YORK Technical Guide: HH8 Series - 18 SEER2 Horizontal Discharge Variable Speed Heat Pump
R-454B Single-Phase - 2 nominal ton to 5 nominal ton
York International Corporation, 5005 York Drive, Norman, OK 73069
6523470-YTG-B-0824
Supersedes: 6523470-YTG-A-0724
2024-08-26
Johnson Controls Ducted Systems
Description
HH8 horizontal discharge variable speed heat pumps are the outdoor section of a high-efficiency heating and cooling system. The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Match each HH8 unit with one ducted indoor unit. This unit is not designed for application in a ductless configuration. Sweat connect units are factory charged with refrigerant for a nominal sized matching indoor coil plus 15 ft of field-supplied lines.
Figure 1: Installation certification map
A map of the US and Canada indicating installation allowance. Note: Not currently certified for installation in localities requiring hurricane certification. Check local codes for specific requirements.
Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.simplygettingthejobdone.com and www.york.com. Additional rating information can be found at www.ahridirectory.org.
Certification
The units are certified by ETL LISTED Intertek, AHRI CERTIFIED Unitary Small HP, AHRI Standard 210/240, and assembled at a facility with an ISO 9001:2015-certified Quality Management System.
Warranty Summary
Extended 10-year limited parts warranty.
Extended 10-year limited compressor warranty.
Extended parts and compressor warranties require online registration within 90 days of purchase for replacement or closing for new home construction.
The warranty does not apply to R-22 models, R410A models, three-phase models, or internet sales. See the Limited Warranty certificate in the User's Information Manual for details.
Features
- 360 DC inverter driven technology: Controls compressor rotation and speed, optimizing energy usage and compressor stability across operating conditions for optimal space temperature control and quiet operation.
- Pressure sensor: Detects low cooling pressure and high heating pressure to protect the system from damage. Enables intelligent control by calculating indoor coil temperature from system suction pressure.
- Smaller outdoor form factor for installation flexibility: This side-discharge outdoor unit saves approximately 35% space over traditional air conditioners, offering flexibility for wall, yard, or roof installation.
- Stable temperature control means optimal comfort: The DC inverter provides full capacity at startup for rapid cooling or warming and adjusts speed to prevent temperature fluctuation and energy loss.
- Agency listed: Safety certified by UL 60335-2-40:2022 Ed.4 and CSA C22.2#60335-2-40:2022 Ed.4. Performance certified to ANSI/AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.
Nomenclature
Table 1: Horizontal discharge AC and HP nomenclature
Number | Category | Option | Description |
---|---|---|---|
1 | Configuration | H | Horizontal discharge |
2 | Product type | C | Air conditioner |
H | Heat pump | ||
3 | Efficiency | 3 | 13 SEER2 |
4 | 14 SEER2 | ||
5 | 15 SEER2 | ||
6 | 16 SEER2 | ||
7 | 17 SEER2 | ||
8 | 18 SEER2 | ||
9 | 19 SEER2 | ||
4, 5 | Capacity | 12 | 1 ton |
18 | 1.5 ton | ||
24 | 2 ton | ||
30 | 2.5 ton | ||
34 | 3 ton | ||
36 | 3 ton | ||
42 | 3.5 ton | ||
48 | 4 ton | ||
60 | 5 ton | ||
6 | Refrigerant | D | TBC |
E | R-454B | ||
7 | Voltage | 2 | 208/230-1-60 |
3 | 208/230-3-60 | ||
4 | 460-3-60 | ||
5 | 575-3-60 | ||
8 | Control strategy | C | Communicating |
B | Wireless (communicating) | ||
S | Standard (conventional) | ||
W | Wireless (conventional) | ||
9 | Factory option | 1 | Standard (no options) |
2 | Hard start kit | ||
3 | Coastal condenser coil | ||
4 | Coastal condenser coil with hard start kit | ||
10 | Generation | 1 | First generation |
2 | Second generation | ||
11 | Style | A | Style A |
B | Style B |
Table 2: Model nomenclature example
Number | 1 | 2 | 3 | 4, 5 | 6 | 7 | 8 | 9 | 10 | 11 |
---|---|---|---|---|---|---|---|---|---|---|
Option | H | H | 8 | 24 | E | 2 | S | 1 | 1 | A |
Physical and Electrical Data
Table 3: Physical and electrical data
Outdoor unit model | HH824E2S11 | HH836E2S11 | HH860E2S11 |
---|---|---|---|
Unit supply voltage | 208/230 V, 1 phase, 60 Hz | ||
Normal voltage range¹ (V) | 187 -- 252 | ||
Minimum circuit ampacity (A) | 24 | 28 | 37 |
Maximum overcurrent device² (A) | 35 | 35 | 45 |
Compressor type | Twin rotary | Twin rotary | Twin rotary |
Compressor rated load | 16.8 | 19.0 | 27.0 |
Crankcase heater | Yes | Yes | Yes |
Base pan heater | Yes | Yes | Yes |
Fan diameter (in.) | 21.89 | 24.4 | 21.85 |
Fan motor rated HP | 1/7 | 1/3 | 1/5 |
Fan motor rated load (A) | 0.80 | 1.50 | 1.00 |
Fan motor nominal RPM | 870 | 850 | 880 |
Fan motor nominal CFM | 2235 | 3350 | 4820 |
Coil face area (sq. ft.) | 7.49 | 10.76 | 14.87 |
Coil rows deep | 2 | 2 | 2.6 |
Coil fins per inch | 17 | 18 | 18 |
Liquid refrigerant piping outdoor unit (field installed) | 3/8 | 3/8 | 3/8 |
Vapor refrigerant piping outdoor unit (field installed)³˒⁴ | 5/8 | 3/4 | 7/8 |
Unit charge (lb-oz) | 5-01 | 7-07 | 11-00 |
Charge (oz/ft) | 0.54 | 0.57 | 0.6 |
Operating weight (lb) | 116.8 | 185.2 | 244.7 |
Physical and electrical data notes:
- 1. Rated in accordance with AHRI Standard 110-2016, utilization range A.
- 2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
- 3. For applications with non-standard vapor line sizes, see Applications and accessories.
- 4. The unit charge provided is correct for the outdoor unit, smallest matched indoor unit, and 15 ft of refrigerant piping. For refrigerant piping lengths other than 15 ft, add or subtract the amount of refrigerant, using the difference in actual refrigerant piping length (not the equivalent length) multiplied by the per foot value.
Dimensions
Table 4: Dimensions
Unit model | Dimensions (in.) | Refrigerant connection service valve (in.) | |||
---|---|---|---|---|---|
A | B | C | Liquid | Vapor | |
HH824E2S11 | 29 1/2 | 35 3/7 | 13 2/5 | 3/8 | 5/8 |
HH836E2S11 | 34 4/9 | 43 1/3 | 17 5/7 | 3/4 | 7/8 |
HH860E2S11 | 57 1/2 | 38 2/5 | 13 |
Figure 2: Dimensions
Diagram showing the outdoor unit with labels A, B, and C indicating dimensions, and refrigerant connection valve sizes.
Dimensions notes:
- All dimensions are in inches and are subject to change without notice.
- The overall height is from the bottom of the base pan to the top of the fan guard.
- The overall length and width include screw heads.
System Charge Table
Table 5: System charge table
Outdoor unit model | HH824E2S11 | HH836E2S11 | HH860E2S11 |
---|---|---|---|
Required metering device | 5A1 | 5C1 | 5C1 |
Indoor coil model | Additional charge (oz) | Additional charge (oz) | Additional charge (oz) |
JHC24*C | 0 | -- | -- |
JHC36*D | 11.2 | 0 | -- |
JHC42*F | -- | 1.6 | -- |
JHC48*G | -- | -- | -4.8* |
JHC60*H | -- | -- | 0** |
JHC60*J | -- | -- | 3.04 |
JHE24*C | 0 | -- | -- |
JHE30*D | 11.2 | 0 | -- |
JHE36*D | 11.2 | -- | -- |
JHE42*F | -- | 1.6 | -4.8* |
JHE48*G | -- | -- | 0** |
JHE60*H | -- | -- | 3.04 |
JHE60*J | -- | -- | -- |
CT(F,M,U)30*C | 0 | -- | -- |
CT(F,M)30*D | 11.2 | 0 | -- |
CT(F,M,U)36*D | 11.2 | -- | -- |
CT(F,M,U)48*F | -- | 1.6 | -4.8* |
CT(F,M,U)60*G | -- | -- | 0** |
CT(F,M,U)60*H | -- | -- | 3.04 |
CT(F,M)60*J | -- | -- | -- |
System charge notes:
- For applications that require a TXV, use S1-1TVM5A1 or S1-1TVM5C1 per this table.
