Lennox Indoor Blower Motor Replacement Kit

Installation Instructions for Nidec Indoor Blower Motor Replacement Kits 20P42, 20P43, 20P44 Used on ML296V Model Units

©2019

Safety Warnings

▲ WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.

▲ CAUTION

As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

Shipping and Packing List

Package 1 of 1 contains:

Application

Use the kit specified in the table below to replace the motor for ML296V units.

TABLE 1
Model No. Replacement Kit Catalog No. Indoor Blower Motor Part No.
ML296UH045XV36B 20P42 620604-01
ML296UH070XV36B
ML296DF045XV36B 20P43 620604-02
ML296UH090XV48C
ML296DF070XV48B 20P44 620604-03
ML296UH110XV60C
ML296DF090XV60C

Replacement Procedure

  1. Disconnect all electrical power to the unit. Wait at least five minutes before beginning service procedures. This will allow internal capacitors to fully discharge, avoiding possible electrical shock.
  2. Remove the blower access panel.
  3. Remove two screws securing the blower housing to the blower deck and slide blower-motor assembly out of unit. (See Figure 1)
  4. Unplug all wires from the blower motor.
  5. Loosen motor shaft set screw and remove all motor mount leg screws. (See Figure 1)
  6. Loosen motor frame/belly band screw and remove the motor from the blower housing. (See Figure 2)
  7. Position frame/belly band on to the replacement motor per the dimensions and instructions. (See Figure 3 or 4 as applicable)
  8. On 3/4hp & 1hp motors, position motor mounting legs in the embossed part of belly band.
  9. Tighten motor frame/belly band screw, position motor back on to the blower housing and tighten all motor mount leg screws. Tighten motor shaft set screw as well.
  10. Slide blower-motor assembly back into the unit. Secure blower housing back on to the blower deck using screws removed in step 3. (See Figure 1)
  11. Plug wires back to the blower motor. Reinstall blower access panel, and power back the unit.

Diagrams

Figure 1: Pictorial for loosening shaft bolt & blower housing screws.

Figure 2: Pictorial for loosening motor mount screws to pull out motor & loosening motor mount to remove motor.

Figure 3: Shows positioning of motor wiring plugs between legs as viewed from the motor end. Includes measurements of 2-1/2 inches.

Figure 4: Shows positioning of motor wiring plugs between shipping leg and mounting leg as viewed from the motor end. Includes measurements of 1.00 inch.

▲ WARNING

Electric Shock Hazard! Disconnect all power supplies before servicing. Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.

PDF preview unavailable. Download the PDF instead.

508015-01 Adobe PDF Library 15.0 Adobe InDesign CC 14.0 (Windows)

Related Documents

Preview Lennox ML296UHV(K) Merit Series Gas Furnace - Product Specifications and Features
Comprehensive product specifications, feature highlights, installation details, and technical data for the Lennox ML296UHV(K) Merit Series residential gas furnace. Learn about its 96% AFUE, two-stage heating, variable speed blower, and advanced controls.
Preview Lennox Blower Assembly Replacement Kit Installation Instructions
Detailed installation instructions for the Lennox Blower Assembly Replacement Kit used with LGM/LCM092-150U units. Includes shipping and packing list, application details, and step-by-step installation procedures.
Preview Lennox Integrated Control Replacement Kit 23C48 Installation Instructions
Installation guide for the Lennox Integrated Control Replacement Kit 23C48, providing step-by-step instructions and wiring diagrams for single-stage furnaces with constant torque indoor blower motors.
Preview Lennox Blower Replacement Kit Installation Instructions for LGM/LGT092-150 Units
This document provides detailed installation instructions for the Lennox Blower Replacement Kit (part numbers 626031-01, 626031-02, 31A56, 31A57) compatible with LGM/LGT092-150 HVAC units. It covers essential steps including firmware updates, application specifics, blower motor replacement, limit switch installation, T4 transformer setup, and wiring connections, along with important safety warnings and cautions.
Preview Lennox CH35 Series Indoor Coil Installation Instructions
Comprehensive installation guide for Lennox CH35 Series indoor evaporator coils, covering model identification, specifications, installation procedures, refrigerant line connections, leak testing, condensate drain setup, blower speed selection, and maintenance.
Preview Lennox CX35 Series Coils Installation Instructions
Detailed installation instructions for Lennox CX35 Series Indoor Evaporator Coils with R410A refrigerant. Covers model identification, shipping, refrigerant handling, installation procedures, condensate drain connections, blower speed selection, maintenance, and decommissioning.
Preview Lennox 59M03 Flue Transition Replacement Kit Installation Instructions
Detailed installation guide for the Lennox 59M03 Flue Transition Replacement Kit, designed for G26, 90UGF, and G32 series HVAC units. Includes safety warnings, parts list, and step-by-step instructions for replacing the flue transition and adding a drain for the combustion air inducer.
Preview Lennox EL296UHE Elite Series Gas Furnace: Specifications and Features
Detailed product specifications, features, and technical information for the Lennox EL296UHE Elite Series gas furnace, highlighting its 96% AFUE, two-stage heating, and constant torque blower.