-Phase, 208/230V, 60Hz power supply:

Indoor UnitOutdoor UnitPower Supply
FTXNG09AXVJURXNG09AXVJU1Phase, 208/230V, 60Hz
FTXNG12AXVJURXNG12AXVJU
FTXNG18AXVJURXNG18AXVJU

Nomenclature

Indoor Unit

DefinitionDescription
Unit CategoryF : Air-Cooled Split Indoor Unit
Product TypeT : Wall Mounted
SystemX : Inverter, Heatpump
GradeN : R410A, Internet Model
BrandG : Goodman Brand
Capacity Indication*09 : 9,000 Btu/h
Major Design CategoryA : A Series
Factory OriginX : Malaysia
Power SupplyVJ : 208/230V / 1Phase / 60Hz
CountryU : United States

Outdoor Unit

DefinitionDescription
Unit CategoryR : Air-Cooled Split Outdoor Unit
SystemX : Inverter, Heatpump
GradeN : R410A, Internet Model
BrandG : Goodman Brand
Capacity Indication*09 : 9,000 Btu/h
Major Design CategoryA : A Series
Factory OriginX : Malaysia
Power SupplyVJ : 208/230V / 1Phase / 60Hz
CountryU : United States

Remark: *Capacity value under Nomenclature is an indication. Please refer to Specifications Data for exact capacity value.

Functions

This series offers various functions for comfort and efficiency, including:

  • Basic Function: Wide operation limits for cooling and heating.
  • Compressor: Features Scroll Compressor technology.
  • Comfortable Airflow: Includes Power-airflow Flap, Dual Flaps, Diffuser, Wide Angle Louvers, and Vertical/Horizontal Auto-Swing.
  • Comfort Control: Offers 3D Airflow, Breeze Airflow, Auto Fan Speed, Indoor Unit Quiet Operation, and Intelligent Eye Operation.
  • Operation: Automatic Defrosting, Automatic Operation, Programme Dry Function, and Fan Only modes.
  • Lifestyle Convenience: Sleep Mode, Indoor Unit ON/OFF Button, R/C with Backlight, Signal Receiving Sign, and Set Temperature Display.
  • Health & Clean: Features Saranet Filter, Anti-virus Filter / Gin-ION Filter, Catechin Filter / Green Tea Filter, Titanium Apatite Air-Purifying Filter, PM 2.5 Filter, Streamer, and Plasma technologies.
  • Timer: Weekly Timer Operation (Wired R/C), 24-hour ON/OFF Timer (R/C), and Countdown ON/OFF Timer.
  • Worry Free (Reliability & Durability): Auto Restart (after Power Failure), Self-diagnosis, and Anti-corrosion Treatment of Outdoor Heat Exchanger.
  • Flexibility: Pre-charged Piping Length up to 32-13/16 ft, options for either side drain, and WIFI/BAG/DIII-NET Connectivity (optional).
  • Remote Controller: Available in Wireless and Wired options (e.g., BRC52B67).

Specifications

Detailed specifications for the FTXNG09A/RXNG09A, FTXNG12A/RXNG12A, and FTXNG18A/RXNG18A models are provided below. Specifications include cooling and heating capacities, moisture removal, running current, power consumption, SEER2/HSPF2 ratings, refrigerant type (R410A), piping dimensions, airflow rates, sound pressure levels, dimensions, and electrical characteristics.

FTXNG09A / RXNG09A

CoolingHeating
Rated Capacity (Min. ~ Max.) kW2.57 (1.30 - 3.00)2.75 (1.30 - 3.80)
Moisture Removal Btu/h8800 (4400 - 10200)9400 (4400 - 13000)
Rated Running Current A3.823.70
Rated Power Consumption W800774
EER2 Btu/h/W11.0N/A
SEER218.0N/A
COP W/WN/A3.56
HSPF2N/A9.0
Power Factor (Rated)N/AN/A
Piping Connections Liquid/Gas1/4" (6.35) / 3/8" (9.52)1/4" (6.35) / 3/8" (9.52)
Refrigerant TypeR410AR410A
Charge lbs (kg)1.54 (0.7)1.54 (0.7)
Max. Interunit Piping Length ft (m)65-5/8 (20)65-5/8 (20)
Max. Interunit Height Difference ft (m)32-13/16 (10)32-13/16 (10)
Chargeless ft (m)32-13/16 (10)32-13/16 (10)
Amount of Additional Charge of Refrigerant oz/ft (g/m)0.21 (20)0.21 (20)
Indoor Unit Dimensions (H x W x D) inch (mm)11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234)11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234)
Indoor Unit Weight lbs (kg)20.3 (9.2)20.3 (9.2)
Outdoor Unit Dimensions (H x W x D) inch (mm)21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284)21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284)
Outdoor Unit Weight lbs (kg)55 (25)55 (25)
Indoor Airflow Rate (CFM)Turbo: 466, High: 431, Medium: 322, Low: 249, Quiet: 142Turbo: 402, High: 431, Medium: 322, Low: 249, Quiet: 219
Indoor Sound Pressure Level (H/M/L/Q) dBA43/36/29/1942/35/29/25