- Use a TXV kit with these indoor units to obtain system performance.
- Systems matched with furnaces or air handlers that are not equipped with blower-off delays may require blower time delay.
- Do not use CTF or CTU coils in horizontal applications.
- The charge adders shown in the table do not indicate that coils are rated for every application. Refer to the performance data tables in the Technical Guide for actual performance for specified system matches. Obtain certified system ratings from www.ahridirectory.org.
- All of the combinations shown in the table require advanced main air circulating fan indoor product.
Note: *This row is a system match if the outdoor unit is configured as a 4 ton model. **This row is a system match if the outdoor unit is configured as a 4 ton or 5 ton model.
Charging
- Check the unit factory charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and 15 ft of interconnecting line tubing.
- Verify the TXV and additional charge required for the specific matched indoor unit in the system using Table 5.
- Add additional charge for the amount of interconnecting line tubing greater than 15 ft at the rate specified in Table 3.
- For indoor matches requiring additional charge, weigh in the refrigerant for the specific matched indoor unit and the actual lineset length.
- After weighing in the charge adders for the matched indoor unit and lineset, verify the system operation against the temperatures and pressures in the charging chart for the outdoor unit. Locate the charging charts on the outdoor unit and also in the Service Data Application Guide at www.simplygettingthejobdone.com. Follow the charging procedure in the Installation Manual according to the type of indoor metering device in the system, and allow 10 min after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the charging chart.
- For downflow installations and horizontal right installations, some indoor units require additional charging adjustments to ensure correct equipment operation. Refer to the Installation Manual for the outdoor unit.
- Permanently stamp the unit nameplate with the total system charge, which is defined as follows: total system charge = base charge (as shipped) + charge adder for matched indoor unit + charge adder for actual lineset length + charge adjustments to match the charging chart.
Applications and Accessories
Table 6: Minimum and maximum operating limit conditions
Ambient temperature limits | Outdoor coil °F (°C) | |
---|---|---|
DB cool | DB heat | |
Minimum | 35 (2) | -13 (-25) |
Maximum | 125 (52) | 75 (24) |
Note: The maximum refrigerant piping equivalent length is 131 ft for HH824E2S11 units, 148 ft for HH836E2S11 units, and 246 ft for HH860E2S11 units.
The following accessories are compatible with H Series heat pumps:
- TXV kits (S1-1TVM*): For applications that require a TXV, use S1-1TVM5A1 or S1-1TVM5C1. See Table 5.
- Filter drier: Use a field-supplied R-454B bi-flow liquid-line filter drier.
Sound Power Rating Cooling
Table 7: Sound power data– stage 2– cooling – octave band sound power level (db re. 1-pW)
Outdoor unit model | Power level 63 (Hz) | Power level 125 (Hz) | Power level 250 (Hz) | Power level 500 (Hz) | Power level 1000 (Hz) | Power level 2000 (Hz) | Power level 4000 (Hz) | Power level 8000 (Hz) | dBA | SQI |
---|---|---|---|---|---|---|---|---|---|---|
HH824E2S11 | 65 | 64 | 63 | 62 | 60 | 56 | 49 | 57 | 65 | 19.1 |
HH836E2S11 | 70 | 70 | 70 | 68 | 65 | 59 | 53 | 47 | 70 | 19.1 |
HH860E2S11 | 71 | 75 | 71 | 70 | 66 | 60 | 57 | 54 | 71 | 19.0 |
Sound Power Rating Heating
Table 8: Sound power data– stage 2- heating – octave band sound power level (db re. 1-pW)
Outdoor unit model | Power level 63 (Hz) | Power level 125 (Hz) | Power level 250 (Hz) | Power level 500 (Hz) | Power level 1000 (Hz) | Power level 2000 (Hz) | Power level 4000 (Hz) | Power level 8000 (Hz) | dBA | SQI |
---|---|---|---|---|---|---|---|---|---|---|
HH824E2S11 | 71 | 69 | 64 | 64 | 61 | 58 | 52 | 48 | 66 | 19.1 |
HH836E2S11 | 71 | 68 | 70 | 67 | 64 | 58 | 54 | 49 | 69 | 19.1 |
HH860E2S11 | 73 | 77 | 72 | 71 | 67 | 63 | 64 | 56 | 73 | 19.0 |
Mechanical Specifications
Take note of the mechanical specifications outlined in the following sections.
Manufacture and certifications
- Units shall be assembled at a facility with an ISO 9001:2015-certified Quality Management System.
- Units shall be certified by UL 60335-2-40:2022 Ed.4 and CSA C22.2#60335-2-40:2022 Ed.4 and performance certified to ANSI/AHRI Standard 210/240.
- Units shall be sound tested according to ANSI/AHRI Standard 270.
- Certified matched system ratings will be available for download from the AHRI online directory at www.ahridirectory.org.
Unit application
- Units shall be approved for cooling operation between 35°F and 125°F without modification.
- Units shall be approved for heating operation between -13°F and 75°F without modification.
- Units shall be approved for linesets up to an equivalent length of 131 ft for HH824E2S11 units, 148 ft for HH836E2S11 units, and 246 ft for HH860E2S11 units without modification.
- Units shall be approved for installation at a minimum of 8 in. (long side) and 6 in. (short side) of a flat vertical wall without modification, according to the instructions in the technical literature. See Figure 3.
- Units shall be designed to 73 dBA or less to minimize sound pollution.
Unit access
- Units shall be factory leak checked, run tested, and shipped with a holding charge of R-454B refrigerant.
- Unit cabinet components shall be G90 equivalent steel finished with powder-coat paint rated at a minimum of 1,000 h under ASTM B117 testing.
- Units shall be constructed with a high-pressure switch for system protection.
- Units shall be constructed with all badging and labels applied at the factory.
Unit components
- Compressor shall be hermetic with internal electrical overload protection and internal overpressure protection.
- Compressor shall be mounted on neoprene vibration isolators that do not require the removal of transportation clips or brackets.
- Outdoor fan shall be direct drive with horizontal air discharge for low sound levels.
- Outdoor fan blades shall be swept-wing to minimize sound (applies to select models).
- Outdoor fan motor shall be totally enclosed with permanently lubricated ball bearings motors approved for vertical shaft applications.
- Outdoor fan motor shall be ECM construction with permanently lubricated ball bearing motors approved for vertical shaft applications.
Unit warranties
- Unit manufacturer shall provide a 5-year compressor warranty without a requirement for unit registration.
Typical Installation
Figure 3: Minimum clearances when selecting a location
Diagram illustrating minimum clearance requirements around the outdoor unit, with specific distances for different models (24k/36k: Over 12 in. (300 mm), 60k: Over 24 in. (600 mm)) and general clearances (Over 8 in. (200 mm), Over 6 in. (150 mm), Over 20 in. (500 mm), Over 14 in. (350 mm)).
CAUTION
Take care to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang.
Alternative Installation Clearances
Figure 4: Alternative installation clearances
Diagram showing wall and fence clearances for single units, with dimensions like 6 in., 8 in., 20 in., 36 in. and airflow indicators.
Figure 5: Alternative installation clearances for multiple units
Diagram illustrating clearances between multiple outdoor units, with dimensions like 14 in., 80 in., 12 in., 20 in., 24 in., 36 in.
