ROOFTOP UNIT KITS AND ACCESSORIES

BLOWER ASSEMBLY REPLACEMENT KIT

Part Number: 507315-02

Revision: 2/2022 (Replaces 4/2021)

INSTALLATION INSTRUCTIONS FOR BLOWER ASSEMBLY REPLACEMENT KIT

USED WITH: LGM/LCM092-150U UNITS

Shipping and Packing List

Package 1 of 1 contains:

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
CAUTION: As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

Application

The blower assembly replacement kit is used on LGM/LCM092, 102, 120, & 150U units. See table 1.

TABLE 1
Cat. No. Assembly No. Voltage
22A41 612793-07 Y
22A42 612793-08 G, J
22A43* 612793-09 Y
22A44* 612793-10 G, J

*Corrosion protection

Installation

  1. Disconnect electrical power to unit. Wait five minutes before continuing service procedures to avoid electrical shock. This will allow internal capacitors time to fully discharge.
  2. Open access panels as shown in figure 1.
  3. Disconnect B3 Modbus connection and PT6 connection in the blower section. See figure 2.
  4. Disconnect P48 in the controls area. See figure 3.
  5. Cut wire ties where necessary and pull P48 wiring harness from control area into blower section.
  6. Remove four screws securing blower assembly to unit. See figure 5.
  7. If unit was equipped with a blower proving switch, remove switch from existing blower housing. Attach the proving switch to replacement blower assembly in the same manner it was removed.
  8. Disconnect the pressure tubing from PT6 pressure sensor. See figure 4. Remove two screws and remove sensor/bracket assembly (note the orientation) from existing blower housing. Install the sensor/bracket onto the replacement blower assembly. Reattach the tubing in the same manner they were removed.
  9. Use the handle on the blower assembly to slide the assembly out of unit.
  10. Install replacement blower assembly flanges into rails on the blower deck in the same manner it was removed. Secure into place using four screws shown in figure 5.
  11. Uncoil P48 wiring harness secured to replacement blower housing.
  12. Route P48 end of harness through unit to control area in the same manner it was removed.
  13. Connect P48, B3 Modbus, and PT6 connections as shown in figures 2 and 3.
  14. Bundle harnesses and use wire ties to secure kit harnesses to unit harnesses in the same manner they were removed.
FIGURE 1: BLOWER SECTION

[Diagram showing the blower section of the unit with labels for BLOWER ACCESS DOOR and CONTROL ACCESS.]

FIGURE 2: BLOWER SECTION

[Diagram showing wiring connections in the blower section, including PT6 PRESSURE SENSOR CONNECTION, P43 POWER HARNESS, B3 MODBUS CONTROL CONNECTOR, and BUNDLE AND SECURE EXCESS POWER WIRING.]

FIGURE 3: CONTROL AREA

[Diagram showing the control area with labels for TO BLOWER, P48, and a representation of the wiring harness connections.]

FIGURE 4: PT6 SENSOR

[Diagram illustrating the PT6 pressure sensor mounting bracket, pressure tubing connection, and mounting screws.]

FIGURE 5: SLIDE BLOWER ASSEMBLY OUT OF UNIT

[Diagram showing the blower assembly being removed from the unit, with labels for BLOWER ASSEMBLY, PT6 PRESSURE SENSOR, BLOWER PROVING SWITCH (OPTIONAL), and REMOVE SCREWS (2 ON EACH SIDE).]

Models: LGM-LCM092 Rooftop Unit Kits and Accessories, LGM-LCM092, Rooftop Unit Kits and Accessories, Unit Kits and Accessories, Accessories

PDF preview unavailable. Download the PDF instead.

507315-02a Acrobat Distiller 19.0 (Windows)

Related Documents

Preview LGM/LCM092U-150U Gas and Cooling Packaged Units Installation Instructions
Comprehensive installation guide for Lennox LGM/LCM092U, LGM/LCM102U, LGM/LCM120U, and LGM/LCM150U gas and cooling packaged rooftop units. Covers safety precautions, unit support, duct connection, rigging, condensate drains, gas piping, electrical connections, start-up procedures, and maintenance for R-454B refrigerant.
Preview Lennox Indoor Blower Motor Replacement Kit Installation Instructions
Installation instructions for Lennox Nidec Indoor Blower Motor Replacement Kits 20P42, 20P43, and 20P44 used on ML296V model units. Includes safety warnings, application details, and step-by-step replacement procedures.
Preview Lennox PowerMate Innovator Z Blower Coil Unit Maintenance and Operation Guide
Comprehensive guide to maintaining and operating your Lennox PowerMate Innovator Z blower coil unit, covering warranty, filter care, thermostat settings, and troubleshooting.
Preview Lennox Integrated Control Replacement Kit 23C48 Installation Instructions
Installation guide for the Lennox Integrated Control Replacement Kit 23C48, providing step-by-step instructions and wiring diagrams for single-stage furnaces with constant torque indoor blower motors.
Preview Lennox EL296UHE Elite Series Gas Furnace: Specifications and Features
Detailed product specifications, features, and technical information for the Lennox EL296UHE Elite Series gas furnace, highlighting its 96% AFUE, two-stage heating, and constant torque blower.
Preview Lennox Integrated Control Replacement Kit Installation Instructions
Comprehensive installation guide for the Lennox Integrated Control Replacement Kit (22K51), designed for communicating enabled SL280UHV, SL280DFV, EL296UHV, and EL296DFV HVAC units. Includes safety warnings, application details, installation steps, ESD precautions, and wiring diagrams.
Preview Lennox 59M03 Flue Transition Replacement Kit Installation Instructions
Detailed installation guide for the Lennox 59M03 Flue Transition Replacement Kit, designed for G26, 90UGF, and G32 series HVAC units. Includes safety warnings, parts list, and step-by-step instructions for replacing the flue transition and adding a drain for the combustion air inducer.
Preview Lennox CORE Control System (M4 Unit Controller) Application Guide
This application guide provides detailed information on the Lennox CORE Control System, also known as the M4 Unit Controller, covering its features, installation, operation, and troubleshooting for commercial HVAC applications.