FTXNG12A / RXNG12A

CoolingHeating
Rated Capacity (Min. ~ Max.) kW3.22 (1.30 - 3.90)3.31 (1.30 - 4.81)
Moisture Removal Btu/h11000 (4400 - 13300)11300 (4400 - 16400)
Rated Running Current A3.224.55
Rated Power Consumption W12941004
EER2 Btu/h/W8.5N/A
SEER218.0N/A
COP W/WN/A3.30
HSPF2N/A9.0
Power Factor (Rated)N/AN/A
Piping Connections Liquid/Gas1/4" (6.35) / 3/8" (9.52)1/4" (6.35) / 3/8" (9.52)
Refrigerant TypeR410AR410A
Charge lbs (kg)2.09 (0.95)2.09 (0.95)
Max. Interunit Piping Length ft (m)65-5/8 (20)65-5/8 (20)
Max. Interunit Height Difference ft (m)32-13/16 (10)32-13/16 (10)
Chargeless ft (m)32-13/16 (10)32-13/16 (10)
Amount of Additional Charge of Refrigerant oz/ft (g/m)0.21 (20)0.21 (20)
Indoor Unit Dimensions (H x W x D) inch (mm)11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234)11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234)
Indoor Unit Weight lbs (kg)21.4 (9.7)21.4 (9.7)
Outdoor Unit Dimensions (H x W x D) inch (mm)21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284)21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284)
Outdoor Unit Weight lbs (kg)62 (28)62 (28)
Indoor Airflow Rate (CFM)Turbo: 473, High: 436, Medium: 316, Low: 247, Quiet: 132Turbo: 412, High: 436, Medium: 316, Low: 247, Quiet: 210
Indoor Sound Pressure Level (H/M/L/Q) dBA45/37/31/1943/36/30/26

FTXNG18A / RXNG18A

CoolingHeating
Rated Capacity (Min. ~ Max.) kW5.27 (1.96 - 5.86)5.24 (1.70 - 6.60)
Moisture Removal Btu/h18000 (6700 - 20000)17900 (5800 - 22500)
Rated Running Current A7.536.98
Rated Power Consumption W17141590
EER2 Btu/h/W10.5N/A
SEER218.0N/A
COP W/WN/A3.30
HSPF2N/A8.5
Power Factor (Rated)N/AN/A
Piping Connections Liquid/Gas1/4" (6.35) / 1/2" (12.70)1/4" (6.35) / 1/2" (12.70)
Refrigerant TypeR410AR410A
Charge lbs (kg)3.20 (1.45)3.20 (1.45)
Max. Interunit Piping Length ft (m)98-1/2 (30)98-1/2 (30)
Max. Interunit Height Difference ft (m)32-13/16 (10)32-13/16 (10)
Chargeless ft (m)32-13/16 (10)32-13/16 (10)
Amount of Additional Charge of Refrigerant oz/ft (g/m)0.21 (20)0.21 (20)
Indoor Unit Dimensions (H x W x D) inch (mm)11-11/16 x 39-9/16 x 10-3/4 (297 x 990 x 273)11-11/16 x 39-9/16 x 10-3/4 (297 x 990 x 273)
Indoor Unit Weight lbs (kg)31 (14)31 (14)
Outdoor Unit Dimensions (H x W x D) inch (mm)27-13/32 x 36-5/8 x 13-13/16 (696 x 930 x 351)27-13/32 x 36-5/8 x 13-13/16 (696 x 930 x 351)
Outdoor Unit Weight lbs (kg)97 (44)97 (44)
Indoor Airflow Rate (CFM)Turbo: 754, High: 716, Medium: 605, Low: 467, Quiet: 395Turbo: 754, High: 716, Medium: 605, Low: 467, Quiet: 395
Indoor Sound Pressure Level (H/M/L/Q) dBA48/43/37/3346/41/36/33

Dimensions

Detailed physical dimensions for the indoor and outdoor units are provided in diagrams. These include measurements for height, width, and depth, as well as connection port locations.

Indoor Unit Dimensions:

Model FTXNG09/12A:

  • Overall dimensions: 11-1/3" (288 mm) Height x 30-5/16" (770 mm) Width x 9-3/16" (234 mm) Depth.

Model FTXNG18A:

  • Overall dimensions: 11-11/16" (297 mm) Height x 39-9/16" (990 mm) Width x 10-3/4" (273 mm) Depth.