Performance Data - 2 ton
See the following tables for cooling and heating performance data for the HH824E2S11 unit.
Cooling performance data - 2 ton
Table 9: Cooling performance data - 2 ton
Air temperature entering outdoor unit (°F) | Indoor CFM 600 | Indoor CFM 800 | Indoor CFM 1000 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 22.4 | 25.6 | 25.9 | 28.5 | 31.6 | 25.1 | 26.8 | 26.9 | 29.5 | 32.5 | 27.9 | 28.0 | 28.1 | 30.5 | 33.4 |
Sensible capacity | 22.4 | 22.3 | 19.1 | 19.1 | 15.9 | 25.1 | 25.0 | 20.8 | 20.7 | 16.5 | 27.9 | 27.8 | 22.6 | 22.4 | 17.1 | |
kW | 0.95 | 1.11 | 1.11 | 1.09 | 1.07 | 1.12 | 1.20 | 1.21 | 1.19 | 1.17 | 1.27 | 1.27 | 1.28 | 1.26 | 1.24 | |
65 | Total capacity | 22.3 | 24.9 | 25.1 | 27.6 | 30.4 | 24.6 | 26.0 | 26.0 | 28.5 | 31.3 | 27.0 | 27.2 | 27.0 | 29.5 | 32.2 |
Sensible capacity | 22.3 | 21.8 | 18.4 | 18.7 | 14.9 | 24.6 | 24.4 | 20.3 | 20.5 | 15.8 | 27.0 | 27.1 | 22.3 | 22.3 | 16.8 | |
kW | 1.16 | 1.27 | 1.28 | 1.28 | 1.26 | 1.31 | 1.37 | 1.38 | 1.38 | 1.36 | 1.44 | 1.45 | 1.46 | 1.45 | 1.44 | |
75 | Total capacity | 22.2 | 24.3 | 24.4 | 26.6 | 29.3 | 24.1 | 25.3 | 25.1 | 27.6 | 30.1 | 26.1 | 26.4 | 25.9 | 28.5 | 31.1 |
Sensible capacity | 22.2 | 21.4 | 17.7 | 18.3 | 13.8 | 24.1 | 23.8 | 19.9 | 20.2 | 15.1 | 26.1 | 26.3 | 22.1 | 22.2 | 16.5 | |
kW | 1.37 | 1.44 | 1.44 | 1.46 | 1.45 | 1.50 | 1.54 | 1.55 | 1.57 | 1.56 | 1.61 | 1.62 | 1.65 | 1.65 | 1.64 | |
85 | Total capacity | 21.5 | 23.3 | 23.1 | 25.6 | 28.2 | 23.3 | 24.3 | 24.0 | 26.4 | 28.9 | 25.2 | 25.3 | 24.9 | 27.3 | 29.8 |
Sensible capacity | 21.5 | 20.8 | 17.3 | 17.7 | 13.8 | 23.3 | 23.3 | 19.3 | 19.6 | 14.9 | 25.2 | 25.3 | 21.4 | 21.5 | 16.1 | |
kW | 1.59 | 1.63 | 1.64 | 1.66 | 1.66 | 1.71 | 1.74 | 1.75 | 1.77 | 1.77 | 1.82 | 1.83 | 1.84 | 1.85 | 1.86 | |
95 | Total capacity | 20.8 | 22.4 | 21.9 | 24.6 | 27.1 | 22.5 | 23.2 | 22.9 | 25.3 | 27.8 | 24.3 | 24.2 | 23.9 | 26.1 | 28.4 |
Sensible capacity | 20.8 | 20.2 | 16.9 | 17.1 | 13.7 | 22.5 | 22.7 | 18.7 | 18.9 | 14.6 | 24.3 | 24.2 | 20.7 | 20.8 | 15.6 | |
kW | 1.81 | 1.83 | 1.83 | 1.85 | 1.88 | 1.93 | 1.94 | 1.94 | 1.97 | 1.99 | 2.04 | 2.04 | 2.03 | 2.06 | 2.07 | |
105 | Total capacity | 19.3 | 20.4 | 20.1 | 23.3 | 24.8 | 20.6 | 21.2 | 21.1 | 23.6 | 25.5 | 22.2 | 22.1 | 22.2 | 24.1 | 26.1 |
Sensible capacity | 19.3 | 18.2 | 15.5 | 16.0 | 12.5 | 20.6 | 20.2 | 17.1 | 17.6 | 13.3 | 22.2 | 22.1 | 18.7 | 19.3 | 14.3 | |
kW | 2.01 | 2.02 | 2.02 | 2.18 | 2.09 | 2.17 | 2.17 | 2.17 | 2.34 | 2.20 | 2.27 | 2.27 | 2.27 | 2.43 | 2.29 | |
115 | Total capacity | 17.7 | 18.3 | 18.3 | 21.9 | 22.5 | 18.7 | 19.1 | 19.3 | 21.9 | 23.1 | 20.0 | 19.9 | 20.5 | 22.0 | 23.8 |
Sensible capacity | 17.6 | 16.2 | 14.0 | 14.9 | 11.2 | 18.4 | 17.6 | 15.4 | 16.3 | 12.0 | 19.3 | 19.1 | 16.7 | 17.8 | 13.0 | |
kW | 2.20 | 2.20 | 2.20 | 2.50 | 2.30 | 2.40 | 2.40 | 2.40 | 2.70 | 2.40 | 2.50 | 2.50 | 2.50 | 2.80 | 2.50 | |
125 | Total capacity | 12.2 | 12.3 | 12.5 | 15.8 | 15.3 | 12.9 | 12.8 | 13.4 | 15.5 | 15.8 | 13.6 | 13.5 | 14.4 | 15.2 | 16.3 |
Sensible capacity | 12.2 | 12.3 | 12.0 | 13.1 | 9.3 | 12.9 | 12.8 | 13.0 | 14.2 | 10.1 | 13.6 | 13.5 | 14.0 | 15.2 | 11.1 | |
kW | 1.54 | 1.54 | 1.54 | 1.83 | 1.55 | 1.65 | 1.65 | 1.64 | 1.94 | 1.66 | 1.74 | 1.73 | 1.73 | 2.02 | 1.74 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 2 ton
Table 10: Heating performance data - 2 ton
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 26.6 | 24.0 | 21.8 | 20.8 | 18.4 | 17.6 | 17.0 | 16.7 | 13.8 | 12.9 |
kW | 1.8 | 1.95 | 1.96 | 1.96 | 1.96 | 2.20 | 2.37 | 2.51 | 2.16 | 2.35 |
COP | 4.36 | 3.60 | 3.26 | 3.12 | 2.75 | 2.34 | 2.10 | 1.95 | 1.88 | 1.61 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 3 ton
See the following tables for cooling and heating performance data for the HH836E2S11 unit.
