ROOFTOP UNIT KITS AND ACCESSORIES
BLOWER ASSEMBLY REPLACEMENT KIT
Part Number: 507315-02
Revision: 2/2022 (Replaces 4/2021)
INSTALLATION INSTRUCTIONS FOR BLOWER ASSEMBLY REPLACEMENT KIT
USED WITH: LGM/LCM092-150U UNITS
Shipping and Packing List
Package 1 of 1 contains:
- 1- Blower assembly
Application
The blower assembly replacement kit is used on LGM/LCM092, 102, 120, & 150U units. See table 1.
Cat. No. | Assembly No. | Voltage |
---|---|---|
22A41 | 612793-07 | Y |
22A42 | 612793-08 | G, J |
22A43* | 612793-09 | Y |
22A44* | 612793-10 | G, J |
*Corrosion protection
Installation
- Disconnect electrical power to unit. Wait five minutes before continuing service procedures to avoid electrical shock. This will allow internal capacitors time to fully discharge.
- Open access panels as shown in figure 1.
- Disconnect B3 Modbus connection and PT6 connection in the blower section. See figure 2.
- Disconnect P48 in the controls area. See figure 3.
- Cut wire ties where necessary and pull P48 wiring harness from control area into blower section.
- Remove four screws securing blower assembly to unit. See figure 5.
- If unit was equipped with a blower proving switch, remove switch from existing blower housing. Attach the proving switch to replacement blower assembly in the same manner it was removed.
- Disconnect the pressure tubing from PT6 pressure sensor. See figure 4. Remove two screws and remove sensor/bracket assembly (note the orientation) from existing blower housing. Install the sensor/bracket onto the replacement blower assembly. Reattach the tubing in the same manner they were removed.
- Use the handle on the blower assembly to slide the assembly out of unit.
- Install replacement blower assembly flanges into rails on the blower deck in the same manner it was removed. Secure into place using four screws shown in figure 5.
- Uncoil P48 wiring harness secured to replacement blower housing.
- Route P48 end of harness through unit to control area in the same manner it was removed.
- Connect P48, B3 Modbus, and PT6 connections as shown in figures 2 and 3.
- Bundle harnesses and use wire ties to secure kit harnesses to unit harnesses in the same manner they were removed.
[Diagram showing the blower section of the unit with labels for BLOWER ACCESS DOOR and CONTROL ACCESS.]
[Diagram showing wiring connections in the blower section, including PT6 PRESSURE SENSOR CONNECTION, P43 POWER HARNESS, B3 MODBUS CONTROL CONNECTOR, and BUNDLE AND SECURE EXCESS POWER WIRING.]
[Diagram showing the control area with labels for TO BLOWER, P48, and a representation of the wiring harness connections.]
[Diagram illustrating the PT6 pressure sensor mounting bracket, pressure tubing connection, and mounting screws.]
[Diagram showing the blower assembly being removed from the unit, with labels for BLOWER ASSEMBLY, PT6 PRESSURE SENSOR, BLOWER PROVING SWITCH (OPTIONAL), and REMOVE SCREWS (2 ON EACH SIDE).]