Outdoor Unit Dimensions:

Model RXNG09/12A:

  • Overall dimensions: 21-11/16" (550 mm) Width x 26-1/2" (675 mm) Depth x 15-11/16" (398 mm) Height (approximate, based on diagram). Includes details on anchor bolt hole spacing and service valve locations.

Model RXNG18A:

  • Overall dimensions: 27-13/32" (696 mm) Width x 36-5/8" (930 mm) Depth x 13-13/16" (351 mm) Height (approximate, based on diagram). Includes details on anchor bolt hole spacing and service valve locations.

Wiring Diagrams

Wiring diagrams are provided for both the indoor and outdoor units, illustrating the electrical connections for components such as fan motors, thermistors, compressor motors, terminal blocks, and power supply connections. Field wiring connections are also indicated.

Indoor Unit Wiring Diagram:

The diagram shows connections for the fan motor (MF), indoor coil thermistor (TH1), room thermistor (TH2), control board connections (CN_SW_LR, CN_DSP, CN_COIL, CN_SW_UD, CN S21, CN_NS), and power supply (LIVE, NEUTRAL). Optional connections for WIFI ADAPTER and WIRED ACCESSORY are also shown. Field wiring is indicated by a dotted line.

Outdoor Unit Wiring Diagram:

Diagrams for the outdoor units (RXNG09/12A and RXNG18A) detail connections for the compressor motor (MC), fan motor (MF), electronic expansion valve (EXV), four-way valve (4WV), overload protector (OLP/HPS), terminal blocks (TB), fuses (FU1, FU2, FU3), ferrite cores (Z1C, Z2C, Z3C), and various sensors (Outdoor Air Sensor, Heat Exchanger Sensor, Discharge Sensor). Power supply and connections to the indoor unit are also illustrated.

Piping Diagrams

Piping diagrams illustrate the refrigerant flow paths and connections for both indoor and outdoor units, detailing the components within the refrigeration circuit.

Indoor Unit Piping Diagrams:

These diagrams show the indoor heat exchanger, fan motor, and thermistor connections. They indicate field piping connections for 1/4" CuT and 3/8" CuT lines, along with single union joints. Refrigerant flow for cooling and heating is depicted.

Outdoor Unit Piping Diagrams:

The outdoor unit piping diagrams show the heat exchanger, compressor, fan, four-way valve (for heat pump models), electronic expansion valve (EXV), mufflers, strainers, liquid stop valves, gas stop valves, and accumulators. They illustrate the refrigerant flow for both cooling and heating modes, with field piping connections specified.

Capacity Tables

Extensive capacity tables are provided for various operating conditions. These tables detail Total Capacity (TC), Sensible Heat Capacity (SHC), and Power Input (PI) for different indoor and outdoor temperatures, measured in both Celsius and Fahrenheit. These tables are essential for system design and performance analysis.

Capacity Correction Factor

Graphs illustrate the capacity correction factor based on the length of refrigerant piping for different model series (FTXNG09A-RXNG09A, FTXNG12A-RXNG12A, and FTXNG18A-RXNG18A). These charts help in adjusting nominal capacities for longer piping runs, with notes explaining the calculation method and limitations.

Operation Limit

Operation limit graphs define the permissible operating temperature ranges for cooling and heating modes. These graphs plot outdoor temperature against indoor temperature, indicating zones for continuous operation and pull-down periods, ensuring efficient and safe system performance.

  • Cooling Operation Limit: Shows acceptable indoor and outdoor temperature combinations for continuous operation and initial pull-down.
  • Heating Operation Limit: Displays the temperature ranges for continuous heating operation.

Sound Level

Measuring Location

Sound level measurements are conducted in an anechoic chamber. The microphone (MIC LOCATION) is positioned 1.0 meter horizontally and 0.8 meters vertically from the unit for standardized testing.

Sound Pressure Level and NC Curve

Tables provide the 1/1 Octave A-weighted Sound Pressure Level (dB) for various speeds (High, Medium, Low, Quiet) in both cooling and heating modes for each model. NC (Noise Criteria) curves are also presented, graphically representing sound pressure levels across different octave bands and correlating them with NC ratings, allowing for assessment of perceived noise levels.

Electric Characteristic

The electric characteristics of the unit combinations are detailed in a table, including voltage range, Minimum Circuit Amps (MCA), Maximum Overcurrent Protection (MOP), Compressor Input Current (A), Outdoor Fan Motor (OFM) rated output (kW), Indoor Fan Motor (IFM) rated output (kW), and Maximum Operating Current (MOC).