Cooling performance data - 3 ton
Table 11: Cooling performance data - 3 ton
Air temperature entering outdoor unit (°F) | Indoor CFM 850 | Indoor CFM 1125 | Indoor CFM 1400 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 28.7 | 35.9 | 37.2 | 39.2 | 43.8 | 33.5 | 37.8 | 39.4 | 41.4 | 46.4 | 38.6 | 39.9 | 41.8 | 43.8 | 49.1 |
Sensible capacity | 28.7 | 29.8 | 26.3 | 25.9 | 20.8 | 33.5 | 34.0 | 29.8 | 29.0 | 22.8 | 38.6 | 38.5 | 33.4 | 32.2 | 25.1 | |
kW | 1.21 | 1.62 | 1.63 | 1.59 | 1.56 | 1.53 | 1.73 | 1.74 | 1.70 | 1.66 | 1.79 | 1.78 | 1.79 | 1.75 | 1.71 | |
65 | Total capacity | 30.1 | 35.0 | 35.6 | 38.6 | 42.4 | 33.8 | 37.2 | 37.7 | 40.8 | 44.5 | 37.6 | 39.6 | 40.0 | 43.1 | 46.7 |
Sensible capacity | 30.1 | 29.7 | 25.7 | 25.6 | 20.4 | 33.8 | 33.9 | 29.0 | 28.7 | 22.3 | 37.6 | 38.3 | 32.5 | 32.1 | 24.3 | |
kW | 1.59 | 1.87 | 1.87 | 1.85 | 1.82 | 1.85 | 1.98 | 1.98 | 1.96 | 1.94 | 2.04 | 2.04 | 2.05 | 2.02 | 1.99 | |
75 | Total capacity | 31.6 | 34.0 | 34.0 | 38.1 | 41.0 | 34.0 | 36.5 | 36.0 | 40.1 | 42.6 | 36.7 | 39.2 | 38.2 | 42.3 | 44.3 |
Sensible capacity | 31.3 | 29.5 | 25.0 | 25.3 | 20.0 | 34.0 | 33.7 | 28.2 | 28.5 | 21.7 | 36.7 | 38.1 | 31.6 | 31.9 | 23.6 | |
kW | 1.97 | 2.11 | 2.10 | 2.10 | 2.09 | 2.16 | 2.23 | 2.23 | 2.23 | 2.21 | 2.29 | 2.30 | 2.30 | 2.29 | 2.27 | |
85 | Total capacity | 29.2 | 32.4 | 32.9 | 35.7 | 38.9 | 32.2 | 34.3 | 34.3 | 37.2 | 40.8 | 35.5 | 36.5 | 36.0 | 39.0 | 43.0 |
Sensible capacity | 29.2 | 28.9 | 24.3 | 24.2 | 19.2 | 32.2 | 32.6 | 27.6 | 27.2 | 20.9 | 35.5 | 36.5 | 31.1 | 30.3 | 22.9 | |
kW | 2.29 | 2.39 | 2.38 | 2.40 | 2.39 | 2.47 | 2.52 | 2.51 | 2.52 | 2.52 | 2.59 | 2.59 | 2.58 | 2.59 | 2.59 | |
95 | Total capacity | 26.9 | 30.8 | 31.7 | 33.2 | 36.8 | 30.5 | 32.2 | 32.7 | 34.3 | 39.1 | 34.3 | 33.8 | 33.9 | 35.6 | 41.6 |
Sensible capacity | 26.9 | 28.2 | 23.6 | 23.1 | 18.3 | 30.5 | 31.4 | 27.0 | 25.8 | 20.2 | 34.3 | 33.8 | 30.7 | 28.8 | 22.2 | |
kW | 2.61 | 2.67 | 2.66 | 2.69 | 2.70 | 2.77 | 2.80 | 2.79 | 2.82 | 2.83 | 2.89 | 2.88 | 2.87 | 2.90 | 2.90 | |
105 | Total capacity | 26.3 | 29.4 | 27.1 | 30.6 | 35.0 | 29.1 | 30.3 | 28.9 | 31.8 | 37.2 | 32.1 | 31.4 | 31.1 | 33.4 | 39.5 |
Sensible capacity | 26.3 | 26.6 | 20.9 | 22.2 | 17.9 | 29.1 | 28.8 | 24.4 | 24.5 | 19.8 | 31.6 | 31.2 | 28.2 | 27.0 | 22.0 | |
kW | 3.11 | 3.19 | 2.83 | 3.05 | 3.25 | 3.29 | 3.30 | 3.15 | 3.26 | 3.42 | 3.45 | 3.34 | 3.44 | 3.35 | 3.50 | |
115 | Total capacity | 25.7 | 28.0 | 22.4 | 27.9 | 33.2 | 27.7 | 28.4 | 25.1 | 29.3 | 35.2 | 29.9 | 29.0 | 28.2 | 31.1 | 37.4 |
Sensible capacity | 25.1 | 25.0 | 18.1 | 21.2 | 17.4 | 26.7 | 26.1 | 21.7 | 23.2 | 19.4 | 28.5 | 27.5 | 25.6 | 25.2 | 21.8 | |
kW | 3.60 | 3.70 | 3.00 | 3.40 | 3.80 | 3.80 | 3.80 | 3.50 | 3.70 | 4.00 | 4.00 | 3.80 | 4.00 | 3.80 | 4.10 | |
125 | Total capacity | 16.3 | 17.1 | 10.2 | 15.7 | 20.1 | 16.9 | 16.8 | 12.9 | 16.9 | 21.3 | 17.6 | 16.7 | 15.8 | 18.3 | 22.7 |
Sensible capacity | 16.3 | 17.0 | 10.2 | 15.0 | 12.5 | 16.9 | 16.8 | 12.9 | 15.9 | 14.1 | 17.6 | 16.7 | 15.8 | 17.0 | 16.0 | |
kW | 1.93 | 1.99 | 1.40 | 1.71 | 2.05 | 2.06 | 2.02 | 1.79 | 1.89 | 2.18 | 2.13 | 2.01 | 2.13 | 2.01 | 2.25 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 2 ton
Table 10: Heating performance data - 2 ton
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 26.6 | 24.0 | 21.8 | 20.8 | 18.4 | 17.6 | 17.0 | 16.7 | 13.8 | 12.9 |
kW | 1.8 | 1.95 | 1.96 | 1.96 | 1.96 | 2.20 | 2.37 | 2.51 | 2.16 | 2.35 |
COP | 4.36 | 3.60 | 3.26 | 3.12 | 2.75 | 2.34 | 2.10 | 1.95 | 1.88 | 1.61 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 3 ton
See the following tables for cooling and heating performance data for the HH836E2S11 unit.
Cooling performance data - 3 ton
Table 11: Cooling performance data - 3 ton
Air temperature entering outdoor unit (°F) | Indoor CFM 850 | Indoor CFM 1125 | Indoor CFM 1400 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 28.7 | 35.9 | 37.2 | 39.2 | 43.8 | 33.5 | 37.8 | 39.4 | 41.4 | 46.4 | 38.6 | 39.9 | 41.8 | 43.8 | 49.1 |
Sensible capacity | 28.7 | 29.8 | 26.3 | 25.9 | 20.8 | 33.5 | 34.0 | 29.8 | 29.0 | 22.8 | 38.6 | 38.5 | 33.4 | 32.2 | 25.1 | |
kW | 1.21 | 1.62 | 1.63 | 1.59 | 1.56 | 1.53 | 1.73 | 1.74 | 1.70 | 1.66 | 1.79 | 1.78 | 1.79 | 1.75 | 1.71 | |
65 | Total capacity | 30.1 | 35.0 | 35.6 | 38.6 | 42.4 | 33.8 | 37.2 | 37.7 | 40.8 | 44.5 | 37.6 | 39.6 | 40.0 | 43.1 | 46.7 |
Sensible capacity | 30.1 | 29.7 | 25.7 | 25.6 | 20.4 | 33.8 | 33.9 | 29.0 | 28.7 | 22.3 | 37.6 | 38.3 | 32.5 | 32.1 | 24.3 | |
kW | 1.59 | 1.87 | 1.87 | 1.85 | 1.82 | 1.85 | 1.98 | 1.98 | 1.96 | 1.94 | 2.04 | 2.04 | 2.05 | 2.02 | 1.99 | |
75 | Total capacity | 31.6 | 34.0 | 34.0 | 38.1 | 41.0 | 34.0 | 36.5 | 36.0 | 40.1 | 42.6 | 36.7 | 39.2 | 38.2 | 42.3 | 44.3 |
Sensible capacity | 31.3 | 29.5 | 25.0 | 25.3 | 20.0 | 34.0 | 33.7 | 28.2 | 28.5 | 21.7 | 36.7 | 38.1 | 31.6 | 31.9 | 23.6 | |
kW | 1.97 | 2.11 | 2.10 | 2.10 | 2.09 | 2.16 | 2.23 | 2.23 | 2.23 | 2.21 | 2.29 | 2.30 | 2.30 | 2.29 | 2.27 | |
85 | Total capacity | 29.2 | 32.4 | 32.9 | 35.7 | 38.9 | 32.2 | 34.3 | 34.3 | 37.2 | 40.8 | 35.5 | 36.5 | 36.0 | 39.0 | 43.0 |
Sensible capacity | 29.2 | 28.9 | 24.3 | 24.2 | 19.2 | 32.2 | 32.6 | 27.6 | 27.2 | 20.9 | 35.5 | 36.5 | 31.1 | 30.3 | 22.9 | |
kW | 2.29 | 2.39 | 2.38 | 2.40 | 2.39 | 2.47 | 2.52 | 2.51 | 2.52 | 2.52 | 2.59 | 2.59 | 2.58 | 2.59 | 2.59 | |
95 | Total capacity | 26.9 | 30.8 | 31.7 | 33.2 | 36.8 | 30.5 | 32.2 | 32.7 | 34.3 | 39.1 | 34.3 | 33.8 | 33.9 | 35.6 | 41.6 |
Sensible capacity | 26.9 | 28.2 | 23.6 | 23.1 | 18.3 | 30.5 | 31.4 | 27.0 | 25.8 | 20.2 | 34.3 | 33.8 | 30.7 | 28.8 | 22.2 | |
kW | 2.61 | 2.67 | 2.66 | 2.69 | 2.70 | 2.77 | 2.80 | 2.79 | 2.82 | 2.83 | 2.89 | 2.88 | 2.87 | 2.90 | 2.90 | |
105 | Total capacity | 26.3 | 29.4 | 27.1 | 30.6 | 35.0 | 29.1 | 30.3 | 28.9 | 31.8 | 37.2 | 32.1 | 31.4 | 31.1 | 33.4 | 39.5 |
Sensible capacity | 26.3 | 26.6 | 20.9 | 22.2 | 17.9 | 29.1 | 28.8 | 24.4 | 24.5 | 19.8 | 31.6 | 31.2 | 28.2 | 27.0 | 22.0 | |
kW | 3.11 | 3.19 | 2.83 | 3.05 | 3.25 | 3.29 | 3.30 | 3.15 | 3.26 | 3.42 | 3.45 | 3.34 | 3.44 | 3.35 | 3.50 | |
115 | Total capacity | 25.7 | 28.0 | 22.4 | 27.9 | 33.2 | 27.7 | 28.4 | 25.1 | 29.3 | 35.2 | 29.9 | 29.0 | 28.2 | 31.1 | 37.4 |
Sensible capacity | 25.1 | 25.0 | 18.1 | 21.2 | 17.4 | 26.7 | 26.1 | 21.7 | 23.2 | 19.4 | 28.5 | 27.5 | 25.6 | 25.2 | 21.8 | |
kW | 3.60 | 3.70 | 3.00 | 3.40 | 3.80 | 3.80 | 3.80 | 3.50 | 3.70 | 4.00 | 4.00 | 3.80 | 4.00 | 3.80 | 4.10 | |
125 | Total capacity | 16.3 | 17.1 | 10.2 | 15.7 | 20.1 | 16.9 | 16.8 | 12.9 | 16.9 | 21.3 | 17.6 | 16.7 | 15.8 | 18.3 | 22.7 |
Sensible capacity | 16.3 | 17.0 | 10.2 | 15.0 | 12.5 | 16.9 | 16.8 | 12.9 | 15.9 | 14.1 | 17.6 | 16.7 | 15.8 | 17.0 | 16.0 | |
kW | 1.93 | 1.99 | 1.40 | 1.71 | 2.05 | 2.06 | 2.02 | 1.79 | 1.89 | 2.18 | 2.13 | 2.01 | 2.13 | 2.01 | 2.25 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 3 ton
Table 12: Heating performance data - 3 ton
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 36.0 | 32.4 | 30.1 | 29.1 | 26.6 | 25.8 | 25.2 | 24.0 | 22.7 | 19.3 |
kW | 2.6 | 2.71 | 2.85 | 2.91 | 3.06 | 3.33 | 3.52 | 3.70 | 3.89 | 3.58 |
COP | 4.05 | 3.50 | 3.09 | 2.93 | 2.54 | 2.27 | 2.10 | 1.90 | 1.71 | 1.58 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 4 ton
You can configure the HH860E2S11 unit as a 4 ton model by adjusting the DIP switch settings. See the following tables for cooling and heating performance data for the HH860E2S11 unit configured as a 4 ton model.
Cooling performance data - 4 ton
Table 13: Cooling performance data - 4 ton - adjust DIP switch setting on 60k to configure 48k
Air temperature entering outdoor unit (°F) | Indoor CFM 1200 | Indoor CFM 1600 | Indoor CFM 2000 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 36.0 | 43.9 | 42.0 | 49.5 | 51.0 | 41.1 | 49.2 | 47.8 | 56.9 | 53.9 | 45.9 | 54.2 | 53.3 | 64.0 | 56.5 |
Sensible capacity | 35.4 | 36.3 | 30.4 | 31.3 | 24.8 | 40.5 | 42.2 | 34.7 | 35.7 | 25.9 | 45.2 | 47.9 | 38.9 | 39.8 | 26.8 | |
kW | 1.80 | 2.12 | 2.10 | 2.24 | 2.20 | 2.19 | 2.38 | 2.37 | 2.43 | 2.39 | 2.67 | 2.73 | 2.73 | 2.70 | 2.67 | |
65 | Total capacity | 36.6 | 43.2 | 42.5 | 47.1 | 50.7 | 41.1 | 47.1 | 47.0 | 52.8 | 53.6 | 45.3 | 50.7 | 51.2 | 58.2 | 56.3 |
Sensible capacity | 35.7 | 35.7 | 29.6 | 30.1 | 23.6 | 40.2 | 40.7 | 33.6 | 34.0 | 25.4 | 44.4 | 45.5 | 37.3 | 37.7 | 26.8 | |
kW | 2.19 | 2.50 | 2.49 | 2.56 | 2.53 | 2.56 | 2.73 | 2.73 | 2.75 | 2.73 | 3.02 | 3.05 | 3.05 | 3.03 | 3.01 | |
75 | Total capacity | 37.1 | 42.5 | 43.1 | 44.6 | 50.4 | 41.0 | 45.0 | 46.2 | 48.6 | 53.4 | 44.7 | 47.3 | 49.1 | 52.3 | 56.1 |
Sensible capacity | 36.0 | 35.0 | 28.9 | 28.8 | 22.5 | 39.9 | 39.2 | 32.5 | 32.4 | 24.8 | 43.5 | 43.2 | 35.8 | 35.7 | 26.9 | |
kW | 2.58 | 2.88 | 2.88 | 2.89 | 2.87 | 2.93 | 3.08 | 3.08 | 3.08 | 3.06 | 3.36 | 3.37 | 3.37 | 3.36 | 3.35 | |
85 | Total capacity | 35.9 | 41.2 | 40.5 | 43.1 | 48.4 | 39.8 | 44.8 | 44.3 | 47.9 | 53.9 | 43.3 | 48.1 | 47.8 | 52.4 | 59.2 |
Sensible capacity | 34.8 | 34.8 | 28.7 | 29.0 | 22.0 | 38.6 | 39.5 | 32.5 | 33.3 | 24.6 | 42.1 | 44.0 | 36.0 | 37.3 | 27.0 | |
kW | 2.89 | 3.21 | 3.21 | 3.23 | 3.14 | 3.27 | 3.42 | 3.42 | 3.44 | 3.40 | 3.73 | 3.72 | 3.72 | 3.74 | 3.74 | |
95 | Total capacity | 34.8 | 39.9 | 38.0 | 41.6 | 46.4 | 38.5 | 44.6 | 42.4 | 47.1 | 54.5 | 41.9 | 49.0 | 46.5 | 52.4 | 62.3 |
Sensible capacity | 33.7 | 34.6 | 28.5 | 29.2 | 21.6 | 37.3 | 39.8 | 32.5 | 34.2 | 24.5 | 40.7 | 44.7 | 36.2 | 38.9 | 27.1 | |
kW | 3.21 | 3.54 | 3.55 | 3.57 | 3.42 | 3.60 | 3.76 | 3.77 | 3.80 | 3.74 | 4.09 | 4.08 | 4.07 | 4.12 | 4.13 | |
105 | Total capacity | 32.1 | 35.9 | 34.7 | 39.4 | 46.4 | 36.3 | 40.2 | 39.0 | 44.8 | 52.6 | 40.0 | 44.2 | 42.8 | 49.9 | 58.5 |
Sensible capacity | 30.7 | 31.3 | 26.3 | 27.8 | 21.6 | 34.7 | 35.6 | 30.0 | 32.8 | 23.7 | 38.4 | 39.7 | 33.3 | 37.4 | 25.5 | |
kW | 3.41 | 3.67 | 3.68 | 3.89 | 4.21 | 4.00 | 3.98 | 4.04 | 4.30 | 4.52 | 4.65 | 4.39 | 4.49 | 4.76 | 4.92 | |
115 | Total capacity | 29.4 | 31.8 | 31.4 | 37.2 | 46.3 | 34.0 | 35.8 | 35.5 | 42.5 | 50.7 | 38.1 | 39.4 | 39.1 | 47.4 | 54.6 |