Unit CombinationPower SupplyCOMPOFMIFM
Indoor UnitOutdoor UnitHz-VoltsVoltage RangeMCAMOPRHzAkWMOCkWMOC
FTXNG09ARXNG09A60Hz-208V / 60Hz-230VMAX. 60Hz 253V MIN. 60Hz 187V12.3515884.340.0260.600.0220.35
FTXNG12ARXNG12A60Hz-208V / 60Hz-230VMAX. 60Hz 253V MIN. 60Hz 187V12.4015965.570.0260.610.0220.40
FTXNG18ARXNG18A60Hz-208V / 60Hz-230VMAX. 60Hz 253V MIN. 60Hz 187V16.5520908.170.0551.300.0390.55

Symbols: MCA: Minimum Circuit Amps (A), MOP: Maximum Overcurrent Protection (A), COMP: Compressor, RHz: Rated Operating Frequency (Hz), A: Compressor Input Current (A), OFM: Outdoor Fan Motor, IFM: Indoor Fan Motor, kW: Fan Motor Rated Output (kW), MOC: Maximum Operating Current (A).

Notes: 1. RHz is the maximum frequency during cooling and heating operation. 2. RLA is the maximum current during cooling and heating operation. 3. Maximum allowable voltage imbalance between phases is 2%. 4. Select wire size based on the larger value of MCA. 5. Use circuit breaker instead of fuse.

Models: FTXNG-A Series Inverter Split Unit Air Conditioner Wall Mounted Heatpump 60Hz, FTXNG-A Series, Inverter Split Unit Air Conditioner Wall Mounted Heatpump 60Hz, Conditioner Wall Mounted Heatpump 60Hz

File Info : application/pdf, 31 Pages, 5.47MB

PDF preview unavailable. Download the PDF instead.

goodman ftxng a series engineering manual Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)

Related Documents

Preview Goodman FTXNG-A Series Inverter Split Unit Air Conditioner Engineering Data
This document provides comprehensive engineering data for the Goodman FTXNG-A Series Inverter Split Unit Air Conditioner with Heatpump functionality. It includes detailed specifications, nomenclature, functions, dimensions, wiring and piping diagrams, capacity tables, operation limits, sound level data, and electrical characteristics for models FTXNG09A, FTXNG12A, and FTXNG18A, along with their corresponding outdoor units RXNG09A, RXNG12A, and RXNG18A.
Preview Goodman FTXNG-A Series Inverter Split Unit Air Conditioner Engineering Data
Detailed engineering data for the Goodman FTXNG-A Series Wall Mounted Inverter Split Unit Air Conditioner Heatpump operating at 60Hz. It includes detailed specifications, functions, dimensions, wiring and piping diagrams, capacity tables, operation limits, sound level information, and electrical characteristics for various models.
Preview Goodman R410A Inverter Wall Mounted Heatpump FTXNG-A Series Product Brochure
Explore the features and specifications of the Goodman R410A Inverter Wall Mounted Heatpump FTXNG-A Series. This brochure details product line-up, advanced inverter technology, lifestyle convenience features, cleanliness functions, and comprehensive technical specifications for models FTXNG09AXVJU, FTXNG12AXVJU, and FTXNG18AXVJU.
Preview Goodman R410A Inverter Wall Mounted Heatpump FTXNG-A Series
Comprehensive overview of the Goodman R410A Inverter Wall Mounted Heatpump, FTXNG-A Series. Features include inverter technology for energy efficiency and consistent comfort, DC Inverter motor, swing compressor for quiet operation, lifestyle convenience functions (Powerful operation, ECO+, Sleep mode), advanced cleanliness features (Catechin and Titanium Apatite filters), and detailed technical specifications.
Preview Goodman GLXS5B High-Efficiency R-32 Split System Air Conditioner
Detailed specifications, features, and performance data for the Goodman GLXS5B High-Efficiency R-32 Split System Air Conditioner, offering up to 16.5 SEER2 and capacities from 1.5 to 5 tons.
Preview Goodman GLXS3B R-32 Split System Air Conditioners & AMST Series Air Handlers: Specifications, Data, and Diagrams
Comprehensive technical specifications, performance data, nomenclature, dimensions, wiring diagrams, and accessories for Goodman GLXS3B R-32 split system air conditioners and AMST series air handlers. Includes details on SEER2 ratings, cooling capacities, and installation information.
Preview Goodman GPCH3 Packaged Air Conditioner Specifications and Features
Comprehensive guide to the Goodman GPCH3 series packaged air conditioners, covering standard and cabinet features, nomenclature, detailed product specifications, expanded cooling and airflow data, electrical information for heat kits, dimensions, wiring diagrams, and available accessories. Designed for efficiency and durability, these units are available in 2 to 5 tons with 13.4 SEER2 ratings.
Preview Goodman R410A Split Series Room Air Conditioner Installation Manual
This installation manual provides comprehensive guidance for setting up Goodman R410A Split Series room air conditioners, detailing safety protocols, site selection, unit installation, piping, wiring, and commissioning for optimal performance and safety.