Sensible capacity | 27.6 | 28.0 | 24.1 | 26.3 | 21.5 | 32.0 | 31.4 | 27.4 | 31.3 | 22.9 | 36.1 | 34.6 | 30.3 | 35.8 | 23.9 | |
kW | 3.60 | 3.80 | 3.80 | 4.20 | 5.00 | 4.40 | 4.20 | 4.30 | 4.80 | 5.30 | 5.20 | 4.70 | 4.90 | 5.40 | 5.70 | |
125 | Total capacity | 16.7 | 17.0 | 17.5 | 22.3 | 30.4 | 20.1 | 19.2 | 20.0 | 25.7 | 31.4 | 23.3 | 21.2 | 22.2 | 28.9 | 32.2 |
Sensible capacity | 16.3 | 16.3 | 14.6 | 16.8 | 14.9 | 19.6 | 17.8 | 16.5 | 20.2 | 15.1 | 22.7 | 19.0 | 18.2 | 23.4 | 15.0 | |
kW | 2.21 | 2.21 | 2.21 | 2.65 | 3.56 | 2.74 | 2.50 | 2.59 | 3.08 | 3.68 | 3.36 | 2.88 | 3.05 | 3.61 | 3.88 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 3 ton
Table 12: Heating performance data - 3 ton
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 36.0 | 32.4 | 30.1 | 29.1 | 26.6 | 25.8 | 25.2 | 24.0 | 22.7 | 19.3 |
kW | 2.6 | 2.71 | 2.85 | 2.91 | 3.06 | 3.33 | 3.52 | 3.70 | 3.89 | 3.58 |
COP | 4.05 | 3.50 | 3.09 | 2.93 | 2.54 | 2.27 | 2.10 | 1.90 | 1.71 | 1.58 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 4 ton
You can configure the HH860E2S11 unit as a 4 ton model by adjusting the DIP switch settings. See the following tables for cooling and heating performance data for the HH860E2S11 unit configured as a 4 ton model.
Cooling performance data - 4 ton
Table 13: Cooling performance data - 4 ton - adjust DIP switch setting on 60k to configure 48k
Air temperature entering outdoor unit (°F) | Indoor CFM 1200 | Indoor CFM 1600 | Indoor CFM 2000 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 36.0 | 43.9 | 42.0 | 49.5 | 51.0 | 41.1 | 49.2 | 47.8 | 56.9 | 53.9 | 45.9 | 54.2 | 53.3 | 64.0 | 56.5 |
Sensible capacity | 35.4 | 36.3 | 30.4 | 31.3 | 24.8 | 40.5 | 42.2 | 34.7 | 35.7 | 25.9 | 45.2 | 47.9 | 38.9 | 39.8 | 26.8 | |
kW | 1.80 | 2.12 | 2.10 | 2.24 | 2.20 | 2.19 | 2.38 | 2.37 | 2.43 | 2.39 | 2.67 | 2.73 | 2.73 | 2.70 | 2.67 | |
65 | Total capacity | 36.6 | 43.2 | 42.5 | 47.1 | 50.7 | 41.1 | 47.1 | 47.0 | 52.8 | 53.6 | 45.3 | 50.7 | 51.2 | 58.2 | 56.3 |
Sensible capacity | 35.7 | 35.7 | 29.6 | 30.1 | 23.6 | 40.2 | 40.7 | 33.6 | 34.0 | 25.4 | 44.4 | 45.5 | 37.3 | 37.7 | 26.8 | |
kW | 2.19 | 2.50 | 2.49 | 2.56 | 2.53 | 2.56 | 2.73 | 2.73 | 2.75 | 2.73 | 3.02 | 3.05 | 3.05 | 3.03 | 3.01 | |
75 | Total capacity | 37.1 | 42.5 | 43.1 | 44.6 | 50.4 | 41.0 | 45.0 | 46.2 | 48.6 | 53.4 | 44.7 | 47.3 | 49.1 | 52.3 | 56.1 |
Sensible capacity | 36.0 | 35.0 | 28.9 | 28.8 | 22.5 | 39.9 | 39.2 | 32.5 | 32.4 | 24.8 | 43.5 | 43.2 | 35.8 | 35.7 | 26.9 | |
kW | 2.58 | 2.88 | 2.88 | 2.89 | 2.87 | 2.93 | 3.08 | 3.08 | 3.08 | 3.06 | 3.36 | 3.37 | 3.37 | 3.36 | 3.35 | |
85 | Total capacity | 35.9 | 41.2 | 40.5 | 43.1 | 48.4 | 39.8 | 44.8 | 44.3 | 47.9 | 53.9 | 43.3 | 48.1 | 47.8 | 52.4 | 59.2 |
Sensible capacity | 34.8 | 34.8 | 28.7 | 29.0 | 22.0 | 38.6 | 39.5 | 32.5 | 33.3 | 24.6 | 42.1 | 44.0 | 36.0 | 37.3 | 27.0 | |
kW | 2.89 | 3.21 | 3.21 | 3.23 | 3.14 | 3.27 | 3.42 | 3.42 | 3.44 | 3.40 | 3.73 | 3.72 | 3.72 | 3.74 | 3.74 | |
95 | Total capacity | 34.8 | 39.9 | 38.0 | 41.6 | 46.4 | 38.5 | 44.6 | 42.4 | 47.1 | 54.5 | 41.9 | 49.0 | 46.5 | 52.4 | 62.3 |
Sensible capacity | 33.7 | 34.6 | 28.5 | 29.2 | 21.6 | 37.3 | 39.8 | 32.5 | 34.2 | 24.5 | 40.7 | 44.7 | 36.2 | 38.9 | 27.1 | |
kW | 3.21 | 3.54 | 3.55 | 3.57 | 3.42 | 3.60 | 3.76 | 3.77 | 3.80 | 3.74 | 4.09 | 4.08 | 4.07 | 4.12 | 4.13 | |
105 | Total capacity | 32.1 | 35.9 | 34.7 | 39.4 | 46.4 | 36.3 | 40.2 | 39.0 | 44.8 | 52.6 | 40.0 | 44.2 | 42.8 | 49.9 | 58.5 |
Sensible capacity | 30.7 | 31.3 | 26.3 | 27.8 | 21.6 | 34.7 | 35.6 | 30.0 | 32.8 | 23.7 | 38.4 | 39.7 | 33.3 | 37.4 | 25.5 | |
kW | 3.41 | 3.67 | 3.68 | 3.89 | 4.21 | 4.00 | 3.98 | 4.04 | 4.30 | 4.52 | 4.65 | 4.39 | 4.49 | 4.76 | 4.92 | |
115 | Total capacity | 29.4 | 31.8 | 31.4 | 37.2 | 46.3 | 34.0 | 35.8 | 35.5 | 42.5 | 50.7 | 38.1 | 39.4 | 39.1 | 47.4 | 54.6 |
Sensible capacity | 27.6 | 28.0 | 24.1 | 26.3 | 21.5 | 32.0 | 31.4 | 27.4 | 31.3 | 22.9 | 36.1 | 34.6 | 30.3 | 35.8 | 23.9 | |
kW | 3.60 | 3.80 | 3.80 | 4.20 | 5.00 | 4.40 | 4.20 | 4.30 | 4.80 | 5.30 | 5.20 | 4.70 | 4.90 | 5.40 | 5.70 | |
125 | Total capacity | 16.7 | 17.0 | 17.5 | 22.3 | 30.4 | 20.1 | 19.2 | 20.0 | 25.7 | 31.4 | 23.3 | 21.2 | 22.2 | 28.9 | 32.2 |
Sensible capacity | 16.3 | 16.3 | 14.6 | 16.8 | 14.9 | 19.6 | 17.8 | 16.5 | 20.2 | 15.1 | 22.7 | 19.0 | 18.2 | 23.4 | 15.0 | |
kW | 2.21 | 2.21 | 2.21 | 2.65 | 3.56 | 2.74 | 2.50 | 2.59 | 3.08 | 3.68 | 3.36 | 2.88 | 3.05 | 3.61 | 3.88 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 4 ton
Table 14: Heating performance data - 4 ton - adjust DIP switch setting on 60k to configure 48k
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 51.2 | 46.0 | 41.8 | 40.1 | 35.5 | 34.6 | 34.0 | 31.0 | 28.0 | 25.0 |
kW | 3.9 | 3.85 | 3.90 | 3.92 | 3.97 | 4.42 | 4.75 | 4.53 | 4.32 | 4.11 |
COP | 3.83 | 3.50 | 3.14 | 3.00 | 2.62 | 2.30 | 2.10 | 2.00 | 1.90 | 1.78 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 5 ton
See the following tables for cooling and heating performance data for the HH860E2S11 unit.
Cooling performance data - 5 ton
Table 15: Cooling performance data - 5 ton
Air temperature entering outdoor unit (°F) | Indoor CFM 1200 | Indoor CFM 1600 | Indoor CFM 2000 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 40.0 | 54.8 | 55.5 | 60.1 | 62.3 | 47.8 | 57.8 | 58.3 | 64.2 | 64.6 | 55.5 | 60.6 | 60.9 | 68.1 | 66.8 |
Sensible capacity | 40.0 | 47.5 | 39.9 | 41.0 | 31.3 | 47.8 | 51.7 | 42.5 | 43.8 | 32.40 | 55.5 | 55.8 | 44.9 | 46.5 | 33.2 | |
kW | 1.70 | 2.91 | 2.91 | 2.91 | 2.82 | 2.35 | 3.09 | 3.08 | 3.08 | 3.03 | 3.04 | 3.31 | 3.30 | 3.28 | 3.28 | |
65 | Total capacity | 41.2 | 53.0 | 54.5 | 58.2 | 62.8 | 48.2 | 56.0 | 57.8 | 61.9 | 65.2 | 55.1 | 58.8 | 61.0 | 65.5 | 67.5 |
Sensible capacity | 41.2 | 45.3 | 39.6 | 39.7 | 31.7 | 48.2 | 50.2 | 42.8 | 42.7 | 33.0 | 55.1 | 55.0 | 45.8 | 45.6 | 34.1 | |
kW | 2.23 | 3.20 | 3.27 | 3.29 | 3.26 | 2.85 | 3.41 | 3.45 | 3.46 | 3.45 | 3.52 | 3.66 | 3.66 | 3.68 | 3.68 | |
75 | Total capacity | 42.5 | 51.2 | 53.6 | 56.4 | 63.3 | 48.7 | 54.2 | 57.4 | 59.7 | 65.8 | 54.8 | 57.1 | 61.0 | 62.9 | 68.2 |
Sensible capacity | 42.5 | 43.1 | 39.2 | 38.4 | 32.1 | 48.7 | 48.7 | 43.0 | 41.6 | 33.6 | 54.8 | 54.3 | 46.7 | 44.7 | 34.9 | |
kW | 2.76 | 3.49 | 3.63 | 3.66 | 3.70 | 3.36 | 3.73 | 3.81 | 3.85 | 3.87 | 4.00 | 4.01 | 4.03 | 4.07 | 4.08 | |
85 | Total capacity | 42.6 | 48.7 | 50.2 | 54.5 | 60.4 | 47.6 | 52.2 | 53.7 | 57.6 | 63.0 | 52.5 | 55.5 | 57.2 | 60.6 | 65.5 |
Sensible capacity | 42.6 | 41.5 | 36.6 | 36.4 | 30.0 | 47.6 | 47.3 | 40.8 | 40.2 | 31.8 | 52.5 | 52.9 | 44.9 | 43.9 | 33.4 | |
kW | 3.36 | 3.76 | 3.91 | 4.00 | 4.05 | 3.86 | 4.06 | 4.14 | 4.21 | 4.25 | 4.39 | 4.41 | 4.42 | 4.46 | 4.50 | |
95 | Total capacity | 42.6 | 46.3 | 46.8 | 52.6 | 57.4 | 46.5 | 50.2 | 50.1 | 55.5 | 60.2 | 50.2 | 53.9 | 53.4 | 58.2 | 62.7 |
Sensible capacity | 42.6 | 40.0 | 33.9 | 34.3 | 27.9 | 46.5 | 45.8 | 38.5 | 38.8 | 30.0 | 50.2 | 51.6 | 43.0 | 43.1 | 31.9 | |
kW | 3.97 | 4.03 | 4.19 | 4.34 | 4.39 | 4.36 | 4.40 | 4.48 | 4.58 | 4.63 | 4.78 | 4.81 | 4.81 | 4.85 | 4.91 | |
105 | Total capacity | 38.2 | 41.2 | 39.8 | 48.5 | 53.4 | 42.9 | 45.9 | 44.2 | 52.1 | 56.1 | 47.4 | 50.4 | 48.6 | 55.5 | 58.6 |
Sensible capacity | 38.2 | 35.6 | 29.4 | 32.1 | 25.1 | 42.9 | 41.4 | 34.1 | 37.0 | 27.5 | 47.4 | 47.2 | 38.8 | 41.6 | 29.7 | |
kW | 4.09 | 4.17 | 4.05 | 4.67 | 4.80 | 4.73 | 4.75 | 4.54 | 5.14 | 5.07 | 5.34 | 5.41 | 5.11 | 5.63 | 5.41 | |
115 | Total capacity | 33.7 | 36.0 | 32.7 | 44.3 | 49.3 | 39.3 | 41.5 | 38.3 | 48.6 | 51.9 | 44.5 | 46.9 | 43.7 | 52.8 | 54.5 |
Sensible capacity | 32.9 | 31.2 | 24.8 | 29.9 | 22.2 | 38.0 | 37.0 | 29.7 | 35.1 | 24.9 | 42.9 | 42.7 | 34.5 | 40.1 | 27.5 | |
kW | 4.20 | 4.30 | 3.90 | 5.00 | 5.20 | 5.10 | 5.10 | 4.60 | 5.70 | 5.50 | 5.90 | 6.00 | 5.40 | 6.40 | 5.90 | |
125 | Total capacity | 22.2 | 23.3 | 18.9 | 30.8 | 34.8 | 27.3 | 28.5 | 24.4 | 34.9 | 37.0 | 32.3 | 33.5 | 29.7 | 38.9 | 39.0 |
Sensible capacity | 22.2 | 23.3 | 18.1 | 25.0 | 17.4 | 27.3 | 28.5 | 22.6 | 30.1 | 20.1 | 32.3 | 33.5 | 27.1 | 35.0 | 22.7 | |
kW | 2.82 | 2.82 | 2.31 | 3.52 | 3.68 | 3.55 | 3.57 | 2.98 | 4.13 | 3.93 | 4.33 | 4.35 | 3.69 | 4.77 | 4.21 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 4 ton
Table 14: Heating performance data - 4 ton - adjust DIP switch setting on 60k to configure 48k
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 51.2 | 46.0 | 41.8 | 40.1 | 35.5 | 34.6 | 34.0 | 31.0 | 28.0 | 25.0 |
kW | 3.9 | 3.85 | 3.90 | 3.92 | 3.97 | 4.42 | 4.75 | 4.53 | 4.32 | 4.11 |
COP | 3.83 | 3.50 | 3.14 | 3.00 | 2.62 | 2.30 | 2.10 | 2.00 | 1.90 | 1.78 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.
Performance Data - 5 ton
See the following tables for cooling and heating performance data for the HH860E2S11 unit.
Cooling performance data - 5 ton
Table 15: Cooling performance data - 5 ton
Air temperature entering outdoor unit (°F) | Indoor CFM 1200 | Indoor CFM 1600 | Indoor CFM 2000 | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Indoor dry bulb (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | |
Indoor wet bulb (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
55 | Total capacity | 40.0 | 54.8 | 55.5 | 60.1 | 62.3 | 47.8 | 57.8 | 58.3 | 64.2 | 64.6 | 55.5 | 60.6 | 60.9 | 68.1 | 66.8 |
Sensible capacity | 40.0 | 47.5 | 39.9 | 41.0 | 31.3 | 47.8 | 51.7 | 42.5 | 43.8 | 32.40 | 55.5 | 55.8 | 44.9 | 46.5 | 33.2 | |
kW | 1.70 | 2.91 | 2.91 | 2.91 | 2.82 | 2.35 | 3.09 | 3.08 | 3.08 | 3.03 | 3.04 | 3.31 | 3.30 | 3.28 | 3.28 | |
65 | Total capacity | 41.2 | 53.0 | 54.5 | 58.2 | 62.8 | 48.2 | 56.0 | 57.8 | 61.9 | 65.2 | 55.1 | 58.8 | 61.0 | 65.5 | 67.5 |
Sensible capacity | 41.2 | 45.3 | 39.6 | 39.7 | 31.7 | 48.2 | 50.2 | 42.8 | 42.7 | 33.0 | 55.1 | 55.0 | 45.8 | 45.6 | 34.1 | |
kW | 2.23 | 3.20 | 3.27 | 3.29 | 3.26 | 2.85 | 3.41 | 3.45 | 3.46 | 3.45 | 3.52 | 3.66 | 3.66 | 3.68 | 3.68 | |
75 | Total capacity | 42.5 | 51.2 | 53.6 | 56.4 | 63.3 | 48.7 | 54.2 | 57.4 | 59.7 | 65.8 | 54.8 | 57.1 | 61.0 | 62.9 | 68.2 |
Sensible capacity | 42.5 | 43.1 | 39.2 | 38.4 | 32.1 | 48.7 | 48.7 | 43.0 | 41.6 | 33.6 | 54.8 | 54.3 | 46.7 | 44.7 | 34.9 | |
kW | 2.76 | 3.49 | 3.63 | 3.66 | 3.70 | 3.36 | 3.73 | 3.81 | 3.85 | 3.87 | 4.00 | 4.01 | 4.03 | 4.07 | 4.08 | |
85 | Total capacity | 42.6 | 48.7 | 50.2 | 54.5 | 60.4 | 47.6 | 52.2 | 53.7 | 57.6 | 63.0 | 52.5 | 55.5 | 57.2 | 60.6 | 65.5 |
Sensible capacity | 42.6 | 41.5 | 36.6 | 36.4 | 30.0 | 47.6 | 47.3 | 40.8 | 40.2 | 31.8 | 52.5 | 52.9 | 44.9 | 43.9 | 33.4 | |
kW | 3.36 | 3.76 | 3.91 | 4.00 | 4.05 | 3.86 | 4.06 | 4.14 | 4.21 | 4.25 | 4.39 | 4.41 | 4.42 | 4.46 | 4.50 | |
95 | Total capacity | 42.6 | 46.3 | 46.8 | 52.6 | 57.4 | 46.5 | 50.2 | 50.1 | 55.5 | 60.2 | 50.2 | 53.9 | 53.4 | 58.2 | 62.7 |
Sensible capacity | 42.6 | 40.0 | 33.9 | 34.3 | 27.9 | 46.5 | 45.8 | 38.5 | 38.8 | 30.0 | 50.2 | 51.6 | 43.0 | 43.1 | 31.9 | |
kW | 3.97 | 4.03 | 4.19 | 4.34 | 4.39 | 4.36 | 4.40 | 4.48 | 4.58 | 4.63 | 4.78 | 4.81 | 4.81 | 4.85 | 4.91 | |
105 | Total capacity | 38.2 | 41.2 | 39.8 | 48.5 | 53.4 | 42.9 | 45.9 | 44.2 | 52.1 | 56.1 | 47.4 | 50.4 | 48.6 | 55.5 | 58.6 |
Sensible capacity | 38.2 | 35.6 | 29.4 | 32.1 | 25.1 | 42.9 | 41.4 | 34.1 | 37.0 | 27.5 | 47.4 | 47.2 | 38.8 | 41.6 | 29.7 | |
kW | 4.09 | 4.17 | 4.05 | 4.67 | 4.80 | 4.73 | 4.75 | 4.54 | 5.14 | 5.07 | 5.34 | 5.41 | 5.11 | 5.63 | 5.41 | |
115 | Total capacity | 33.7 | 36.0 | 32.7 | 44.3 | 49.3 | 39.3 | 41.5 | 38.3 | 48.6 | 51.9 | 44.5 | 46.9 | 43.7 | 52.8 | 54.5 |
Sensible capacity | 32.9 | 31.2 | 24.8 | 29.9 | 22.2 | 38.0 | 37.0 | 29.7 | 35.1 | 24.9 | 42.9 | 42.7 | 34.5 | 40.1 | 27.5 | |
kW | 4.20 | 4.30 | 3.90 | 5.00 | 5.20 | 5.10 | 5.10 | 4.60 | 5.70 | 5.50 | 5.90 | 6.00 | 5.40 | 6.40 | 5.90 | |
125 | Total capacity | 22.2 | 23.3 | 18.9 | 30.8 | 34.8 | 27.3 | 28.5 | 24.4 | 34.9 | 37.0 | 32.3 | 33.5 | 29.7 | 38.9 | 39.0 |
Sensible capacity | 22.2 | 23.3 | 18.1 | 25.0 | 17.4 | 27.3 | 28.5 | 22.6 | 30.1 | 20.1 | 32.3 | 33.5 | 27.1 | 35.0 | 22.7 | |
kW | 2.82 | 2.82 | 2.31 | 3.52 | 3.68 | 3.55 | 3.57 | 2.98 | 4.13 | 3.93 | 4.33 | 4.35 | 3.69 | 4.77 | 4.21 |
Cooling performance data notes:
- All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
- Drive output is limited in the shaded area. Performance may vary and interpolation is not permissible.
Heating performance data - 5 ton
Table 16: Heating performance data - 5 ton
Heating performance | Outdoor ambient temperature | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
60 | 47 | 35 | 30 | 17 | 10 | 5 | 0 | -5 | -10 | |
MBH | 57.6 | 54.0 | 47.3 | 44.5 | 37.2 | 38.0 | 38.5 | 35.6 | 32.4 | 29.3 |
kW | 4.7 | 4.65 | 4.45 | 4.36 | 4.13 | 5.01 | 5.64 | 4.99 | 4.69 | 4.41 |
COP | 3.56 | 3.40 | 3.12 | 2.99 | 2.64 | 2.22 | 2.00 | 2.09 | 2.03 | 1.95 |
Heating performance data notes:
- Calculations are based on a nominal CFM and an indoor dry bulb temperature of 70°F.
- kW indicates total system power.
- The shaded area represents the AHRI rating conditions at an outdoor ambient temperature of 47°F.
- The performance data provided is only for reference and is derived from AHRI nominal data. In certain applications, actual performance may deviate from these values.